GENERAL NOTES:

1. CONTRACTOR IS RESPONSIBLE FOR AND SHALL VERIFY ANDCOORDINATE ALL DIMENSIONS AND DETAILS BEFORE PROCEEDING WITHWORK. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATEATTENTION OF THE ARCHITECT AND ENGINEERS.

2. DETAILS SHOWN IN ANY SECTION APPLY TO ALL SIMILAR SECTIONS ANDCONDITIONS UNLESS NOTED OTHERWISE.

3. CONTRACTOR SHALL FULLY BRACE AND OTHERWISE PROTECT ALL WORKIN PROGRESS UNTIL THE BUILDING IS COMPLETED.

4. ALL STRUCTURAL ITEMS FOR THIS PROJECT HAVE BEEN DESIGNED INACCORDANCE WITH APPROPRIATE PROVISIONS OF EACH OF THEFOLLOWING:

A. THE FLORIDA BUILDING CODE, (FIFTH EDITION) 2014.B. ACI STANDARD 318-11 BUILDING CODE REQUIREMENTS FOR

REINFORCED CONCRETE.C. BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI

530-11/ASCE 7-10/TMS 402-11).D. AISC "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION

OF STRUCTURAL STEEL FOR BUILDINGS" 360-10.E. AMERICAN FOREST AND PAPER ASSOCIATION, NATIONAL DESIGN

SPECIFICATION 2007 EDITION.F. ASCE 7-10 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER

STRUCTURES".

5. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITHTHE SPECIFICATIONS AND THE ARCHITECTURAL AND MECHANICALDRAWINGS. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS THECONTRACTOR'S RESPONSIBILITY TO NOTIFY THE ARCHITECT PRIOR TOPERFORMING WORK. IN CASE OF CONFLICT THE MOST STRINGENTCONDITION SHALL APPLY.

6. ALL DIMENSIONS MUST BE COORDINATED WITH ARCHITECTURALDRAWINGS AND WITH EQUIPMENT MANUFACTURER (I.E. WINDOW, DOOR,AIR HANDLER, ETC.). CONTRACTOR MUST OBTAIN AN ARCHITECTURALDIRECTIVE IN CASE OF ANY CONFLICT. REFER TO ARCHITECTURALDRAWINGS FOR DIMENSIONS NOT SHOWN IN STRUCTURAL DRAWINGS.

7. ROOFTOP EQUIPMENT ANCHORAGE & OUTDOOR RACK MOUNTED EQUIPMENTANCHORAGE. ALL ROOF TOP EQUIPMENT CURBS, ROOF TOP MECHANICALEQUIPMENT, EQUIPMENT TIE DOWNS, AND CONNECTIONS OF ALL EQUIPMENT TOOUTDOOR RACKS OR BUILDING STRUCTURE FOR WIND LOADING ARE TO BEDESIGNED AND ENGINEERED BY A REGISTERED SPECIALTY ENGINEER RETAINEDBY THE MECHANICAL EQUIPMENT SUPPLIER. SIGNED AND SEALED DRAWINGSAND CALCULATIONS ARE TO BE SUBMITTED TO THE ENGINEER OF RECORD FORREVIEW AND APPROVAL. THE EQUIPMENT MANUFACTURER SHALL PROVIDE THEATTACHMENT OF THE UNIT TO THE STRUCTURE AND SUBMIT TO THE ENGINEERLOADS, LOCATIONS, AND METHODS OF ATTACHMENT. THE STRUCTURAL ENGINEERWILL MAKE PROVISIONS IN THE DESIGN OF THE PRIMARY STRUCTURAL FRAME TOACCOMMODATE THE LOADS AND ATTACHMENTS SUBMITTED BY THE MANUFACTURER.

CONCRETE AND REINFORCING:

1. ALL CONCRETE WORK SHALL CONFORM TO THE LATEST ACI "BUILDINGCODE REQUIREMENTS FOR REINFORCED CONCRETE, ACI-318".

2. ALL CONCRETE SHALL HAVE A MINIMUM 28-DAY COMPRESSIVESTRENGTHS AS INDICATED BELOW:

CONCRETE MAX WATER TYPESTRENGTH CEMENT RATIO AGGREGATE LOCATION USED

4000 PSI 0.45 STONE CONCRETE U.N.O.3000 PSI 0.52 STONE SLAB ON GRADE

&FOUNDATIONS3. ALL REINFORCING STEEL SHALL BE INTERMEDIATE GRADE, NEW BILLET

STEEL, DEFORMED BARS, CONFORMING TO ASTM A-615, GRADE 60.ALL BARS SHALL BE SECURELY SUPPORTED AND WIRED IN PLACE.PRIOR TO POURING CONCRETE. ALL REINFORCING STEEL TO BE WELDEDSHALL CONFORM TO ASTM A-706.

4. ALL WELDED WIRE FABRIC (W.W.F.) IN FLAT SHEETS ONLY AND SHALLCONFORM TO ASTM A-185.

5. UNLESS NOTED, ALL BARS MARKED CONTINUOUS SHALL BE SPLICED ATALL LAP POINTS AND CORNERS AND DEVELOPED AT NON-CONTINUOUSENDS AS PER TYPICAL DETAILS. SPLICE CONTINUOUS TOP BARS ATCENTER BETWEEN SUPPORTS AND SPLICE CONTINUOUS BOTTOM BARSAT SUPPORTS.

6. CONCRETE COVER FOR REINFORCING BARS SHOWN IN TYPICAL DETAILS.7. UNLESS NOTED, TEMPERATURE REINFORCING (ASTM A-615-60) TO BE

0.0018 X CONCRETE AREA.8. PROVIDE #4 @ 12" O.C., WITH STANDARD HOOK, TOP BARS IN ALL SLABS

AT DISCONTINUOUS ENDS UNLESS OTHERWISE NOTED ON PLANS.LENGTH OF BARS 1/4 OF SPAN, MINIMUM 3'-0". UNLESS OTHERWISENOTED PROVIDE #4 @ 12" O.C IN ALL CANTILEVERS. BAR LENGTHSHALL BE CANTILEVER SPAN PLUS 10'-0" PLUS STANDARD HOOK ATCANTILEVER ENDS.

9. WHERE PIPE SLEEVES (UP TO 2" IN DIAMETER) PASS THROUGHCONCRETE BEAMS, PROVIDE ADDITIONAL STIRRUP EACH SIDE OFSLEEVE, SLEEVES FOR PIPES 2" IN DIAMETER OR LARGER MUST BESTEEL OR CAST IRON, AND THE LOCATION MUST BE APPROVED BY THESTRUCTURAL ENGINEER.

10. ALL CONSTRUCTION JOINTS SHALL BE THOROUGHLY CLEANED JUSTBEFORE PLACING NEW CONCRETE IN ACCORDANCE WITH THE BUILDINGCODE.

11. FOR CHAMFER OF EXPOSED CORNERS OF BEAMS AND/OR COLUMNS,SEE ARCHITECTURAL DRAWINGS.

12. CONTRACTOR SHALL COORDINATE PLACEMENT OF, OR BOX OUT FOR,ALL PIPE SLEEVES, OPENINGS, ETC, REQUIRED FOR VARIOUS TRADES.

13. CONTRACTOR SHALL COORDINATE AND NOTIFY OTHER TRADES INSUFFICIENT TIME TO ALLOW THEM TO SET ANCHORS, INSERTS, BOLTS,HANGERS, ETC., AS REQUIRED FOR THEIR USE.

14. SEE ARCHITECTURAL DRAWINGS FOR DETAILS OF FLASHING REGLETS,FASCIA DETAILS, ETC.

15. UNDER NO CIRCUMSTANCES SHALL CONCRETE BE PUMPED THROUGHALUMINUM PIPES. CONCRETE SHALL NOT BE PLACED IN CONTACT WITHALUMINUM, ALUMINUM MIXING DRUMS, TRUCK MIXERS, BUGGIES,CHUTES, CONVEYORS, TREMIE PIPES, AND OTHER EQUIPMENT MADE OFALUMINUM SHALL NOT BE USED ON THIS PROJECT.

16. SLUMPS OF OVER 4 INCHES WILL NOT BE PERMITTED UNLESS THEHRWR ADMIXTURE (SUPER PLASTICIZER) IS USED. MAXIMUM SLUMP ISTHEN 8 INCHES UNLESS OTHERWISE DIRECTED BY THE ENGINEER.

17. NO ADMIXTURE SHALL BE USED IN CONCRETE EXCEPT WITH THEPERMISSION OF THE ENGINEERS AND AFTER LABORATORY DESIGN MIXAPPROVAL. ALL ADMIXTURES SHALL CONTAIN NO MORE CHLORIDE IONSTHAN ARE PRESENT IN MUNICIPAL DRINKING WATER.

18. WATER REDUCING ADMIXTURE SHALL CONFORM TO THE ASTM C-494,TYPE A, AND SHALL BE USED IN ALL CONCRETE.

19. AIR ENTRAINING ADMIXTURE SHALL CONFORM TO ASTM C260. AIRCONTENT OF CONCRETE SHALL BE USED AS FOLLOWS:

A. FOR CONCRETE EXPOSED TO SOIL AND/OR WEATHER, 5%.B. FOR INTERIOR WALLS, COLUMNS, AND SLABS, 3%.

20. FLY ASH - ASTMC618, TYPE C OR TYPE F SHOULD BE USED BUT NOT TOEXCEED 20% CEMENTITIOUS CONTENT.

21. ALL EXPOSED CONCRETE SLABS SHALL RECEIVE A CURING COMPOUND.THE CURING COMPOUND SHALL CONFORM TO ASTM C309 AND SHALLHAVE 30% SOLIDS MINIMUM. WATER/BLANKET CURING AS PER ACIRECOMMENDATION MAY BE USED AS ALTERNATE.

FOUNDATION NOTES:

1. SITE SOIL FOR THIS PROJECT HAS BEEN INVESTIGATED BY THE FIRM OFDRIGGERS ENGINEERING SERVICES INC. AND FOUND, AS PRESENTED INTHEIR REPORT DATED MARCH 25, 2016, SUITABLE TO SUPPORT 2.5 KSFSPREAD FOOTINGS. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCEWITH THE ABOVE STATED CRITERIA.

2. FILL AND SUBGRADE PREPARATION SHALL BE IN ACCORDANCE WITHTHE GEOTECHNICAL ENGINEER RECOMMENDATION AS CONTAINED INTHEIR REPORT STATED IN ITEM 1.

3. ALL COLUMN FOOTINGS SHALL BE CENTERED UNDER COLUMNCENTERLINES UNLESS OTHERWISE NOTED.

4. BACKFILLING AGAINST FOUNDATION WALLS SHALL BE DONE CAREFULLYWITH SMALL COMPACTION EQUIPMENT, AFTER SLABS ON GROUND AREIN PLACE AND CONCRETE HAS SET. NO TRUCKS, BULLDOZERS, ETC.SHALL BE ALLOWED CLOSER THAN 6'-0" TO ANY FOUNDATION WALL.ANY WALL 3'-0" OR HIGHER MUST BE BRACED DURING THECONSTRUCTION PROCESS.

5. NO FOUNDATIONS SHALL BE PLACED ABOVE 1 VERTICAL ON 2 HORIZONTALSLOPES EXTENDED FROM THE CLOSEST EDGE OF ANY UNDISTURBED SOILOR OTHER FOUNDATION STRUCTURE. BOTTOM OF FOOTINGS SHALL NOTBE LESS THAN 1'-0" BELOW EXISTING GRADE (U.N.O.).

6. FOR FOUNDATIONS SIZE AND REINFORCING SEE SCHEDULE.7. CONTRACTOR SHALL TREAT SOIL BENEATH BUILDING FOR TERMITES.

MASONRY/INTERSTATE ATLAS BRICK:

1. DESIGN AND CONSTRUCTION SHALL CONFORM TO BUILDING CODEREQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-10 ASCE 7-10) / TMS402-11 AND SPECIFICATIONS FOR MASONRY STRUCTURES ACI 530.1-11 /ASCE 7-10 (WITH ERRATA DATED JANUARY 10, 2011).

2. MINIMUM NET COMPRESSIVE STRENGTH OF BLOCK ASSEMBLY SHALLBE 1500 P.S.I. (f'm) MORTAR FOR MASONRY SHALL BE TYPE "S" OR "M".

2a. MINIMUM NET COMPRESSION STRENGTH OF BRICK SHALL BW 3000PSI (fm)& MORTAR FOR BRICK SHALL BE TYPE "S" OR "M"

3. FOR ALL EXTERIOR AND INTERIOR BEARING, BED JOINTS ARE TO COVER100% OF THE MASONRY SURFACES AND ALL HEAD JOINTS ARE TOCOVER 100% OF THE PROJECTED AREA OF THE FACE SHELLS.

4. FILL ALL CELLS AS REQUIRED WITH 3000 P.S.I. GROUT. SLUMP SHALLBE 8 TO 11 INCHES. SUBMIT DESIGN MIX FOR APPROVAL.

5. MINIMUM HORIZONTAL JOINT REINFORCING SHALL BE 9 GAGE HOT DIPGALVANIZED TRUSS OR LADDER TYPE JOINT REINFORCING AT 16" O.C.,PROVIDE MANUFACTURE "T" AND "L" SHAPES FOR INTERSECTIONS ANDCORNERS, (MINIMUM LAP 8").

6. MINIMUM VERTICAL REINFORCING SHALL BE 1-#5 @ 48" OR 1-#4 @32" O.C., (U.N.O.).

7. PROVIDE ADDITIONAL VERTICAL REINFORCING BAR AT EVERY CORNER,INTERSECTION, CONTROL JOINT, AND OPENING EDGES (U.N.O.).

8. MINIMUM SPLICE FOR VERTICAL REINFORCING IS SHOWN IN DETAIL 4-023,SPLICE FOR HORIZONTAL JOINT REINFORCING = 12".

9. WALLS ARE DESIGNED TO BE BRACED BY FLOOR OR ROOF MEMBERS,CONTRACTOR SHALL PROVIDE TEMPORARY BRACING DURINGCONSTRUCTION.

10. ALL CELLS BELOW FIRST FLOOR FINISHED ELEVATION MUST BE FULLYGROUT FILLED.

11. ALL KNOCK OUT BLOCK HORIZONTAL BARS SHALL HAVE CORNER BARSAT ALL CORNERS AND WALL INTERSECTIONS. SIZE AND NUMBER OFCORNER BARS SHALL BE SAME AS HORIZONTAL BARS.

12. ALL INTERSECTING WALLS AND CORNER WALLS SHALL BE LAID IN ANOVERLAPPING MASONRY BONDING PATTERN, WITH ALTERNATE UNITSHAVING A BEARING OF NOT LESS THAN 3 INCHES ON UNIT BELOW.

STEEL JOIST:

1. STEEL JOIST CONSTRUCTION SHALL CONFORM TO THE LATESTSPECIFICATIONS OF, AND THE JOISTS SHALL BE APPROVED BY, THESTEEL JOIST INSTITUTE.

2. UNLESS OTHERWISE NOTED, BEAR SHORT SPAN JOISTS MINIMUM OF2-1/2" ON STEEL BEAMS AND BEAR LONG SPAN JOIST MINIMUM OF 4"ON STEEL SUPPORTS. IN CASES WHERE JOISTS BEAR ON BEAMSFROM ONE SIDE ONLY, JOIST SEATS SHALL EXTEND A MINIMUM OF 1"PAST THE CENTERLINE OF SUPPORTING BEAM.

3. ALL JOISTS BEARING ON BEAMS SHALL BE WELDED OR BOLTED TOTHOSE BEAMS.

4. PROVIDE BRIDGING FOR ALL JOISTS AS SHOWN ON PLAN BUT NOTLESS THAN WHAT IS REQUIRED BY THE STEEL JOIST INSTITUTE ORTHE STEEL JOIST DESIGNER. BRIDGING SHALL CONSIST OF MINIMUM1-1/4" X 1-1/4" X 7/64" ANGLES, (U.N.0.).

5. ALL BRIDGING SHALL BE PROVIDED AND INSTALLED BY JOIST SUPPLIER.6. ALL CLIPS AND CONNECTIONS SHALL BE SHOP WELDED.7. NO FIELD WELDING TO BAR JOISTS EXCEPT ITEMS SPECIFICALLY

SHOWN ON STRUCTURAL DRAWINGS SHALL BE ALLOWED WITHOUTSPECIFIC PERMISSION FROM THE ENGINEER.

8. NO JOIST SHALL BE FIELD SPLICED.9. MAXIMUM DEFLECTION OF STEEL JOISTS = L/240.10. FOR PAINTING OF STEEL JOIST, SEE SPECIFICATIONS.11. JOIST MANUFACTURER SHALL SUBMIT WITH THE SHOP DRAWINGS HIS

CATALOG USED FOR THE MANUFACTURE OF JOISTS, INDICATING THELOAD TABLES AND SIZES OF ALL MEMBERS USED.

12. NO LOADS EXCEEDING 40 POUNDS MAY BE HUNG FROM JOISTSWITHOUT SPECIFIC PERMISSION FROM THE STRUCTURAL ENGINEER.LOADS LESS THAN 40 POUNDS MAY BE HUNG AT PANEL POINTS ONLY.ANY COST INVOLVED IN REINFORCING OF JOISTS SHALL BE BORNE BYTHE PRIME CONTRACTOR REQUIRING ADDED LOADS.

13. ALL SHORT SPAN JOISTS, AND DEEP LONG SPAN JOISTS SHALL HAVEUNIFORM CROSS SECTION, WITH STANDARD DEAD LOAD CAMBER.ROOF PITCH IS ACCOMPLISHED BY SLOPED JOISTS AND SUPPORT BEAMS.ADJUST JOIST SEATS AS SHOWN ON DRAWINGS.

14. FOR SPECIFIC JOIST ENDS, SEE ROOF SECTIONS.15. RIGID CONNECTIONS OF BOTTOM CHORDS OF JOISTS TO COLUMNS

SHALL BE MADE ONLY AFTER THE APPLICATION OF ALL THE DEADLOADS. PROVIDE LOOSE BOLTED CONNECTION OF THESE BOTTOMCHORDS DURING ERECTION.

STEEL ROOF DECK:

1. STEEL ROOF DECK SHALL BE A MINIMUM OF 1-1/2" - 20 GAGE WIDERIB FOR SPANS UP TO 6'-0" OR 3" TYPE N - 20 GAGE FOR SPANS UPTO 12'-0" . THE SIZE, TYPE AND GAGE INDICATED ABOVE SHOULD BEUSED UNLESS A DIFFERENT ONE IS INDICATED IN THE ROOF FRAMINGNOTES OF THE ROOF PLAN DRAWING.

2. ALL STEEL ROOF DECK SHALL BE GALVANIZED G90 AS PER ASTMSPECIFICATIONS.

3. ALL STEEL ROOF DECK SHALL BE CAPABLE OF SUPPORTING ALLCONSTRUCTION LOADS.

4. ALL STEEL ROOF DECK SHALL BE CONTINUOUS OVER FOUR OR MORESTRUCTURAL SUPPORTS (I.E. DECK SHOULD BE DETAILED FOR A THREESPAN CONDITION.)

5. STEEL ROOF DECK SHALL HAVE NESTING SIDE LAPS (ATTACHED BYMECHANICAL MEANS). PROVIDE FASTENER LAYOUT AS PER DETAIL5-305 ON DRAWING S3.05.

6. IF DECK IS CUT IN SINGLE SPAN CONDITION, EACH END OF SUCHSECTIONS SHALL BE WELDED TO ITS SUPPORT THROUGH WELDINGWASHERS IN THE BOTTOM OF EACH RIB.

7. IN AREAS WHERE THE DECK IS CUT AS PER NOTE 6, THE GAGE OFTHE SINGLE SPAN DECK SHALL BE ADJUSTED UPWARDS AS REQUIREDBY THE ENGINEER TO SUPPORT THE LOADS.

8. ANY ELECTRICAL WORK WEIGHING MORE THAN 5 PSF OR 50 LBSCONCENTRATED SHALL BE HUNG FROM STEEL BEAMS ONLY. FORHANGERS, SEE SPECIFICATIONS. ALL MECHANICAL WORK AND PIPINGSHALL BE HUNG FROM STEEL BEAMS. SEE STRUCTURAL STEEL NOTE12 (OF STRUCTURAL STEEL NOTES) FOR ADDITIONAL STEEL REQUIREDBY MECHANICAL/ELECTRICAL TRADES TO SUPPORT THEIR EQUIPMENT.

9. METAL DECK CONTRACTOR TO PROVIDE 18 GAGE RIDGE PLATE, VALLEYPLATE, EDGE STRIP, ETC., AS REQUIRED.

10. STEEL ROOF DECK SHALL BE WELDED AT ENDS AND ALL INTERMEDIATESUPPORTING MEMBERS WITH 5/8" DIAMETER PUDDLE WELDS ORELONGATED WELDS OF EQUAL STRENGTH SPACED PER SPECIFICATIONSIN THE BOTTOM OF THE RIB ACROSS THE WIDTH OF THE DECK UNIT.

11. CUT OUT METAL DECK WHERE BOLT PROJECTIONS INTERFERE WITHMETAL DECK.

12. DIRECTION OF METAL DECK SHOWN THUS ON PLAN.

LIGHTGAUGE METAL FRAMING:

1. ALL STRUCTURAL MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITHAMERICAN IRON AND STEEL INSTITUTE, "SPECIFICATION FOR THE DESIGNOF COLD FORMED STRUCTURAL MEMBERS", 2007 EDITION WITH 2010SUPPLEMENTS. PROVIDE SIGN AND SEALED CALCULATIONS ANDDRAWINGS FOR ALL LIGHT GAUGE STRUCTURAL ELEMENTS OF THEBUILDING, INCLUDING THE EXTERIOR METAL STUDS (CURTAIN WALL),AND ALL EXTERIOR CEILINGS.

2. ALL STRUCTURAL STUDS AND JOISTS 22, 20, AND 18 GAUGES SHALL BEFORMED FROM GALVANIZED STEEL PER ASTM A653, G60 COATINGMEETING THE REQUIREMENTS OF ASTM C955 WITH A YIELD STRENGTHOF 33,000 PSI.

3. ALL STRUCTURAL STUDS AND JOISTS 16, 14, AND 12 GAUGES SHALL BEFORMED FROM GALVANIZED STEEL PER ASTM A653, G60 COATINGMEETING ASTM C955, WITH YIELD STRENGTH OF 50,000 PSI.

4. ALL STRUCTURAL TRACK AND BRIDGING SHALL BE FORMED FROMGALVANIZED STEEL PER ASTM A653, G60 COATING MEETING THEREQUIREMENTS OF ASTM C595, WITH YIELD STRENGTH OF 33,000 PSI.

5. WITH EACH TYPE OF METAL FRAMING REQUIRED, PROVIDEMANUFACTURER'S STANDARD STEEL RUNNERS (TRACKS), BLOCKING,LINTELS, CLIP ANGELS, SHOES, REINFORCEMENTS, FASTENERS, ANDACCESSORIES AS RECOMMENDED BY MANUFACTURER FORAPPLICATIONS INDICATED, AS NEEDED TO PROVIDE A COMPLETEMETAL FRAMING SYSTEM.

6. PROVIDE GALVANIZED FINISH TO METAL FRAMING COMPONENTSCOMPLYING WITH ASTM A653 FOR MINIMUM G60 COATING. ATTACHSIMILAR COMPONENTS BY WELDING. ATTACH DISSIMILAR COMPONENTSBY WELDING, BOLTING OR SCREW FASTENERS, AS STANDARD WITHMANUFACTURER. ALL WELDING SHALL BE PERFORMED BY WELDERSCERTIFIED AND EXPERIENCED IN LIGHT GAUGE STRUCTURAL STEELFRAMING WORK.

7. INSTALL METAL FRAMING SYSTEMS IN ACCORDANCE WITHMANUFACTURER'S PRINTED OR WRITTEN INSTRUCTIONS ANDRECOMMENDATIONS, UNLESS OTHERWISE INDICATED.

8. INSTALL CONTINUOUS TRACKS SIZED TO MATCH STUDS.9. SET STUDS PLUMB, EXCEPT AS NEEDED FOR DIAGONAL BRACING OR

REQUIRED FOR NON-PLUMB WALLS OR WARPED SURFACED ANDSIMILAR REQUIREMENTS.

10. WHERE STUD SYSTEM ABUTS STRUCTURAL COLUMN OR WALLS,INCLUDING MASONRY WALL, ANCHOR ENDS OF STIFFENERS TOSUPPORTING STRUCTURE.

11. SECURE STUDS TO TOP AND BOTTOM RUNNER TRACKS BY EITHERWELDING OR SCREW FASTENERS AT BOTH INSIDE AND OUTSIDEFLANGES.

GENERAL STRUCTURAL NOTESSHOP DRAWINGS:

1. NO STRUCTURAL DRAWINGS SHALL BE REPRODUCED FOR USE AS SHOPDRAWINGS.

2. ALL DIMENSIONAL COORDINATION SHALL BE DONE BY THE CONTRACTORAND/OR HIS DETAILER.

3. DETAILER SHALL CHECK ALL ARCHITECTURAL AND MECHANICALDRAWINGS FOR ALL ATTACHMENTS, CLIPS, OPENINGS, OR DUCT WORKAFFECTING STRUCTURAL MEMBERS. ALL ITEMS SHALL BE SHOWN ONSHOP DRAWINGS.

4. ALL SHOP DRAWINGS SHALL BE SUBMITTED ELECTRONICALLY IN PDFFORMAT. DISTRIBUTION AS PER ARCHITECT INSTRUCTIONS.

5. PROVIDE SUFFICIENT SPACE ON SHOP DRAWINGS NEAR TITLE BOX(ABOUT 40 SQUARE INCHES) FOR STAMPS AND ENGINEERS COMMENTS.

6. THE SHOP DRAWINGS SHALL BEAR INITIALS OF DETAILER'S CHECKERAND CONTRACTOR PRIOR TO SUBMISSION.

7. COMPLETED ERECTION PLANS SHALL BE SUBMITTED PRIOR TO OR INCONJUNCTION WITH DETAIL DRAWINGS. BUT IN NO CASE SHALL DETAILDRAWINGS BE SUBMITTED PRIOR TO ERECTION PLANS.

8. DETAILER SHALL SUBMIT AN INDEX OF THE DETAIL DRAWINGS WITHEACH SHOP DRAWING SUBMITTAL.

9. SHOP DRAWINGS NOT COMPLYING WITH ALL THE ABOVE ITEMS SHALLBE RETURNED FOR CORRECTIONS WITHOUT PROCESSING.

10. RESUBMITTED SHOP DRAWINGS SHALL HAVE THE FOLLOWING CHANGESINCORPORATED: FIRST RESUBMISSION TO HAVE LETTER "A" ADDED TODRAWING

A. NUMBER AND ANY CHANGES MARKED ON THE DRAWINGMARKED 1 AT EACH ITEM CHANGED. ALL ITEMS TO BE NOTED INREVISION BOX.

B. SUBSEQUENT RESUBMISSION SHALL BEAR CHANGES "B" AND 2 AND3 ETC. AS IN 11A.

11. CONTRACTOR SHALL HAVE SHOP DRAWINGS WHICH HAVE BEENSATISFACTORILY REVIEWED BY THE ARCHITECT AND/OR ENGINEER ANDCONFIRMED BY THE CONTRACTOR BEFORE PROCEEDING WITH ANY WORK.

12. DETAILER SHALL USE THE SAME STRUTURAL ELEMENTS NUMBERS IN HISDETAILS AS THOSE SHOWN ON CONTRACT DRAWINGS.

13. SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOULD BESUBMITTED TO MCE WITH A MINIMUM TIME TO BE REVIEWED OF 10WORKING DAYS. IN CASE OF A LARGE SUBMITTAL OR MORE THAN ONESUBMITTAL FOR THE SAME PROJECT, AN ADDITIONAL WORKING DAY ISREQUIRED FOR EVERY 5 DRAWINGS/SHEETS OVER 30 DRAWINGS/SHEETS.THE TIME INDICATED ABOVE IS FOR MCE REVIEW ONLY, CONTRACTOR MUSTINCLUDE ENOUGH TIME FOR DELIVERY, ARCHITECTURAL REVIEW, ANDOWNERS REVIEW AND WORK THIS TIME IN THE PROJECT SCHEDULE ASNEEDED.

14. THERE SHALL BE NO DEVIATION FROM THESE CONSTRUCTION DOCUMENTS.IF ANY CHANGES ARE PROPOSED BY THE CONTRACTOR OR THE PROVIDEROF THE SHOP DRAWINGS, THEY SHOULD BE CLEARLY INDICATED, SIGNEDAND SEALED DRAWINGS AND CALCULATIONS BY FLORIDA PROFESSIONALENGINEER MUST BE PROVIDED. ANY CHANGES WITHOUT PROPERDOCUMENTATION INDICATED ABOVE WILL RESULT IN SOME REVISIONS BYTHE ENGINEER OF RECORD AND/OR ARCHITECT. THE COST FOR THESEREVISIONS INCLUDING ENGINEER AND ARCHITECTURAL FEES SHALL BE PAIDBY THE CONTRACTOR.

STRUCTURAL STEEL:

1. ALL STRUCTURAL STEEL WORK SHALL BE FABRICATED AND ERECTED INACCORDANCE WITH THE LATEST A.I.S.C. SPECIFICATIONS.

2. STRUCTURAL STEEL SHALL CONFORM TO:

WIDE FLANGE (WF) ASTM A992 (50 KSI)SHAPES (L,T,C,PL) ASTM A36STRUCTURAL TUBE (HSS) ASTM A500 (46 KSI)STEEL PIPE (HSS) ASTM A500 (42 KSI)ANCHOR BOLTS ASTM F1554 (36 KSI)FRAMING BOLTS ASTM A325 OR A490SHEAR STUDS ASTM A108WELDING ELECTRODES E70XX

3. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM SPECIFICATIONA325 AND SHALL BE PROVIDED WITH HARDENED WASHERS UNDER THETURNED ELEMENT (NUT OR BOLT HEAD).

4. INSTALLATION AND TIGHTENING OF ALL HIGH STRENGTH BOLTS SHALLCONFORM TO THE "SPECIFICATION FOR STRUCTURAL JOINTS USINGASTM A325 OR A490 BOLTS".

5. SHOP CONNECTIONS MAY BE WELDED OR HIGH STRENGTH BOLTED.ALL BOLTS SHALL BE 3/4" DIAMETER MINIMUM. ALL CONNECTIONS SHALLCONFORM TO THE TYPICAL CONNECTION DETAILS SHOWN ON THEPLANS UNLESS SPECIFICALLY APPROVED BY THE ENGINEER.

6. ALL FIELD CONNECTIONS SHALL BE BOLTED WITH HIGH STRENGTHBOLTS, SLIP-CRITICAL (FRICTION) TYPE EXCEPT WHERE SLOTTED HOLESARE SPECIFIED OR WHERE MOVEMENT OF THE CONNECTED MEMBERS ISEXPECTED. IN THESE CASES PROVIDE OVERSIZED WASHER, HANDTIGHTEN BOLTS, AND TACK WELD WASHER TO NUT TO VERIFY ASSEMBLYIS HELD TOGETHER.

7. ALL WELDING SHALL CONFORM TO THE AMERICAN WELDING SOCIETYCODE, ANS01.1, ALL WELDING SHALL BE PERFORMED USING E7OXX U.N.O.

8. CUTS, HOLES, COPINGS, ETC. REQUIRED IN STRUCTURAL STEELMEMBERS FOR THE WORK OF OTHER TRADES SHALL BE SHOWN IN THESTRUCTURAL STEEL SHOP DRAWINGS AND SHALL BE MADE IN THE SHOP.HOLES SHALL BE REINFORCED AS REQUIRED BY THE ENGINEER.

9. BURNING OF HOLES, CUTS, ETC. IN STRUCTURAL STEEL MEMBERS IN THEFIELD WILL NOT BE PERMITTED, EXCEPT WITH THE SPECIFIC APPROVALOF THE ENGINEER.

10. ALL STEEL MEMBERS EXPOSED TO WEATHER (SUCH AS LINTELS, DOORJAMBS, ETC.) SHALL BE HOT DIPPED GALVANIZED.

11. FOR MISCELLANEOUS STEEL, SEE ARCHITECTURAL DRAWINGS.12. ANY STEEL MEMBERS REQUIRED BY THE ELECTRICAL OR MECHANICAL

TRADES FOR THE SUPPORT OF THEIR EQUIPMENT, WHICH ARE NOTSHOWN ON ARCHITECTURAL OR STRUCTURAL DRAWINGS, SHALL BEPROVIDED BY THE TRADE REQUIRING SUCH SUPPORT.

13. SEE SPECIFICATIONS FOR PAINTING OF STRUCTURAL STEEL. ALLFABRICATION AND ERECTION MARKS SHALL BE COVERED DURING FIELDTOUCH-UP PAINTING.

14. ALL CONNECTIONS TO BE DOUBLE ANGLE FRAMED BEAM CONNECTIONPER AISC UNLESS NOTED OTHERWISE. ALL BOLTS TO BE 3/4" MINIMUMDIAMETER UNLESS NOTED OTHERWISE. SHOP CONNECTIONS MAY BEWELDED OR BOLTED. WELDS ARE TO BE EQUAL IN STRENGTH TO BOLTS.

15. DESIGN CONNECTIONS FOR THE MAXIMUM SHEAR (V IN KIPS) LISTED INTHE TABLES FOR "ALLOWABLE UNIFORM LOADS IN KIPS FOR BEAMSLATERALLY SUPPORTED" AT THE BOTTOM OF EACH PAGE IN THE"PROPERTIES AND REACTION VALUES", PART 2 OF THE LATEST EDITIONOF THE AISC "MANUAL OF STEEL CONSTRUCTION". PROVIDE SIGNEDAND SEALED DRAWINGS AND CALCULATIONS BY A PROFESSIONALENGINEER.

16. WHEN STEEL MEMBERS ARE WELDED TO EMBED PLATES IN CONCRETE,WELDING PROCESS SHOULD BE PERFORMED IN SUCH WAY THAT EMBEDPLATE DOES NOT OVERHEAT AND EXPAND. SUCH EXPANSION WILLCRACK THE CONCRETE SURROUNDING THE EMBED PLATE AND MAYWEAKEN THE STRUCTURAL CAPACITY OF THE CONNECTION. WERECOMMEND TO PROVIDE SEVERAL SINGLE PASSES TO BUILT UP THEWELD SIZE REQUIRE WITH COOLING OFF PERIODS TO AVOID THE EMBEDPLATE EXPANSION. UNDER NO CIRCUMSTANCES PROVIDE MORE THAN 6"OF 1/4" WELD WITHOUT ALLOWING A COOLING OFF PERIOD.

POST -INSTALLED ANCHORS

1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIEDON THE CONSTRUCTION DOCUMENTS. SPECIAL INSPECTIONS AREREQUIRED PER THE PROVISIONS SET FORTH BELOW. CONTRACTORTO CONTACT MANUFACTURER'S REPRESENTATIVE FOR PROPERPRODUCT INSTALLATION TRAINING ON INITIAL ANCHORS.

2. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSESPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TOTHE ENGINEER-OF-RECORD ALONG WITH CALCULATIONS THAT AREPREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER.THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTEDPRODUCT IS CAPABLE OF ACHIEVING THE PERTINENT EQUIVALENTPERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USINGTHE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) ASREQUIRED BY THE BUILDING CODE.

3. EXPANSION ANCHORS SHALL BE STUD TYPE WITH A SINGLE PIECE OFTHREE SECTION WEDGE AND ZINC PLATED IN ACCORDANCE WITHASTM B633. THE ANCHORS SHALL MEET FEDERAL SPECIFCATIONFF-S-325, GROUP II, TYPE 4, CLASS I FOR CONCRETE EXPANSIONANCHORS. ANCHORS SHALL BE HILTI KWIK BOLT II AS SUPPLIED BYHILTI INC. TULSA OKLAHOMA. ANCHORS SHALL BE INSTALLED IN HOLESDRILLED WITH HILTI CARBIDE TIPPED DRILL BITS OR MATCHEDTOLERANCE DIAMOND CORE BITS. ANCHORS SHALL BE INSTALLED INACCORDANCE WITH MANUFACTURE'S RECOMMENDATIONS.

4. INJECTED ADHESIVE ANCHORS SHALL BE USED FOR INSTALLATION OFTHREADED RODS. ADHESIVE SHALL BE FURNISHED IN A SIDE BY SIDEREFILL PACK WHICH KEEP COMPONENT A AND B SEPARATE. INJECTIONADHESIVE SHALL BE HILTI HIT HY 150 AS SUPPLIED BY HILTI INC. TULSAOKLAHOMA. ANCHOR RODS MEET ASTM F1554 (36 KSI). NUTS ANDWASHERS SHALL BE FURNISHED TO MEET THE REQUIREMENTS OF ANASTM F1554 (36 KSI) STEEL ROD.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JA

ME

SR. MEHLTR E

TT

LI C E N S

E

FL O R I D

A

PR

OF

E

SS

I O NA L E NG

IN

EE

R

ER

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.

180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

1/5/20

17 10

:00:34

AM

1442

S1.01GENERAL STRUCTURAL

NOTES

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #7

01-05-2017 BUILDING01-05-201701-05-201701-05-2017

51

RBIDJM

SHEET LIST

SHEETNUMBER SHEET NAME

S1.01 GENERAL STRUCTURAL NOTES

S1.02 WIND DESIGN DATA & LOAD SCHEDULE

S2.01 FOUNDATION PLAN

S2.02 SLAB ON GRADE PLAN

S2.03 LOW ROOF FRAMING PLAN

S2.04 ROOF FRAMING PLAN

S2.05 SHED FRAMING PLAN

S3.01 TYPICAL DETAILS

S3.02 TYPICAL DETAILS

S3.03 TYPICAL DETAILS

S3.04 TYPICAL DETAILS

S3.05 TYPICAL DETAILS

S3.06 TYPICAL DETAILS

S3.07 TYPICAL DETAILS

S3.08 TYPICAL DETAILS

S4.01 WALL SECTIONS

S4.02 WALL SECTIONS

S4.03 WALL SECTIONS

S4.04 WALL SECTIONS

S4.05 WALL SECTIONS

S4.06 WALL SECTIONS

S4.07 WALL SECTIONS

S5.01 SCHEDULES

LOW ROOF:

1 1/2" METAL DECKSTEEL FRAMINGCEILING 3 PSF

5 PSF3 PSF

INSULATION 5 PSF====

LOAD SCHEDULE:

LIVE LOAD = 20 PSF

-154 PSF

-108 PSF

10 SQ. FT.

PATTERN

3

-72 PSF

MAIN ROOF

EFFECTIVE WIND AREAZONE

2

1

5

4

ZONE

DESIGN WIND PRESSURE (ULTIMATE) FOR WALLS, DOORS & WINDOWS

EFFECTIVE WIND AREAPATTERN

COMPONENTS AND CLADDING

COMPONENTS AND CLADDING (ULTIMATE) UPLIFT PRESSURE SCHEDULE

-67 PSF

100 SQ. FT.

-76 PSF

-76 PSF

500 SQ. FT.

-68 PSF

50 SQ. FT.

-85PSF

-99 PSF

10 SQ. FT.

+72 PSF/-76 PSF +62 PSF/-67 PSF

100 SQ. FT.

+58 PSF/-62 PSF

500 SQ. FT.

+69 PSF/-74 PSF

50 SQ. FT.

-67 PSF

-76 PSF

-76 PSF

NOTE:1. ALL EXTERIOR DOORS & WINDOW ASSEMBLIES SHALL SATISFY THE REQUIREMENTS OF THE FLORIDA BUILDING CODE (2014, 5TH EDITION,

SECTION 1710.5). ALL CONNECTIONS TO BUILDING STRUCTURE SHALL HAVE THE CAPACITY TO WITHSTAND THE PRESSURESINDICATED IN THIS SCHEDULE.

2. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.3. ALL WIND PRESSURE VALUES INDICATED ARE IN POUNDS PER SQUARE FOOT (PSF). MULTIPLY ULTIMATE WIND PRESSURE

BY 0.60 FOR ASD PRESSURE.

MEP 7 PSF=

+72 PSF/-90 PSF +62 PSF/-76 PSF +58 PSF/-62 PSF+69 PSF/-85 PSF

DEAD LOAD

-70 PSF

20 SQ. FT.

-99 PSF

-131 PSF

20 SQ. FT.

+67 PSF/-72 PSF

+67 PSF/-81 PSF

WIND DESIGN DATA:

CODE: ASCE 7-10, FLORIDA BUILDING CODE, 2014 ( 5th Ed.)

BASIC WIND SPEED

CATEGORY (RISK)EXPOSUREBUILDING HEIGHT 20 ft.

CIV

Vasd = 119 mph

* GLAZED OPENINGS IN RISK CATEGORY II, III, IVLOCATED IN HURRICANE PRONE REGIONS SHALLBE PROTECTED IN ACCORDANCE WITH ASCE 7-10SEC. 26.10.3.

EXPOSURE CLASSIFICATION ENCLOSED

-104 PSF -99 PSF-100 PSF -76 PSF-102 PSF2'

3'

ov

ov -154 PSF -62 PSF-90 PSF -62 PSF-127 PSF

MISCELLANEOUS 2 PSF=ROOFING 5 PSF=

30 PSF

50 PSFLOW ROOF TOTAL LOAD =

INT. PRESSURE COEFFICIENT ± 0.18

HIGH ROOF:

4" METAL DECKSTEEL FRAMINGCEILING 3 PSF

5 PSF5 PSF

INSULATION 5 PSF====

LOAD SCHEDULE:

LIVE LOAD = 20 PSF

MEP 7 PSF=

DEAD LOAD

MISCELLANEOUS 2 PSF=ROOFING 5 PSF=

32 PSF

52 PSFLOW ROOF TOTAL LOAD =

Vult = 155 mph

5 5 554 4

TYP.

7' - 0"TYP.

7' - 0"

5 5 5 544 4

TYP.

7' - 0"TYP.

7' - 0"

545

TYP.

6' - 8 1/4"

TYP.

7' - 0"

5 5 5 5 54 4 4

TYP.

7' - 0"

TYP.

7' - 0"

3 32

1

3 32

2 2

3

3

2

3

2

2

12'ov2'ov

2'ov

2'ov

3

1

2

2

2

3

3

1

2

2

2

3'ov

3'ov 3'ov

3'ov

2 2

33

7' - 0", TYP.

7' -

0", T

YP.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:21

PM

1442

S1.02WIND DESIGN DATA &

LOAD SCHEDULE

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

52

RBIDJM

1/16" = 1'-0"WIND DESIGN - NORTHN

1/16" = 1'-0"WIND DESIGN - SOUTHS

1/16" = 1'-0"WIND DESIGN - EASTE

1/16" = 1'-0"WIND DESIGN - WESTW

1/8" = 1'-0"WIND LOAD - ROOF PLAN1

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

2.5W

F2.0

2.5WF2.0

2.5W

F3.0

2.5WF2.0

2.5W

F2.0

2.5WF2.0

2.5W

F2.0

2.5W

F2.0

2.5WF2.0

2.5WF2.0

2.5WF2.0

2.5WF2.0

2.5W

F2.0

2.5WF2.0

2.5WF2.0

2.5WF2.0

A8-5

-24S

A8-5

-24S

A8-5-24S

A8-5-24S

A8-5

-24S

A8-5-24S

A8-5

-24S

A8-5-24S

A8-5-24S

W8-

5-24

S

W8-5-24S

A8-5-24S

A8-5-24S

A8-5-24S

A8-5

-24S

A8-5-24S

A8-5-24S

1 2 7 8 10 11

AA

BB

C

D

F

H

J

K

LL

M

NN

4 5

GG

9

E

I

3 613' - 4 1/4" 3' - 8" 15' - 4" 15' - 4" 15' - 4" 2' - 4" 13' - 3 3/4" 5' - 8" 11' - 8" 29' - 4"

6' -

0 1/

4"2'

- 8"

8' -

8 1/

2"9'

- 4"

13' -

3 1

/2"

2' -

6"5'

- 11

3/4

"7'

- 6

1/4"

8' -

8"12

' - 0

"7'

- 11

3/4

"22

' - 8

"

8' -

8 1/

4"23

' - 6

1/2

"10

' - 3

1/2

"7'

- 2

1/2"

26' -

11

1/2"

7' -

11 3

/4"

2.5F5.0 2.5F5.0

2.5F5.0

2.5F5.02.5F5.0

S1S4.01

S2S4.01

S3S4.02

S4S4.02

S5S4.03

S7S4.04

S8S4.04

S1S4.01

2.5F5.0

2.5W

F3.0

2.5W

F3.0

2.5W

F3.0

2.5W

F3.0

A8-5-24S A8-5-24S

S14S4.06

S6S4.03

S9S4.04

S10S4.05

S11S4.05

S13S4.06

2.5WF2.0

W8-5-24S

2WF2.0

2WF2.0

2.5WF2.0

2.5F4.0

S292.5WF2.0 2.5WF2.02.5WF2.0

A8-5-8S A8-5-8S

S4 S6

S21 S23

S1

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

2.5W

F3.0

2.5W

F3.0

2.5W

F3.0

2.5W

F3.0

2.5W

F3.0

A8-5-24S

A8-5-24S

2.5WF2.0

2.5WF4.0

2.5WF4.0

A8-5-8S A8-5-8S

2.5WF4.0

2.5WF2.02.5WF2.0

2.5WF4.0

2.5WF2.02.5WF2.0

2.5F2.02.5F2.0

2.5F2.0

S13

S8

S15 S14

3' - 6 3/4"6' - 7 1/2"

2' - 10 3/4"5' - 11"

5' -

7 1/

2"

5' -

11 1

/2"

A8-5

-24S

7' - 4"

A8-5

-24S

S12S4.05 2.5F5.0

PROVIDE (2) ADDITIONALGROUT FILLED CELLS W/ (1)#5, TYP. AT MECH. OPENING

11' - 11 1/4"

11' - 6 1/4"

PROVIDE (3) ADDITIONALGROUT FILLED CELLSW/ (1) - #5

S.F.

S.F.

(-2'-8

")(-1

'-4")

S.F.

S.F.

(-4'-0

")(-2

'-8")

S.F.

S.F.

(-5'-4

")(-4

'-0")

1' - 0"

3' - 5"

TYP.

2' - 8"

S.F.

S.F.

(-6'-0

")(-5

'-4")

(-4'-0

")

S.F.S.F.

(-2'-8")(-1'-4")

S.F.S.F.

(-4'-0")(-2'-8")

S.F.S.F.

(-5'-4")(-4'-0")

S.F.S.F.

(-6'-0")(-5'-4")

S.F.

S.F.

(-5'-4

")(-4

'-0")

S.F.

S.F.

(-6'-0

")(-5

'-4")

S.F.

S.F.

(-5'-4

")(-4

'-0")

S.F.

S.F.

(-6'-0

")(-5

'-4")

2.5W

F2.5

W8-

5-24

S

(-6'-0

")

6' - 8"

S9S4.04

FOUNDATION PLAN NOTES:

1. FOR GENERAL STRUCTURAL NOTES, SEE DRAWING S1.01.2. FOR FOOTING SIZE AND REINFORCING, SEE SCHEDULE ON THIS DRAWING.3. ( ) DENOTES TOP OF FOOTING ELEVATION.4. TOP OF FOOTING: ELEVATION @ INTERIOR = (-1' - 4")

TYPICAL U.N.O.ELEVATION @ EXTERIOR = (-1' - 4")TYPICAL U.N.O.

5. FOR PLAN DIMENSIONS NOT SHOWN, REFER TO ARCHITECTURAL DRAWINGS.6. TYPICAL WALL REINFORCING SCHEDULE:

A. 8" CMU EXTERIOR WALL REINFORCING WITH (1)-#5 AT 24"O.C. VERTICAL.

B. INDICATES (1)-#5 IN GROUT FILLED CELL.C. PROVIDE ADDITIONAL (1)-#5 VERTICAL IN FIRST (2) CELLS EACH SIDE OFALL WALL OPENINGS, CORNERS AND INTERSECTIONS.

7. COLUMN DESIGNATION SHOWN THUS ON PLAN. FOR SIZE ANDREINFORCING SEE SCHEDULE ON S5.01.

8. ALL CMU WALLS SHALL BE REINFORCED AS SHOWN ON PLAN WITHDOWELS TO MATCH, U.N.O. ALL CELLS AT REINFORCING LOCATIONSHALL BE FILLED WITH GROUT. PROVIDE INSPECTION/CLEANOUT HOLEAT BASE WHEN POUR HEIGHT IS GREATER THAN 4'-0".

WALL OPENING CORNER INTERSECTION

C1

T/COLUMN ELEVATION

COLUMN TYPE

CARRIED COLUMN

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:26

PM

1442

S2.01FOUNDATION PLAN

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

53

RBIDJM

SCALE: 1/8" = 1'-0"S2.01FOUNDATION PLAN1

WALL SCHEDULE

TYPE DESCRIPTIONA8-5-8S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 8" O.C.

A8-5-24S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 24" O.C.C12-5-24D 12" CONCRETE WALL REINF. W/ (2)#5 AT 24" O.C. EACH WAY, EACH FACEW8-5-24S 8" CMU LOAD BRG.WALL REINF. W/ #5 AT 24" O.C.

WALL FOOTING SCHEDULE

MARK* WIDTH DEPTHTOP & BOTT.REINF. CONT.

TOP & BOTT.REINF. TRANSV. REMARKS

2.5WF2.0 2' - 0" 1' - 4" 3-#5 #4 @ 24"2.5WF2.5 2' - 6" 1' - 4" 3-#5 #4 @ 24"2.5WF3.0 3' - 0" 1' - 4" 4-#5 #4 @ 16"2.5WF4.0 4' - 0" 1' - 4" 4-#5 #5 @ 16"

COLUMN FOOTING SCHEDULE

MARK* LENGTH WIDTH DEPTHTOP & BOTT. REINF.*

EA. WAY U.N.O. REMARKS2.5F2.0 2' - 0" 2' - 0" 1' - 6" 5-#4 STD. ACI HOOK2.5F2.5 2' - 6" 2' - 6" 1' - 6" 5-#4 STD. ACI HOOK2.5F4.0 4' - 0" 4' - 0" 1' - 6" 5-#5 STD. ACI HOOK2.5F5.0 5' - 0" 5' - 0" 1' - 6" 6-#5 STD. ACI HOOK

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

oo

oo

o

oo

o

o

33

3

8" SLAB,SEE NOTE 2

4" SLAB,SEE NOTE 1

4" SLAB,SEE NOTE 1 4" SLAB,

SEE NOTE 1

4" SLAB,SEE NOTE 1

1 2 7 8 10 11

6' - 8" 13' - 4 1/4" 3' - 8" 15' - 4" 15' - 4" 15' - 4" 2' - 4" 13' - 3 3/4" 5' - 8" 11' - 8" 29' - 4"

AA

BB

C

D

F

H

J

K

LL

M

NN

6' -

0 1/

4"2'

- 8"

8' -

8 1/

2"9'

- 4"

13' -

3 1

/2"

2' -

6"5'

- 11

3/4

"7'

- 6

1/4"

8' -

8"12

' - 0

"7'

- 11

3/4

"22

' - 8

"

4 5

GG

9

E

I

3 6

8' -

8 1/

4"23

' - 6

1/2

"10

' - 3

1/2

"7'

- 2

1/2"

26' -

11

1/2"

7' -

11 3

/4"

S1S4.01

S2S4.01

S3S4.02

S4S4.02

S5S4.03

S7S4.04

S8S4.04

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ) (CJ)

(CJ)

(CJ)

(CJ)

(CJ) (CJ)

(CJ)

(CJ)

(CJ)

(CJ)

(CJ)

S1

S1S4.01

TS-1

TS-1TS-1

TS-1TS-1 TS-1 TS-1

A8-5-24SW8-5-24S

A8-5-24S

A8-5-24SA8-5-24S

A8-5-24S

A8-5-24S

A8-5-24S

A8-5-24S

A8-5-24S

A8-5-24S A8-5-24S

A8-5-24S

A8-5

-24S

A8-5

-24S

A8-5

-24S

A8-5

-24S

A8-5-24S

A8-5

-24S

S14S4.06

S6S4.03

S9S4.04

S10S4.05

S11S4.05

S13S4.06

0' - 0"

0' - 0"

0' - 0"

0' - 0"0' - 0"0' - 0"

0' - 0"

A8-5-8S A8-5-8S

A8-5-24S A8-5-8S A8-5-8S A8-5-24S

TS-1TS-1 S4 S6

S21 S23

S29

TS-1

A8-5-24S

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D

C12

-5-2

4D(CJ)

W8-5-24S

S13

S15 S14

3' - 6 1/4" 6' - 7 1/2"2' - 10 3/4"

5' - 11"

S8

5' -

7 1/

2"

3-999S3.03

3-999S3.03

TYP. ATAPPARATUS BAY

S12S4.05

TOP OF SLAB ELEV. = (0'-4")DEPTH OF SLAB = 1'-4" REINF.W/ (6) #5 EACH WAY T&B

2 1/2"

2 1/2"

2 1/2"

2 1/2"

2 1/

2"

(CJ)

4"

(CJ)

1/2"

1/2"

T/ WALL ( 0' - 4" )

TOP OF SLAB ELEV. = (0'-4")DEPTH OF SLAB = 1'-4" REINF.W/ #5@12" O.C. EACH WAY T&B

4"

S9S4.04

SLAB ON GRADE PLAN NOTES:

1. SLAB ON GRADE TO BE 4" THICK CONCRETE OVER VAPOR BARRIER ONCOMPACTED SUB-BASE AS PER GEOTECHNICAL REPORT REINFORCEDWITH 6x6xW2.1xW2.1 W.W.F. (FLAT SHEETS) CENTERED IN SLAB.SUPPORT WELDED WIRE FABRIC WITH 2" SLAB BOLSTER OR APPROVEDEQUAL @ 3'-0"(±) O.C. BOTH WAYS. USE OF CONCRETE BRICK IS NOTALLOWED.

2. SLAB ON GRADE TO BE 8" THICK CONCRETE OVERVAPOR BARRIER CONFORMING TO ASTM E-1745 ON COMPACTEDSUB-BASE AS PER GEOTECHNICAL REPORT AND REINFORCED WITH#4 @ 12" O.C. EACH WAY TOP AND BOTTOM. SUPPORT REINFORCING ON3 1/2" SLAB BOLSTERS OR APPROVED EQUAL @ 3'-0" (±) O.C. BOTH WAYS.USE OF CONCRETE BRICK IS NOT ALLOWED.

3. VAPOR BARRIER REQUIREMENTS/APPLICATION/INSTALLATION SHALL BEDONE AS PER ARCHITECTURAL OR MOISTURE CONSULTANT DOCUMENTSAND RECOMMENDATIONS. IF NONE ARE AVAILABLE, AT A MINIMUM THEFOLLOWING RECOMMENDATIONS SHALL BE FOLLOWED.

A. VAPOR BARRIER SHALL CONFORM TO ASTM E-1745 , MEETS OREXCEEDS CLASS "B".

B. VAPOR BARRIER INSTALLATION SHALL FOLLOW MANUFACTURER'SINSTRUCTIONS AND ASTM E 1643-98.

C. UNROLL VAPOR BARRIER WITH THE LONGEST DIMENSION PARALLELWITH THE DIRECTION OF THE POUR.

D. LAP VAPOR BARRIER OVER FOOTINGS AND SEAL TO FOUNDATIONWALLS.

E. OVERLAP JOINTS 6 INCHES AND SEAL WITH MANUFACTURER’S TAPE.F. SEAL ALL PENETRATIONS (INCLUDING PIPES) WITH MANUFACTURER’S

PIPE BOOT.G. NO PENETRATION OF THE VAPOR BARRIER IS ALLOWED EXCEPT FOR

REINFORCING STEEL AND PERMANENT UTILITIES.H. REPAIR DAMAGED AREAS BY CUTTING PATCHES OF VAPOR BARRIER,

OVERLAPPING DAMAGED AREA 6 INCHES AND TAPING ALL FOURSIDES WITH TAPE.

4. TOP OF SLAB ELEVATION SHOWN THUS '- " ON PLAN EQUALSREFERENCE EL., FOR ACTUAL EL., SEE CIVIL DRAWINGS.

5. FOR GENERAL STRUCTURAL NOTES, SEE DRAWING S1.01.6. FOR FLOOR SLAB DEPRESSION LOCATIONS AND LIMITS NOT SHOWN ON

PLAN SEE ARCHITECTURAL DRAWINGS.7. FOR PLAN DIMENSIONS NOT SHOWN, REFER TO ARCHITECTURAL DRAWINGS.

8. COLUMN DESIGNATION SHOWN THUS ON PLAN. FOR SIZE ANDREINFORCING SEE SCHEDULE THIS DRAWING.

9. COORDINATE LOCATION OF (CJ) CONTROL JOINTS (SAWCUTS & TOOLEDJOINTS) AT WALKWAY SLABS WITH ARCHITECTURAL DRAWINGS. CONTROLJOINTS AT EXPOSED TO WEATHER WALKWAYS SHALL BE TOOLED JOINTSSEE TYPICAL DETAIL 3-201 ON S3.02.

10. ALL CMU WALLS SHALL BE REINFORCED AS SHOWN ON PLAN WITHDOWELS TO MATCH, U.N.O. ALL CELLS AT REINFORCING LOCATIONSHALL BE FILLED WITH GROUT. PROVIDE INSPECTION/CLEANOUT HOLEAT BASE WHEN POUR HEIGHT IS GREATER THAN 4'-0".

11. GENERAL CONTRACTOR TO COORDINATE LOCATION OF ALL WALLPENETRATIONS REQUIRED FOR MECHANICAL EQUIPMENT AND PROVIDE APRECAST LINTEL AT ALL OPENINGS REFER TO TYPICAL DETAIL 4-004ON S3.03.

12. MASONRY CONTROL JOINT SHOWN THUS MCJ ON PLAN. MAXIMUMSPACING OF JOINTS = 24' - 0", SEE TYPICAL DETAIL 4-002 ON S3.03,COORDINATE LOCATION WITH THE ARCH. BUILDING ELEVATIONS.

C1

T/COLUMN ELEVATION

COLUMN TYPE

CARRIED COLUMN

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:33

PM

1442

S2.02SLAB ON GRADE PLAN

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

54

RBIDJM

SCALE: 1/8" = 1'-0"S2.02SLAB ON GRADE PLAN1

WALL SCHEDULE

TYPE DESCRIPTIONA8-5-8S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 8" O.C.A8-5-24S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 24" O.C.

C12-5-24D 12" CONCRETE WALL REINF. W/ (2)#5 AT 24" O.C. EACH WAY, EACH FACEW8-5-24S 8" CMU LOAD BRG.WALL REINF. W/ #5 AT 24" O.C.

THICKENED SLAB SCHEDULE

MARK* SIZE DEPTHTOP & BOTT.*REINF. CONT.

TOP & BOTT.*REINF.

TRANSV. REMARKSTS 0' - 8" x CONT. 0' - 8" N/A N/A

TS-1 1' - 0" x CONT. 1' - 4" (1) - #5 T, (2)-#5 BCONT., #4 @ 24"TRANSVERSE

N/A

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

2' -

6"2'

- 6"

2' -

6"

2' -

6"2'

- 6"

10K1

10K1

10K1

10K1

10K1

10K1

10K1

10K1

10K1

10K1

10K1

10K1

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

16K7

1 2 7 8 10 11

AA

BB

C

D

F

H

J

K

LL

M

NN

4 5

GG

9

E

I

3 6

13' - 4 1/4" 3' - 8" 15' - 4" 15' - 4" 15' - 4"2' - 4"

13' - 3 3/4" 5' - 8" 11' - 8" 29' - 4"

6' -

0 1/

4"2'

- 8"

8' -

8 1/

2"9'

- 4"

13' -

3 1

/2"

2' -

6"5'

- 11

3/4

"7'

- 6

1/4"

8' -

8"12

' - 0

"7'

- 11

3/4

"

8' -

8 1/

4"23

' - 6

1/2

"10

' - 3

1/2

"7'

- 2

1/2"

26' -

11

1/2"

7' -

11 3

/4"

10K1

10K1

10K1

2' - 6" 2' - 6"

SEE

NO

TES

SEE

NO

TES

SEE

NO

TES

SEE NOTES

CB-4

CB-3

S1S4.01

S2S4.01

S3S4.02

S4S4.02

S5S4.03

S7S4.04

S8S4.04

S1S4.01

CONTINUOUS HORIZONTALBRIDGING PER JOIST MANUF. SPECS.

CONTINUOUS HORIZONTAL UPLIFTBRIDGING AT FIRST BOTTOMCHORD PER JOIST MANUF. SPECS.

CONT. HORIZONTALUPLIFT BRIDGING ATFIRST BOTTOMCHORD PER JOISTMANUF. SPECS.

CONT. HORIZONTALUPLIFT BRIDGING ATFIRST BOTTOMCHORD PER JOISTMANUF. SPECS.

CONT. HORIZONTALBRIDGING PER JOISTMANUF. SPECS.

CONTINUOUS HORIZONTAL UPLIFTBRIDGING AT FIRST BOTTOMCHORD PER JOIST MANUF. SPECS.

(VAR

IES)

VARIES

VAR

IES

VAR

IES

S1

S14S4.06

S6S4.03

S9S4.04

S10S4.05

S11S4.05

S13S4.06

T/ WALL ( 13' - 4" )

T/ W

ALL

( 9' -

6 5

/8" )

T/ W

ALL

( 13'

- 4"

)

T/ W

ALL

( 13'

- 4"

)

T/ W

ALL

( 13'

- 4"

)

T/ W

ALL

( 13'

- 4"

)

T/ W

ALL

( 13'

- 4"

)

T/ WALL ( 13' - 4" )

T/ WALL ( 13' - 4" )

T/ WALL ( 13' - 4" )

T/ WALL ( 13' - 4" )

T/ WALL ( 13' - 4" )

S4 S6

S21 S23

S29

SEE NOTES

CB-1CB-1

CB-1 CB-1

CB-

1

CB-

1

4x4x1/4" CLOSUREANGLE

2' -

6"

S13

S15

S8

S14

HSS4X4X3/16

HSS4X4X3/163' - 6 1/2"

6' - 7 1/2" 2' - 10 3/4"

5' - 11"

5' -

7 1/

2"

S12S4.05

10K1

HSS6X4X1/4 HSS6X4X1/4

CONT. HORIZ. BRIDGINGPER JOIST MANUF. SPECS.

10K1

10K1

S9S4.04

2' -

6"2'

- 6"

LOW ROOF FRAMING NOTES:

1. ROOF FRAMING SHALL BE 1 1/2"- 20 GAGE TYPE "B" (WIDE RIB)METAL DECK SPANNING OVER OPEN WEB STEEL JOIST SPACED @5'-0" O.C. (U.N.O.).

2. DIRECTION OF METAL DECK SPAN SHOWN THUS ON PLAN.3. FOR ROOF DRAIN LOCATIONS AND SIZE SEE ARCHITECTURAL DRAWINGS.

FOR FRAMING SEE TYPICAL DETAIL 5-302/S3.07.4. FOR TYPICAL DETAILS AND GENERAL NOTES SEE DRAWING S3.01 THRU

S3.08.5. ( ) DENOTES UNDERSIDE OF METAL DECK ELEVATION.6. JOIST MANUFACTURER TO DESIGN JOIST FOR THE UPLIFT FORCE SHOWN

ON THE LOADING SCHEDULE AND PROVIDE CERTIFICATION THAT CHORDMEMBERS HAVE BEEN INVESTIGATED FOR REVERSE STRESSES DUE TOALL UPLIFT FORCES. ADDITIONAL BRIDGING SHALL BE PROVIDED AT THEFIRST INTERIOR BOTTOM CHORD PANEL POINT OF ALL JOISTS SUBJECTTO NET UPLIFT PER STEEL JOIST INSTITUTE.

7. FRAME ALL JOIST BOTTOM CHORD MEMBERS TO BEAM BOTTOM FLANGES.INSTALLATION TO BE DONE AFTER ALL DEAD LOADS ARE APPLIED.

8. RAIN LEADER SHOWN THUS R.L. ON PLAN. SEE PLUMBING DRAWINGSFOR SIZE AND LOCATIONS.

9. FOR PLAN DIMENSIONS NOT SHOWN, SEE ARCHITECTURAL DRAWINGS.

10. DENOTES FLAT ROOF.

11. PROVIDE MOMENT CONNECTION AT BEAMS SHOWN THUS ONPLAN.

12. COLUMN DESIGNATIONS SHOWN THUS ON PLAN. FOR COLUMNSCHEDULE, SEE DRAWING S5.01.

13. DENOTES COLUMN STOP AT THIS LEVEL.

15. FOR LOAD SCHEDULE & WIND DESIGN DATA, SEE DRAWING S1.02.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:38

PM

1442

S2.03LOW ROOF FRAMING

PLAN

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

55

RBIDJM

SCALE: 1/8" = 1'-0"S2.03LOW ROOF FRAMING PLAN1

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

1 2 7 8 10 11

AA

BB

C

D

F

H

J

K

LL

M

NN

4 5

GG

9

E

I

3 6

13' - 4 1/4" 3' - 8" 15' - 4" 15' - 4" 15' - 4" 2' - 4" 13' - 3 3/4" 5' - 8" 11' - 8" 29' - 4"

6' -

0 1/

4"2'

- 8"

8' -

8 1/

2"9'

- 4"

13' -

3 1

/2"

2' -

6"5'

- 11

3/4

"7'

- 6

1/4"

8' -

8"12

' - 0

"7'

- 11

3/4

"

8' -

8 1/

4"23

' - 6

1/2

"10

' - 3

1/2

"7'

- 2

1/2"

26' -

11

1/2"

7' -

11 3

/4"

HSS

16X8

X1/2

HSS

16X8

X1/2

HSS

16X8

X1/2

HSS

16X8

X1/2

HSS

16X8

X1/2

S5S3S2 S9 S10

S22S20

S19 S25 S26

S12 S16

SEE NOTES

SEE NOTES

S1S4.01 S2

S4.01

S4S4.02

S5S4.03

S7S4.04

S8S4.04

S1S4.01

(VARIES)

(VARIES)

+(2) 1/2" X 24 1/2" PLATES

HSS 4x4x1/4 OUTRIGGER @4' - 0" O.C. MAX TYP. INSIDEMETAL DECK FLUTES

HSS 4x4x1/4 OUTRIGGER @4' - 0" O.C. MAX TYP. INSIDE

METAL DECK FLUTES

HSS16X8X1/2

HSS16X8X1/2

+(2) 1/2" X 24 1/2" PLATES

CB-1

CB-1

S14S4.06

S6S4.03

S9S4.04

S11S4.05

S13S4.06

S4 S6

S23S21

W24X131 W24X131

S24

S7

L8x8x1/2 CONT.CLOSURE ANGLE

CONT. L8x81/2"CLOSURE ANGLE

CB-

2

CO

NT.

CO

NT.

CO

NT.

CO

NT.

CO

NT.

CB-

1

CB-

1

S12S4.05

S9S4.04

HIGH ROOF FRAMING NOTES:

1. ROOF FRAMING SHALL BE 4" - 16 GAGE TORIS 4A ACCOUSTICAL METALDECK SPANNING OVER STEEL BEAMS @ 19'-0" MAX.

2. DIRECTION OF METAL DECK SPAN SHOWN THUS ON PLAN.3. FOR ROOF DRAIN LOCATIONS AND SIZE SEE ARCHITECTURAL DRAWINGS.

FOR FRAMING SEE TYPICAL DETAIL 5-302/S3.03.4. FOR TYPICAL DETAILS AND GENERAL NOTES SEE DRAWING S3.01 THRU

S3.08.5. ( ) DENOTES UNDERSIDE OF METAL DECK ELEVATION.6. JOIST MANUFACTURER TO DESIGN JOIST FOR THE UPLIFT FORCE SHOWN

ON THE LOADING SCHEDULE AND PROVIDE CERTIFICATION THAT CHORDMEMBERS HAVE BEEN INVESTIGATED FOR REVERSE STRESSES DUE TOALL UPLIFT FORCES. ADDITIONAL BRIDGING SHALL BE PROVIDED AT THEFIRST INTERIOR BOTTOM CHORD PANEL POINT OF ALL JOISTS SUBJECTTO NET UPLIFT PER STEEL JOIST INSTITUTE.

7. FRAME ALL JOIST BOTTOM CHORD MEMBERS TO BEAM BOTTOM FLANGES.INSTALLATION TO BE DONE AFTER ALL DEAD LOADS ARE APPLIED.

8. RAIN LEADER SHOWN THUS R.L. ON PLAN. SEE PLUMBING DRAWINGSFOR SIZE AND LOCATIONS.

9. FOR PLAN DIMENSIONS NOT SHOWN, SEE ARCHITECTURAL DRAWINGS.

10. DENOTES FLAT ROOF.

11. PROVIDE MOMENT CONNECTION AT BEAMS SHOWN THUS ONPLAN.

12. COLUMN DESIGNATIONS SHOWN THUS ON PLAN. FOR COLUMNSCHEDULE, SEE DRAWING S5.01.

13. DENOTES COLUMN STOP AT THIS LEVEL.14. FOR LOAD SCHEDULE & WIND DESIGN DATA, SEE DRAWING S1.02.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:43

PM

1442

S2.04ROOF FRAMING PLAN

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

56

RBIDJM

SCALE: 1/8" = 1'-0"S2.04ROOF FRAMING PLAN1

CONC. TIE BEAM SCHEDULE

MARK BEAM SIZE CONT. REINFORCINGTIE

REINFORCING REMARKSCB-1 8 x 20 (2) LAYERS(2) #6 T/B #3 @ 6" O.C.CB-2 8 x VARIES (2) #6T/B #3 @ 8" O.C. #4 @ 12" O.C. HORIZ. EA FACECB-3 8 x 44 (2) #6T/B #3 @ 8" O.C. #4 @ 12" O.C. HORIZ. EA FACECB-4 8 x 52 (2) #6T/B #3 @ 8" O.C. #4 @ 12" O.C. HORIZ. EA FACE

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

ROOF FRAMING NOTES:

1. ROOF FRAMING SHALL BE 1 1/2"- 20 GAGE TYPE "B" (WIDE RIB)METAL DECK SPANNING OVER OPEN WEB STEEL JOIST SPACED @5'-0" O.C. (U.N.O.).

2. DIRECTION OF METAL DECK SPAN SHOWN THUS ON PLAN.3. FOR ROOF DRAIN LOCATIONS AND SIZE SEE ARCHITECTURAL DRAWINGS.

FOR FRAMING SEE TYPICAL DETAIL 5-302/S3.07.4. FOR TYPICAL DETAILS AND GENERAL NOTES SEE DRAWING S3.01 THRU

S3.08.5. ( ) DENOTES UNDERSIDE OF METAL DECK ELEVATION.6. JOIST MANUFACTURER TO DESIGN JOIST FOR THE UPLIFT FORCE SHOWN

ON THE LOADING SCHEDULE AND PROVIDE CERTIFICATION THAT CHORDMEMBERS HAVE BEEN INVESTIGATED FOR REVERSE STRESSES DUE TOALL UPLIFT FORCES. ADDITIONAL BRIDGING SHALL BE PROVIDED AT THEFIRST INTERIOR BOTTOM CHORD PANEL POINT OF ALL JOISTS SUBJECTTO NET UPLIFT PER STEEL JOIST INSTITUTE.

7. FRAME ALL JOIST BOTTOM CHORD MEMBERS TO BEAM BOTTOM FLANGES.INSTALLATION TO BE DONE AFTER ALL DEAD LOADS ARE APPLIED.

8. RAIN LEADER SHOWN THUS R.L. ON PLAN. SEE PLUMBING DRAWINGSFOR SIZE AND LOCATIONS.

9. FOR PLAN DIMENSIONS NOT SHOWN, SEE ARCHITECTURAL DRAWINGS.

10. DENOTES FLAT ROOF.

11. PROVIDE MOMENT CONNECTION AT BEAMS SHOWN THUS ONPLAN.

12. COLUMN DESIGNATIONS SHOWN THUS ON PLAN. FOR COLUMNSCHEDULE, SEE DRAWING S5.01.

13. DENOTES COLUMN STOP AT THIS LEVEL.

14. FOR LOAD SCHEDULE & WIND DESIGN DATA, SEE DRAWING S1.02.

FOUNDATION PLAN NOTES:

1. FOR GENERAL STRUCTURAL NOTES, SEE DRAWING S1.01.2. FOR FOOTING SIZE AND REINFORCING, SEE SCHEDULE ON THIS DRAWING.3. ( ) DENOTES TOP OF FOOTING ELEVATION.4. TOP OF FOOTING: ELEVATION @ INTERIOR = (-1' - 4")

TYPICAL U.N.O.ELEVATION @ EXTERIOR = (-1' - 4")TYPICAL U.N.O.

5. FOR PLAN DIMENSIONS NOT SHOWN, REFER TO ARCHITECTURAL DRAWINGS.6. TYPICAL WALL REINFORCING SCHEDULE:

A. 8" CMU EXTERIOR WALL REINFORCING WITH (1)-#5 AT 24"O.C. VERTICAL.

B. INDICATES (1)-#5 IN GROUT FILLED CELL.C. PROVIDE ADDITIONAL (1)-#5 VERTICAL IN FIRST (2) CELLS EACH SIDE OFALL WALL OPENINGS, CORNERS AND INTERSECTIONS.

7. COLUMN DESIGNATION SHOWN THUS ON PLAN. FOR SIZE ANDREINFORCING SEE SCHEDULE ON S5.01.

8. ALL CMU WALLS SHALL BE REINFORCED AS SHOWN ON PLAN WITHDOWELS TO MATCH, U.N.O. ALL CELLS AT REINFORCING LOCATIONSHALL BE FILLED WITH GROUT. PROVIDE INSPECTION/CLEANOUT HOLEAT BASE WHEN POUR HEIGHT IS GREATER THAN 4'-0".

WALL OPENING CORNER INTERSECTION

C1

T/COLUMN ELEVATION

COLUMN TYPE

CARRIED COLUMN

SLAB ON GRADE PLAN NOTES:

1. SLAB ON GRADE TO BE 4" THICK CONCRETE OVER VAPOR BARRIER ONCOMPACTED SUB-BASE AS PER GEOTECHNICAL REPORT REINFORCEDWITH 6x6xW2.1xW2.1 W.W.F. (FLAT SHEETS) CENTERED IN SLAB.SUPPORT WELDED WIRE FABRIC WITH 2" SLAB BOLSTER OR APPROVEDEQUAL @ 3'-0"(±) O.C. BOTH WAYS. USE OF CONCRETE BRICK IS NOTALLOWED.

2. VAPOR BARRIER REQUIREMENTS/APPLICATION/INSTALLATION SHALL BEDONE AS PER ARCHITECTURAL OR MOISTURE CONSULTANT DOCUMENTSAND RECOMMENDATIONS. IF NONE ARE AVAILABLE, AT A MINIMUM THEFOLLOWING RECOMMENDATIONS SHALL BE FOLLOWED.

A. VAPOR BARRIER SHALL CONFORM TO ASTM E-1745 , MEETS OREXCEEDS CLASS "B".

B. VAPOR BARRIER INSTALLATION SHALL FOLLOW MANUFACTURER'SINSTRUCTIONS AND ASTM E 1643-98.

C. UNROLL VAPOR BARRIER WITH THE LONGEST DIMENSION PARALLELWITH THE DIRECTION OF THE POUR.

D. LAP VAPOR BARRIER OVER FOOTINGS AND SEAL TO FOUNDATIONWALLS.

E. OVERLAP JOINTS 6 INCHES AND SEAL WITH MANUFACTURER’S TAPE.F. SEAL ALL PENETRATIONS (INCLUDING PIPES) WITH MANUFACTURER’S

PIPE BOOT.G. NO PENETRATION OF THE VAPOR BARRIER IS ALLOWED EXCEPT FOR

REINFORCING STEEL AND PERMANENT UTILITIES.H. REPAIR DAMAGED AREAS BY CUTTING PATCHES OF VAPOR BARRIER,

OVERLAPPING DAMAGED AREA 6 INCHES AND TAPING ALL FOURSIDES WITH TAPE.

3. TOP OF SLAB ELEVATION SHOWN THUS '- " ON PLAN EQUALSREFERENCE EL., FOR ACTUAL EL., SEE CIVIL DRAWINGS.

4. FOR GENERAL STRUCTURAL NOTES, SEE DRAWING S1.01.5. FOR FLOOR SLAB DEPRESSION LOCATIONS AND LIMITS NOT SHOWN ON

PLAN SEE ARCHITECTURAL DRAWINGS.6. FOR PLAN DIMENSIONS NOT SHOWN, REFER TO ARCHITECTURAL DRAWINGS.

7. COLUMN DESIGNATION SHOWN THUS ON PLAN. FOR SIZE ANDREINFORCING SEE SCHEDULE THIS DRAWING.

8. COORDINATE LOCATION OF (CJ) CONTROL JOINTS (SAWCUTS & TOOLEDJOINTS) AT WALKWAY SLABS WITH ARCHITECTURAL DRAWINGS. CONTROLJOINTS AT EXPOSED TO WEATHER WALKWAYS SHALL BE TOOLED JOINTSSEE TYPICAL DETAIL 3-201 ON S3.02.

10. ALL CMU WALLS SHALL BE REINFORCED AS SHOWN ON PLAN WITHDOWELS TO MATCH, U.N.O. ALL CELLS AT REINFORCING LOCATIONSHALL BE FILLED WITH GROUT. PROVIDE INSPECTION/CLEANOUT HOLEAT BASE WHEN POUR HEIGHT IS GREATER THAN 4'-0".

11. GENERAL CONTRACTOR TO COORDINATE LOCATION OF ALL WALLPENETRATIONS REQUIRED FOR MECHANICAL EQUIPMENT AND PROVIDE APRECAST LINTEL AT ALL OPENINGS REFER TO TYPICAL DETAIL 4-004ON S3.03.

12. MASONRY CONTROL JOINT SHOWN THUS MCJ ON PLAN. MAXIMUMSPACING OF JOINTS = 24' - 0", SEE TYPICAL DETAIL 4-002 ON S3.03,COORDINATE LOCATION WITH THE ARCH. BUILDING ELEVATIONS.

C1

T/COLUMN ELEVATION

COLUMN TYPE

CARRIED COLUMN

CJ

CJ

CJ

SEE SLABNOTES

0' - 0"

SEE SLABNOTES

0' - 0"

R

Q

P

16' -

0"

24' -

0"

12

13

20' - 0"

W8-5-24S

W8-5-24S

W8-5-24S

W8-5-24S

W8-5-24S

S16S4.07

S15S4.07

R

Q

P12

13

20' - 0"

16K2

16K2

16K2

16K2

16K2

16K2

8 1/

4"

16' -

0"

24' -

0"

8 1/

4"

T/WALL 11' - 2"

T/WALL 10' - 8"

CONT. HORIZ.UPLIFT BRIDGINGPER MANUF.

T/WALLVARIES

T/WALL VARIES

1/4" / 12"

SLOPE

CONT. L4X4X1/4CLOSUREANGLE, TYP.

S16S4.07

S15S4.07

R

Q

P12

13

S16S4.07

S15S4.07

16' -

0"

24' -

0"

W8-5-24S

W8-5-24S

W8-5-24S

W8-5-24S

2.5WF2.0

2.5WF2.0

2.5WF2.0

2.5W

F2.0

2.5W

F2.0

20' - 0"

W8-5-24S

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:48

PM

1442

S2.05SHED FRAMING PLAN

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

57

RBIDJM

WALL SCHEDULE

TYPE DESCRIPTIONA8-5-8S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 8" O.C.A8-5-24S 8" ATLAS BRICK LOAD BRG WALL REINF. W/ #5 @ 24" O.C.

C12-5-24D 12" CONCRETE WALL REINF. W/ (2)#5 AT 24" O.C. EACH WAY, EACH FACEW8-5-24S 8" CMU LOAD BRG.WALL REINF. W/ #5 AT 24" O.C.

WALL FOOTING SCHEDULE

MARK* WIDTH DEPTHTOP & BOTT.REINF. CONT.

TOP & BOTT.REINF. TRANSV. REMARKS

2.5WF2.0 2' - 0" 1' - 4" 3-#5 #4 @ 24"2.5WF2.5 2' - 6" 1' - 4" 3-#5 #4 @ 24"2.5WF3.0 3' - 0" 1' - 4" 4-#5 #4 @ 16"2.5WF4.0 4' - 0" 1' - 4" 4-#5 #5 @ 16"

SCALE: 1/8" = 1'-0"S2.05SHED SLAB ON GRADE PLAN2

SCALE: 1/8" = 1'-0"S2.05SHED ROOF FRAMING PLAN3

SCALE: 1/8" = 1'-0"S2.05SHED FOUNDATION PLAN1

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

SLAB ON GRADE EDGE 3-007

FINISH FL.EL. SEE PLAN

11

ADJACENT TO NON-CONCRETE

ADJACENT TO CONC PAVEMENT

1'-0"

11

1'-0"

1'-0

"M

INIM

UM

1'-0

"M

INIM

UM

FINISH GRADESEE SITE DWGS.

1-#5 CONT. TOP

3" CLR

3" CLR

CONC PAVEMENTSEE SITE DWGS.

1-#5 CONT. TOP

2-#5 CONT.BOTTOM

2-#5 CONT.BOTTOM

FINISH FL.EL. SEE PLAN

TYPICAL STEEL COLUMNISOLATION JOINT DETAIL 3-013

3" MIN. (TYPICAL)

STEEL COLUMNSEE PLAN ANDSCHEDULE

FILL W/ CONC.SAME CAPACITYAS SLAB

JOINT FILLER TOEXTEND FULLDEPTH OF JOINTBASE PLATE

SEE SCHEDULE

ANCHOR BOLTSSEE SCHEDULE

NOTE:FOOTING & SLABREINFORCEMENT NOTSHOWN FOR CLARITY

1-#3 TOP(4 SIDES)

PREMOLDED JT.FILLER & SEALANT

PIER OR FTG.BELOW

PREMOLDED JOINTFILLER & SEALANT

NO KEY @ COL.POCKET (TYP.)

KEYED CONSTR.JOINT (TYPICAL)

TYP. COLUMNISOLATION JOINT DETAIL 3-014

X

KEYED CONSTR.JOINT (TYP.)

NO KEY @ COL.POCKET (TYP.)

FILL W/ CONC.SAME CAPACITYAS SLAB

PLAN

SECTION X

PREMOLDED JOINTFILLER & SEALANT

NOTE:FTG, SLAB & COLREINFORCEMENT NOTSHOWN FOR CLARITY.

1- #3 TOP(4 SIDES)

PIER OR FTGBELOW

JOINT FILLER TOEXTEND FULLDEPTH OF JOINT

6" MIN

.

CONCRETE COLUMNSEE PLAN ANDSCHEDULE

TYPICAL BOLLARD DETAIL

INTERIOR/REMOVABLE EXTERIOR

3-020

(3)-9"ø #4 TIES

PIPE SLEEVE GROUTED

THICKEND SLAB

(4)-9"ø #4 TIES

ROUNDED CONC.TOP 1/2" CROWN

GALV. HSS6.00x0.125CONC. FILLED STEELPIPE PAINTED SAFETYYELLOW

ROUNDED CONC.TOP 1/2" CROWN

GALV. HSS6.00x0.125CONC. FILLED STEELPIPE PAINTEDSAFETY YELLOW

1/2" PREMOLDEDEXP. JT. WHERECONC. OCCURS

2' - 0" ø

3"2'

- 9"

.4'

- 0"

.

EXTERIOR

1' - 0"

3"

MIN

.

1' -

0"

4' -

0".

T/ SLABSEE PLAN

3-054

9"MIN.

12"

9"MIN.

9"MIN.

9"MIN.

12"

3"CLR.

6"CLR.

6"CLR.

6"

3" CLR.3" CLR.

3" CLR.

11

11

BANK OF PIPES DETAIL

SINGLE PIPE DETAIL

REINF. TO MATCHNUMBER & SIZEOF BOTT. REINF.OF FTG.

PIPE SLEEVE TOBE 2" LARGERTHAN PIPE

REINF. TO MATCHNUMBER & SIZEOF BOTT. REINF.OF FTG.

PIPE SLEEVE TOBE 2" LARGERTHAN PIPE

PIPE SLEEVE DETAILAT FOUNDATION TYP STEPPED FTG DETAIL 3-055

CONT. WALLFOOTING

NOTE 2

NO

TE 1a

2a MIN.MIN.1'-0"NOTE 3

a

11

NOTE 3

NOTE 4

NOTE:

1. DIMENSION "a" TO BE KEPT IN BLOCK COURSING NOTTO EXCEED 1'-4" AT MASONRY WALLS OR 1'-6" ATCONCRETE WALLS.

2. FOOTING REINF. IN ALL BLOCK FOUNDATION WALLS2-#5 CONT. (EXTEND THRU SPREAD FOOTINGS U.N.O.).

3. DIMENSION = LAP TYPE "B" MINIMUM.4. DOWELS AS REQUIRED.

TYP. COLUMN SECTIONS & TIE SCHEDULE 3-061

1'-6" STAGGER FOR #3

2'-1" STAGGER FOR #4

SIZE AND SPACING OF COL. TIESB

A

#5

8" 10" 12" 14" 16" 18" 20" 22" 24" ORMORE

#6

#7

#8

#9,#10

#11#14,& #18

#3@10

#3@10

#3@10

#3@10

#3@10

#3@10 #3@10 #3@10 #3@10 #3@10 #3@10 #3@10

#3@12

#3@12

#3@12

#3@12

#3@12 #3@12 #3@12 #3@12 #3@12 #3@12

#3@14

#3@14

#3@14

#3@14 #3@14 #3@14 #3@14 #3@14

#3@16

#3@16

#3@16 #3@16 #3@16 #3@16

#3@18

#3@8

#3@8

#3@8

#3@8

#3@8

#3@18 #3@18 #3@18

#4@8 #4@10 #4@12 #4@14 #4@16 #4@18 #4@20 #4@22 #4@22

A = SIZE OF VERTICAL REINF.B = LEAST DIMENSION OF COLUMN

4 BARS 6 BARS 8 BARS

10 BARS 12 BARS 14 BARS

16 BARS WALL TYPE COLUMN

4 BARS 5 OR MORE BARS

ROUND COLUMNSW/ SPIRALS

TIES IN ROUND COLUMN

NOTE 4

X XXX

XX

NOTE 1

XX

NOTE 1

NOTE 1

NOTE 1

X X XX

X X

MIN. 3 SPACERSPER SPIRAL

NOTES:

1. THESE BARS MUST BE TIED AS SHOWN BY DASHEDLINES WHEN "X" DISTANCE IS OVER 6 INCHES ANDNEED NOT BE TIED WHEN "X" IS 6" OR LESS.

2. MINIMUM CLEAR COVER 1 1/2" TO TIES (2" FOREXPOSED CONDITION).

3. FOR VERTICAL COLUMN REINFORCING, SEE PLAN ANDCOLUMN SCHEDULE.

4. FOR SPIRAL SEE COLUMN SCHEDULE.

EMBEDED COLUMN 5-600

MASONRY CONTROLJOINT, SEE ARCH DWG'S

FILL CELLS FULL HEIGHTSOLID WITH MORTAR ATHSS COLUMN

MASONRY CONTROLJOINT, SEE ARCH DWG'S

8" ATLAS BLOCK,SEE PLAN

VERT REINF (1) EACHSIDE OF COLUMN ATMASONRY CONTROLJOINT (TYP)

COL ISOLATION JOINT,SEE PLAN

CONTROL JOINT(CJ). SEE PLAN

HSS COL, SEEPLAN

BASE PLATE AND ANCHBOLTS, SEE PLAN

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:31:55

PM

1442

S3.01TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

58

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

TYPICAL CONCRETE BEAM BAR PLACEMENT DIAGRAM 3-062

0" 0"

L1 L2 L3

2" START OFSTIRRUPS TYPICAL

LAP BOTTOM STEELOVER SUPPORTS

SEE BEAM SCHEDULEFOR STIRRUP SPACING

NOTE:

1. WHERE TOP & BOTTOM BARS ARE IN MULTIPLE LAYERS, PROVIDE 1" CLEAR BETWEEN LAYERSTYPICAL.

2. SEE TENSION AND COMPRESSION LAP SPLICE TABLES FOR PROPER LAP AND CONCRETESTRENGTH.

3. ALL BOTTOM LAYERS OF STEEL MUST BE LAPPED OVER CENTERLINE OF SUPPORT.4. ALL TOP AND INTERMEDIATE LAYERS OF STEEL MUST BE LAPPED AT MID-SPAN OF BEAM.5. SEE CONCRETE BEAM SCHEDULE FOR ALL BEAM REINFORCING AND SEE FRAMING PLANS FOR

BEAM DESIGNATION AND PLACEMENT.

COLUMNSUPPORT

COLUMNSUPPORT

COLUMNSUPPORT

TYPICAL CONCRETECOVER FOR REINF. BARS 3-064

THE MINIMUM CLEAR COVER FOR REINFORCEMENT BARS SHALL BE ONEBAR DIAMETER OR THE VALUES TABULATED BELOW, WHICHEVER IS THEGREATER.

SLABS (LT.WT. CONC. OR STONE CONC.)

GIRDERS AND BEAMS (TO STIRRUPS)

JOISTS (STONE OR LT.WT.) BOTTOM BARS

TIED COLUMNS AND PIERS

SURFACE EXPOSED TO EARTH AND WEATHER

OTHER SURFACES

FOUNDATION ELEMENTS

FORMED SURFACES

SURFACES PLACED AGAINST EARTH

WALLS

SURFACES EXPOSED TO EARTH

SURFACES EXPOSED TO WEATHER

OTHER SURFACES

1"

1 1/2"

1 1/4"

2"

1 1/2"

2"

3"

2"

1 1/2"

1"

(TO TIES)

(TO TIES)

TENSION AND COMPRESSION LAP SPLICES WITH F'c = 3000 PSI 3-065

COMPRESSIONLAP SPLICES

TENSION LAP SPLICES

#3

LAP LENGTH PER SPACING AND COVER CASECASE 1

TOP BARS OTHER BARSSIZEBAR LAP

CLASS

2822

CASE 2OTHER BARSTOP BARS

BA

2217

4232

3225 12

#4 3729

BA

2922

5643

4333 15

#5 4736

BA

3628

7054

5441 19

#6 5643

BA

4333

8464

6450 23

#7 8163

BA

6348

12294

9472 26

#8 9372

BA

7255

139107

10782 30

#9 10581

BA

8162

157121

12193 34

#10 11891

BA

9170

177136

136105 38

#11 131101

BA

10178

196151

151116 42

f'c = 3000 PSI, NORMAL WEIGHT

NOTES:

CASE 1

BEAMS AND COLUMNS:CONCRETE COVER >/= TO BAR DIAMETER, C-C BARSPACING >/= TO 2X BAR DIAMETER AND WITH STIRRUPSOR TIES THROUGHOUT TENSION LAP SPLICE LENGTH

NOTLESS THAN THE CODE MINIMUM.

OTHER MEMBERS:CONCRETE COVER >/= TO THE BAR DIAMETER AND C-CBAR SPACING >/= TO 3X BAR DIAMETER.

CASE 2

BEAMS AND COLUMNS:CONCRETE COVER < BAR DIAMETER AND C-C BARSPACING < 2X BAR DIAMETER.

OTHER MEMBERS:CONCRETE COVER < BAR DIAMETER OR C-C BARSPACING < 3X BAR DIAMETER.

* LAP CLASS "B" IS TO BE USED UNLESS OTHERWISESPECIFIED IN THESE CONTRACT DOCUMENTS.

TENSION AND COMPRESSION LAP SPLICES WITH F'c = 4000 PSI 3-066

COMPRESSIONLAP SPLICES

TENSION LAP SPLICES

#3

LAP LENGTH PER SPACING AND COVER CASECASE 1

TOP BARS OTHER BARSSIZEBAR LAP

CLASS CASE 2OTHER BARSTOP BARS

BA 12

#4 BA 15

#5 BA 19

#6 BA 23

#7 BA 26

#8 BA 30

#9 BA 34

#10 BA 38

#11 BA 42

f'c = 4000 PSI, NORMAL WEIGHT

NOTES:

CASE 1

BEAMS AND COLUMNS:CONCRETE COVER >/= TO BAR DIAMETER, C-C BARSPACING >/= TO 2X BAR DIAMETER AND WITH STIRRUPSOR TIES THROUGHOUT TENSION LAP SPLICE LENGTH

NOTLESS THAN THE CODE MINIMUM.

OTHER MEMBERS:CONCRETE COVER >/= TO THE BAR DIAMETER AND C-CBAR SPACING >/= TO 3X BAR DIAMETER.

CASE 2

BEAMS AND COLUMNS:CONCRETE COVER < BAR DIAMETER AND C-C BARSPACING < 2X BAR DIAMETER.

OTHER MEMBERS:CONCRETE COVER < BAR DIAMETER OR C-C BARSPACING < 3X BAR DIAMETER.

* LAP CLASS "B" IS TO BE USED UNLESS OTHERWISESPECIFIED IN THESE CONTRACT DOCUMENTS.

2419

1915

3628

2822

3225

2519

4837

3729

4031

3124

6047

4736

4837

3729

7256

5643

7054

5442

10681

8163

8062

6248

12193

9371

9170

7054

136105

10581

10279

7961

153118

11891

11387

8767

170131

131101

EDGE BEFOREREMOVING BULKHEADEDGE TO MATCHCONSTRUCTION JOINT

VAPOR BARRIER

BULKHEAD DETAILS FOR CONSTRUCTION JOINT

TYPICAL SLAB ON GRADE JOINT DETAILS

MAX

. = 1

5'-0

"U

.N.O

.

SLAB PLACEMENT SEQUENCE

CONSTRUCTION JOINT

SAWED CONTROL JOINT

INFILLSTRIPS

SAWED CONTROL JOINT DETAIL

MAX. = 15'-0"U.N.O.

T/4 MIN.

STRIPSCAST FIRST

T T

1/4" MAX.

3-201

BREAK BOND TO LATERCOMPOUND TO THE SIDESOF THE EARLIER POUR

T/4

(1 1

/2"

MIN

.)

T/10 (3/4" MIN.)

METAL KEY

BULKHEAD OF2" LUMBER.

SAWED JOINT TOBE FILLED WITHFIELD MOLDEDFILLER-SEE SPECS.

NOTES:

1. CONCRETE FOR SLAB ON GRADE SHALL HAVE A MINIMUM COMPRESSIVESTRENGTH AS INDICATED ON THE "CONCRETE AND REINFORCING" NOTES.

2. SUPERPLASTICIZER SHALL BE USED IN SLAB ON GRADE CONCRETE - SEESPECIFICATIONS.

3. SLAB ON GRADE CONCRETE MIX SHALL HAVE A WATER-CEMENT RATIO ASINDICATED IN SPECS AND OR NOTES.

4. CONSTRUCTION JOINTS SHALL BE LOCATED A MINIMUM OF 5'-0" AWAYFROM ANY OTHER JOINTS TO WHICH THEY ARE PARALLEL.

5. SAW CUTTING SHALL BE DONE WITH A POWER SAW WITH A MASONRYCUTTING BLADE. CUTTING SHALL BE DONE AS SOON AS CONCRETEHARDENS ENOUGH SO THAT THE BLADE DOES NOT DISLODGE THEAGGREGATES.

6. WHERE SAWCUT IS DISCONTINUED AT A TRANSVERSE JOINT, STOP CUT2" SHORT.

7. SLAB REINFORING NOT SHOWN FOR CLARITY.

MONUMENT SIGN WALL 3-998

3' - 0"

1' -

4"

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

GROUT ALL CELLSSOLID BELOW GRADE

CONT. WALL FTG.REINF. W/ (4) #5CONT. & #4 @ 16"O.C. TRANS. W/ STDACI HOOK

8" ATLAS BRICK WALLW/ (1) #5 @ 32" O.C.SEE ARCH. DWG'S FORDIMENSIONS

T/WALL2' - 0"

8" BOND BEAM W/(2) #5 CONT.

T/SIGN6' - 0" MAXMONUMENT SIGN

AND CONNECTIONBY DELEGATEDENGINEER

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:02

PM

1442

S3.02TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

55

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

TYPICAL SLAB ON GRADE DETAILS 3-202

FINISHGRADE

1-#5 CONT.

MIN.

NOTE 5

2d ORt MIN.

2-#5 CONT.

11

NOTE 2

NOTE 3

d

AT DEPRESSION

2" MAX.1" MIN.

EXTERIORPLATFORM

ANCHORED ANGLE INDEPRESSION. WELDEDTO STRINGER

W.W.F.

2-#5 CONT.

NOTE 1

STAIRSTRINGER

AT STAIR

2-#5 CONT.

HAUNCH AT PARTITION(NO JOINT)

8" OR LARGERMASONRY NON-BEARING PARTITION

8"8"

12"

8"8"

12"

12"

1'-4"

12"

UNLESS NOTED ON PLANS:

1. SEE FOUNDATION NOTES FOR SLAB THICKNESS AND REINFORCING.2. SLABS SHALL BEAR ON COMPACTED FILL.3. COMPACTED FILL SHALL BE COVERED WITH VAPOR BARIER AT HAUNCHES.).

SEE SPECS.4. UNDER MACHINE EQUIPMENT DEEPEN SLAB TO 8" AND ADD TWO LAYERS OF

WELDED WIRE FABRIC BOTTOM, U.N.O5. FOR DEPRESSIONS - SEE ARCHITECTURAL DRAWINGS.6. AT CONSTRUCTION JOINTS USE WOOD FORMS WITH SHEAR KEYS.7. STOP WIRE MESH AT CONSTRUCTION JOINTS. CUT EVERY OTHER WIRE AT

SAWCUT JOINT.8. WHERE SLAB IS DOWELD INTO WALL, FIRST SLAB CONSTRUCTION JOINT TO

BE NOT MORE THAN 25 FEET FROM WALL.9. FOR EXPANSION JOINT LOCATION SEE PLAN. FOR DETAILS SEE

ARCHITECTURAL DRAWINGS.

TYP. JOINT IN 8" SLAB 3-999

0".T/FIN. FLR

EL.(SEE PLAN)

8" CONC. SLAB SEEPLAN FOR REINF.

2".

3".

5/8" DIA. SMOOTH BAR x 16" LONGGREASE ONE END OF DOWELSPACE DOWELS AT 24" O.C.

TYP MASONRY WALL DETAIL 4-001

LAP

SPLI

CE

ELEVATION PLAN

SEE

DET

. 4-0

23

NOTE:

PROVIDE INSPECTION PORT AT BOTTOM OF LIFT.IF GROUT LIFT IS GREATER THAN 4'-0".

9 GAGE TRUSSTYPE REINF.@ 16" O.C.VERT

VERT. WALLREINF. SEE PLANAND SECTIONS

MASONRY CONTROL JOINT 4-002

AT REGULAR BLOCKS

AT CONC. BM'S/KNOCK-OUT BLOCKS

NOTE: DISCONTINUE HORIZ REINF AT JOINT

NOTE: DISCONTINUE HORIZ REINF AT JOINT

NOTE:1. MAXIMUM SPACING OF CONTROL JOINT EQUALS 24'-0" OR THREE TIMES

WALL HEIGHT (WHICH EVER IS SMALLER)

STOP HORIZ. REINF. OFCONC. BM./KNOCK-OUTBLOCKS @ JOINT EXCEPT@ ROOF DIAPHRAGM

VERT. WALL REINF.SEE PLAN

WIRE TIE BARS ONONE SIDE OF JOINT

2 5/8"ø X 3'-0" SMOOTH BARS,GREASE ONE END TO BREAKBOND.PREMOLDED

RUBBER INSERT

CAULK EA. SIDEOF JOINT

PREMOLDEDRUBBER INSERT

VERT. WALL REINF.SEE PLAN

CAULK EA. SIDEOF JOINT

TYPICAL LINTEL OVERDUCT OPENING 4-004

8"MIN

SEE

ARC

H.

8"

8"MIN

PRECAST LINTEL BYPRECAST MANUF. IFOPENING IS ABOVECEILING USE LINTEL &IF OPENING IS BELOWCEILING USE U-BLOCKAS SHOWN IN DETAIL4-005

LINTELS FORWALLS SHOULDHAVE A CAPACITYOF 1500 PLF, U.N.O.

DOWEL AT LOCATIONSWHERE OPENINGCONFLICTS W/ TYP.WALL REINF.

PROVIDE LINTEL ATOPENINGS THATEXCEED 16" WIDE

TYPICAL LINTELOVER OPENING 4-005

OPE

NIN

G (S

EE A

RC

H.)

8"

OPENING (SEE ARCH.)

8"MIN

8"MIN

LINTELS FOR WALLSSHOULD HAVE ACAPACITY OF 1500PLF, U.N.O.

PROVIDE LINTEL W/SLOT AT END TOALLOW FOR VERT.BAR REINF. TO PASSTHRU CONTINUOUS

PRECAST LINTEL SEESCHEDULE 4-033

(2) ADD'L VERTICALBAR ON EACH SIDEOF OPENING

FIN. FLOORSEE PLAN

ATLAS BRICK WALL REINFORCING LAYOUT 4-009

NOTE #5 TYP.

CONTROL JOINTSEE NOTE #10

NOTE #9 TYP.

NOTES #1, #2TYPICAL

NOTE #8 TYP.

MAX. SPACING 24'-0"

NOTE #7 TYP.

NOTE #4 TYP.

NOTE #3 TYP.

LAP

SPLI

CE

SEE

DET

AIL

4-02

3

NOTES:

1. VERTICAL WALL REINFORCING SHALL ALIGN WITHVERTICAL FOUNDATION DOWELS. DOWELS SHALL BEPLACED AS SHOWN ON DETAILS WITH STANDARD ACIHOOK DIRECTLY ON TOP OF BOTTOM LAYER OFFOOTING REINFORCING. REFER TO WALLREINFORCING SCHEDULE ON PLAN FOR SIZE ANDSPACING.

2. TYPICAL VERTICAL WALL REINFORCING TO BEPLACED AS SHOWN ON DETAILS. GROUT CELLS FULLTHAT CONTAIN REINFORCEMENT.

3. REFER TO LINTEL SCHEDULE FOR SIZE, LOCATIONAND QUANTITY OF LINTEL REINFORCEMENT.

4. VERTICAL REINFORCING BARS MAY BE SPLICED IN6'-0" TO 8'-0" LENGTHS.

5. HORIZONTAL WALL REINFORCING SHALL BE TRUSSTYPE AT 16" O.C. ABOVE GRADE AND 8" O.C. BELOWGRADE UNLESS OTHERWISE NOTED ON PLANS ANDDETAILS. DISCONTINUE AT CONTROL JOINTS.

6. CONTRACTOR SHALL USE THE LOW LIFT METHOD OFGROUTED MASONRY CONSTRUCTION UNLESS CLEANOUTS ARE PROVIDED AT EACH VERTICALREINFORCING BAR.

7. REFER TO PLANS AND DETAILS FOR SIZE ANDLOCATION OF BOND BEAMS AND QUANTITY OFREINFORCING. LAP REINFORCING 24" MINIMUM.DISCONTINUE BOND BEAMS AT CONTROL JOINTS.

8. REFER TO LINTEL SCHEDULE NOTES FOR VERTICALBARS ADJACENT TO OPENING.

9. PROVIDE VERTICAL WALL REINFORCING IN FIRSTCELL NEXT TO CONTROLJOINTS/CORNERS/OPENINGS. TYPICAL.

10. VERTICAL CONTROL JOINTS SHALL TERMINATE ATTOP OF FOOTING.

11. PROVIDE CORNER BARS TO MATCH TYPE ANDQUANITY OF HORIZONTAL WALL REINFORCING,TYPICAL.

(2)-#5 BARS TYP.ABOVE & BELLOWOPENING

TYPICAL HAUNCH ATMASONRY WALLS 4-011

11

31" F

OR

#5'

S25

" FO

R #

4'S

MIN

.

3" CLR

.

1'-0

"

2'-0" MIN.

SEE FNDN PLANFOR MASONRY SIZE& REINFORCING

DOWELS TO MATCHVERT. WALL REINF.(FILL VOIDS SOLIDWITH MORTAR ATDWLS.)

#4 @ 24" TRANSV.

2-#5 CONT. BOTT.

S.O.G. SEE PLANFOR SIZE & REINF.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:11

PM

1442

S3.03TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

60

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

4-012PARTIAL ATLAS BRICKWALL SECTION

3" CLR

.

SEE PLAN

SEE

PLAN

1/2" PREMOLDEDJT. FILLER ANDSEALANT

CONC. FILL SOLID ALLCELLS BELOW S.O.G.

CONC. S.O.G.SEE FNDN PLANFOR BAL. OF INFO

CONC. FTG. - SEEFNDN PLAN & SCHEDFOR SIZE & REINF

ALT DIRECTIONOF HOOK

SEE FNDN PLAN FORMASONRY SIZEAND REINFORCING

DOWELS TO MATCHVERT. WALL REINF.

T/ SLABSEE PLAN

4-015PARTIAL ATLAS BRICKWALL SECTION

1/2" PREMOLDEDJT. FILLER ANDSEALANT

CONC. FILL SOLID ALLCELLS BELOW S.O.G.

CONC. S.O.G.SEE FNDN PLANFOR BAL. OF INFO

CONC. FTG. - SEEFNDN PLAN & SCHEDFOR SIZE & REINF

ALT DIRECTIONOF HOOK

SEE FNDN PLAN FORMASONRY SIZEAND REINFORCING

DOWELS TO MATCHVERT. WALL REINF.

T/ SLABSEE PLAN

SEE PLAN 3" CLR

.

SEE

PLAN

4-017

SLAB HAUNCH BEARINGON ATLAS BRICK WALL SECTION

11

1/2" PREMOLDEDJT. FILLER ANDSEALANT

CONC. FILL SOLID ALLCELLS BELOW S.O.G.

#4 AT 32" O.C.BEND BARSINTO SLAB

CONC. S.O.G.SEE FNDN PLANFOR BAL. OF INFO

(1) #5 CONT.

CONC. FTG. - SEEFNDN PLAN & SCHEDFOR SIZE & REINF

ALT DIRECTIONOF HOOK

T/ FTG.SEE PLAN

SEE PLAN 3" CLR

.

SEE

PLAN

8".

4-021

CONCRETE COLUMN TOMASONRY CORNER CONNECTION

3/4"EXP. JT.

CONT. DOVETAIL SLOTW/ 9 GAGE TIES AT16" O.C. VERT. TYP.

CAULK EACH SIDE

(1) #5

COMPRESSIVEMATERIAL

CONCRETECOLUMN, SEESCHEDULE FORREINF.

4-022

CONCRETE COLUMN TOMASONRY CONNECTION

CONT. DOVETAIL SLOTW/ 9 GAGE TIES AT16" O.C. VERT. TYP.

CONCRETE COLUMNSEE PLAN FOR SIZEAND REINF.

4-023

LAP SPLICE SCHEDULE SINGLEREINFORCED 8" ATLAS BRICK WALL

REMARKSLAP SPLICEBAR SIZE

24

18

36

30

48

54

42

#4

#3

#6

#5

#8

#9

#7

LAP SPLICE SCHEDULE FORSINGLE REINFORCED 8" ATLAS BRICK WALL

NOTES:

1. LENGTH OF SPLICES ARE BASED ON FLORIDA BUILDING CODE2014.

2. LAP SPLICES INDICATED ARE IN INCHES.3. THIS SCHEDULE IS FOR 8" ATLAS BRICK ONLY.4. SEE DETAIL FOR LAP SPLICE SCHEDULE FOR DOUBLE

REINFORCED 8" CMU.

4-025

LAP SPLICE SCHEDULE DOUBLEREINFORCED 8" ATLAS BRICK WALL

REMARKSLAP SPLICEBAR SIZE

24

18

30

#4

#3

#5

LAP SPLICE SCHEDULE FORDOUBLE REINFORCED 8" ATLAS BRICK WALL

NOTES:

1. LENGTH OF SPLICES ARE BASED ON FLORIDA BUILDING CODE2014.

2. LAP SPLICES INDICATED ARE IN INCHES.3. THIS SCHEDULE IS FOR 8" ATLAS BRICK ONLY.

7 5/8"

1 1/4" 1/2"

4-031

4-005

VERTICAL REINF.SEE PLAN

PRECAST LINTELSEE SCHEDULE 4-033

TYP. PRECAST LINTEL SECTION

BOTT. LINTELSEE ARCH.

4-032

TYP. CAST IN PLACE LINTEL

VERTICAL REINF.SEE PLAN

DESIGNER NOTE #1

CAST IN PLACELINTEL, SEESCHEDULE 4-033

BOTT. LINTELSEE ARCH.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:17

PM

1442

S3.04TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

61

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

4-033TYP. ATLAS BRICK LINTEL DETAIL & SCHEDULE

ATLAS BRICK SCHEDULE

TYPE-B

TYPE-A

8"

24" (TYPE B)

16" (TYPE A)

40" (TYPE C)

(2) #5

(2) #4

(2) #6

(2) #5

(2) #5

(2) #6

WALLWIDTH

24" N

OM

INAL

WALLWIDTH

16" N

OM

INAL

WALLTHICKNESS

LINTELDEPTH

BOTTOMREINFORCING

TOPREINFORCING

STIRRUPS& SPACING NOTES

NOTES:

1. AT ALL ATLAS BRICK DOOR OPENINGS, USE 16" ATLAS BRICK SOLDIER COURSE.2. GROUTED LINTEL (THROUGH) BLOCKS SHALL EXTEND A MINIMUM OF 8" BEYOND

FACE OF OPENING EACH SIDE UNLESS NOTED OTHERWISE. THE FIRST TWOVERTICAL CELLS EACH OF THE OPENING SHALL BE GROUTED AND CONTAIN (2) -#5 VERTICAL EACH FACE.

NOTE: THE FIRST CELL EACH SIDE OF THE OPENING SHALL BEGROUTED TO LINTEL LEVEL. SECOND CELL SHALL BE GROUTED TO ROOF LEVEL.

3. CONSTRUCTION/CONTROL JOINT SHALL NOT BE LOCATED WITHIN WIDTH OFOPENING, NOR SHALL IT BE LOCATED WITHIN 24" OF THE OPENING ON EITHERSIDE.

4. BRICK LINTEL BEARING SHALL BE SHORED DURING CONSTRUCTION ANDSHORING SHALL REMAIN IN PLACE UNTIL LINTEL DEPTH ATTAINS 75% OFSPECIFIED CONCRETE STRENGTH.

SEE SCHEDULEFOR REINF. TYP.

CONCRETEFILLED TYP.

CLEARSPAN

#3 @ 8"

#3 @6"

#3 @ 8"

1 THRU 4

1 THRU 4

1 THRU 4

UP TO 12' - 0'U.N.O. IN PLAN

UP TO 6' - 0"U.N.O. IN PLAN

UP TO 18' - 0"

8"

8"

NOTE 1

NOTE 1

TYPE-C

WALLWIDTH

40" N

OM

INAL

SEE SCHEDULEFOR REINF. TYP.

CONCRETEFILLED TYP.

NOTE 1

CMU LINTEL SCHEDULE

8" 8" (TYPE A) -(2) #5

WALLTHICKNESS

LINTELDEPTH

BOTTOMREINFORCING

TOPREINFORCING

STIRRUPS& SPACING NOTESCLEAR

SPAN

- -UP TO 9' - 0"U.N.O. IN PLAN

TYPICAL INTERIORWALL BRACE DETAIL 4-061

ANGLE SIZE"L1 & L2"≤

BRACE SCHEDULE

"L2" SEE SCHED."L1" SEE SCHED.

4" X 4" X 1/4"

3" X 3" X 3/16"

2" X 2" X 3/16"

12'-0"

8'-0"

6'-0"

3/16 TYP.

ATLAS BRICKWALL SEEPLAN FOR SIZEAND REINF.

DBL BOND BMW/ 2-#5 CONT.

PL. 4"x4"x1/4" TYP. ATSTEEL JOIST

PL. 6"x6"x3/8" TYP. EA.SIDE OF CMU W/(1)-1/2"ø THRU BOLT

METAL DECKSEE PLAN

NOTE:MAXIMUM SPACING OF WALL BRACING SHALL NOT EXCEED 36 TIMES THEWALL THICKNESS UNLESS NOTED OTHERWISE IN PLANS OR SECTIONS.

TYPICAL INTERIORWALL BRACE DETAIL 4-062

ANGLE SIZE"L1 & L2"≤

BRACE SCHEDULE

"L2" SEE SCHED.

4" X 4" X 1/4"

3" X 3" X 3/16"

2" X 2" X 3/16"

12'-0"

8'-0"

6'-0"

3/16 TYP.

"L1" SEE SCHED.

PL. 4"x4"x1/4" TYP.AT STEEL JOIST

PL. 6"x8"x1/2" W/(2)-3/8"ø HEADEDSTUDS 6" LONG

METAL DECKSEE PLAN

ATLAS BRICK WALLSEE PLAN FOR SIZEAND REINF.

BOND BM W/2-#5 CONT.

NOTE:MAXIMUM SPACING OF WALL BRACING SHALL NOT EXCEED 36 TIMES THEWALL THICKNESS UNLESS NOTED OTHERWISE IN PLANS OR SECTIONS.

TYPICAL INTERIORWALL BRACE DETAIL 4-063

ANGLE SIZE"L1" ≤

BRACE SCHEDULE

(BEYOND)

3/16 TYP.

4" X 4" X 1/4"

3" X 3" X 3/16"

2" X 2" X 3/16"

12'-0"

8'-0"

6'-0"

NOTE:ALTERNATE DIRECTION OF L BRACE AT EACH JOIST.

"L1"

"L1"

PL. 4"x4"x1/4" TYP.AT STEEL JOIST

PL. 6"x8"x1/2" W/(2)-3/8"ø HEADEDSTUDS 6" LONG

METAL DECKSEE PLAN

STEEL JOISTSEE PLAN

DBL. BOND BMW/ 2-#5 CONT.

ATLAS BRICK WALLSEE PLAN FORSIZE AND REINF.

TYPICAL FOR ALL UNIFORMALY DISTRIBUTED ANCHORAGE 4-082

SEE PLAN/SECTION FORMAX SPACING

NOTES:PROVIDE FIRST ANCHOR 6" (MAX) FROM EDGE OF MEMBER (ANGLE, CHANNEL,ETC.).SEE PLAN OR SECTION FOR MAXIMUM SPACING OF BALANCE OF ANCHORS.

SEE PLAN/SECTION FORMAX SPACING

6" 6" 6" 6" 6"

BEAM OVER COLUMN ANDCOLUMN OVER BEAM 5-001FRAMED CONNECTION

AT TUBE/PIPE COLUMN

MAX.D+4 1/2"

MIN.1 1/4"

MIN.1 1/4"

D

MIN.1/4"

(TYP)

MILL COL.

COL.

1/2"

1/2T

-MIN

T-M

AX

3" MIN

BOLTS AS REQUIREDBOLTS AS REQUIRED

1/2T

-MIN

T-M

AX

1 1/4"

3 1/2" MIN

3"3"

d TK

K

SHOP BOLTED CONN. SHOP WELDED CONN.

NOTE #1

5/8" MIN. COL. CAP PLATEWELDED TO COL., LENGTH OFCAP PLATE AS SHOWN. WIDTHOF CAP PL. = BM. FLANGE (OR= TO COL. WIDTH + 1",WHICH- EVER IS LARGER).CONN. PL TO BEAM WITH4-3/4" ø H.S. BOLTS

IF COL. ABOVE USE FOURSTIFFENER PLATES SAMESIZE AS COL. FLANGES,3/8" MIN., IF COL. WEBIS PERPENDICULAR TOBM. WEB USE "T"SECTION. ALL STIFFENERSTO BE FITTED & WELDEDFULL LENGTH.

IF NO COL. ABOVEUSE TWOSTIFFENER PLATES3/8" MIN. UNLESSNOTED, FITTED &WELDED

COL. MAY OCCUR ABOVE FORTYPE SIZE & ORIENTATIONSEE PLAN & COL. SCHED.

BASE PLATESAME AS COL.CAP PLATEDESCRIBEDBELOW.

NOTE: DIMENSIONS SHOWNAS DEFINED BY A.I.S.C.MANUAL OF STEEL CONSTR.

WELDPLATESWHEREVERPOSSIBLE

3/8" PL. MIN.CONT. THRUCOLUMN

TUBE ORPIPE COL.

WELD ASREQ'D.SEENOTE #12L's 5/16"

THK MIN.

NOTES:

1. ALL CONNECTIONS SHALL BEDESIGNED FOR MAX. UNIFORMLOAD CARRYING CAPACITY UNLESSGREATER REACTION IS SHOWN ONPLAN. IN ANY CASE, CONNECTIONS.SHALL NOT BE LESS THAN STD.A.I.S.C. CONNECTION FOR THEPARTICULAR BEAM. DEPTH.

2. DETAILER SHALL SUBMIT FORAPPROVAL, STANDARDCONNECTION DETAILSCONFORMING TO ABOVE DETAILSW/ERECTION DRAWING.SUBMISSION.

3. MILL COLUMNS. TO BEAR ORPROVIDE FULL PENETRATION WELDAT BASE PL'S & CAP PL'S ATCOLUMNS CARRYING BEAMS.

4. AT CONNECTION OF HUNG BEAM.TO CANTILEVERED BEAMS.PROVIDE STANDARD 2 LCONNECTION AS PER NOTE 1 FORLOAD CAPACITY OF HUNG BEAM.

5. WHERE BEAMS FRAME TO FITTEDSTIFFENERS AT COLUMNS PROVIDESHEAR PLATE CONNECTION W/STRENGTH CAPACITY AS PER NOTE1.

6. ALL BOLTS TO BE MIN. 3/4"ø. A-325H.S. BOLTS FRICTION-TYPE UNLESSNOTED OTHERWISE. ALL WELDINGELECTRODES TO BE E70 XX.

2L's 5/16"THK MIN.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:22

PM

1442

S3.05TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

62

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

5-005STEEL BEAM TO CONCRETE CONNECTION

W10

EMBED PLATE SCHEDULE

1/2" X 10" X 10"

NO. OF 3/4"øHEADED STUDSPLATE SIZE "A" (IN.) "B" (IN.) "C" (IN.)

4 6" 6 7

W12 1/2" X 10" X 12" 6 6" 4 9

W14 1/2" X 10" X 14" 6 6" 5 11

W16 1/2" X 10" X 16" 8 6" 4 13

W18 3/4" X 10" X 18" 10 6" 3 1/2 15

W21 3/4" X 10" X 21 1/2" 12 6" 3 1/2 18 1/2

W24 3/4" X 10" X 22" 14 6" 3 19

W27 1" X 10" X 25" 14 6" 3 1/2 22

BEAMSIZE

"C"

STEEL BEAMSEE PLAN

2" "A"

2"

2"

2"

"B" T

YP.

DBL L4" X 3" X 3/8"CONNECT TO BEAM W/3/4"ø A325 BOLTS ONHORIZONTAL SLOTTEDHOLES. BOLTS TO BEHAND TIGHTENED TACKWELD NUT TO BOLT ORPLATE WASHER

EMBED PLATESEE SCHEDULE

3/4"ø HEADEDSTUD X 6" LG.

5/16

CONC BEAM / WALLSEE PLAN

HSS4X4 1/2" X 5 1/2" X 5 1/2" 4 1 1/2" 1 1/2 N/A

HSS6X4 1/2" X 7 1/2" X 5 1/2" 4 1 1/2" 3 1/2 N/A

HSS10X4 1/2" X 11 1/2" X 5 1/2" 4 1 1/2" 7 1/2 N/A

NOTE:WHERE EMBED IS REQUIRED AT LOCATIONSWITHOUT A CONCRETE BEAM SAW CUT FACE SHELLOF CMU/ATLAS BRICK AND CAST INTO FILLED CELL

TYP. OPEN WEB JOIST DETAILS - SLOPED ROOF 5-201

SEE

PLAN

@ POINT LOAD BETWEENJOIST PANEL POINTSADD L 2 X 2 X 3/16

OPEN WEBJOISTS SEEPLANS SUPPORTING STEEL

MEMBER-SEE PLAN

2 1/2" MIN.NOTE 1

W.P. (HIGH POINT)EL.- SEE PLAN(UNDERSIDE OFMTL DECK)

2 1/2" MIN.BEARING TYP.

@ POINT LOAD BETWEENJOIST PANEL POINTSADD L 2 X 2 X 3/16

2 1/2" MIN.NOTE 1

W.P. (LOW POINT)EL.- SEE PLAN(UNDERSIDE OFMTL DECK)

NUMBER OF ROWS & TYPEOF BRIDGING PERMANUFACTURERSPECIFICATIONS.SEE PLAN

BLDG. END

SPANDRELBEAM

BRIDGING

ENDBAY

INTERIORBAY

JST. SPACING

TIEBEAM

1/8 3"1/8 3"TYP UNO

COLUMN

NOTES:

1. BEARING ENDS OF SLOPED JOISTS SHALL BE HORIZONTAL TO OBTAIN FULL CONTACT WITH SUPPORTING MEMBERS.2. AT END BAYS, EXTEND ALL BOTTOM CHORDS & CONNECT TO SPANDREL BEAMS.3. CEILING EXTENSIONS ARE REQUIRED FOR O.W.J. ABOVE HUNG CEILING AREAS WHERE SHOWN ON ARCH. DRAWINGS.

5-202

DBL. BOND BEAMREINF. W/ (2) #5CONT. IN KNOCKOUT BLOCK

VERTICAL REINF.CONT. TO TOP OFATLAS BRICKPARAPET WALL

CONT. L4x4x1/4 (LLV) DECKCLOSURE FASTEN TO ATLASBRICK WALL W/ 3/4"ø EXP. BOLTSAT 24" O.C. MAX. EMBED DEPTH =4 1/2"

WELD DECK TOCLOSURE ANGLE

METAL DECK- SEE PLAN

STEEL JOIST- SEE PLAN

CROSS BRIDGING- SEE PLAN

HORIZ. BRIDGINGTYPICAL

L3x3x1/4 W/(1) 5/8"ø x 4 1/2"LONG EXP. BOLT

GROUT CELL SOLIDAT CONNECTION

SECTION AT WALLPARALLEL TO JOIST

T/PARAPET WALLSEE ARCH. DWG

B/BOND BEAMSEE ARCH. DWG

5-203SECTION AT WALLSINGLE BEARING

DBL. BOND BEAMREINF. W/ (2) #5CONT. IN KNOCKOUT BLOCK

VERTICAL REINF.CONT. TO TOP OFATLAS BRICKPARAPET WALL

METAL DECK- SEE PLAN

STEEL JOIST- SEE PLAN

L6x4x1/2 x 11 1/2"LONG (LLH) W/(2) 5/8"ø x 12" LONGHEADED STUDS

CONT. L4x4x1/4 DECKCLOSURE FASTEN TOATLAS BRICK WALL W/3/4"ø EXP. BOLTS AT 24"O.C. MAX. EMBEDDEPTH = 4 1/2"

3/16 3"3/16 3"

T/PARAPET WALLSEE ARCH. DWG

B/BOND BEAM

3/163/16

5-204

VERTICAL REINF.CONT. TO TOP OFATLAST BRICKPARAPET WALL

CONT. L4x4x1/4 (LLV) DECKCLOSURE FASTEN TO ATLASBRICK WALL W/ 3/4"ø EXP. BOLTSAT 24" O.C. MAX. EMBED DEPTH =4 1/2"

WELD DECK TOCLOSURE ANGLE

METAL DECK- SEE PLAN

STEEL JOIST- SEE PLAN

CROSS BRIDGING- SEE PLAN

HORIZ. BRIDGINGTYPICAL

L3x3x1/4 W/(1) 5/8"ø x 4 1/2"LONG EXP. BOLT

CONC. TIE BEAM,SEE PLAN

SECTION AT WALLPARALLEL TO JOIST

T/PARAPET WALLSEE ARCH. DWG

U.S. / MTL DECKSEE PLAN

5-205SECTION AT WALLSINGLE BEARING

CONC. TIE BEAMW/ 2-#6 T&B CONT.#3 @ 18" TIES

VERTICAL REINF.CONT. TO TOP OFCMU PARAPETWALL

METAL DECK- SEE PLAN

STEEL JOIST- SEE PLAN

PL 1/2" X 4" X 6" W/(2) 1/2"ø X 4" LG.HEADED STUDS

CONT. L3x3x1/4DECK CLOSURE -WELD TO JOISTS

1/8 3"1/8 3"

PL 1/2" X 6" X 8" W/(2) 1/2"ø X 6" LG.HEADED STUDS

PL 1/2" X 3" X 6"

T/PARAPET WALLSEE ARCH. DWG

U.S. / MTL DECKSEE PLAN

5-212

2" 2"

JOIST BEARING DETAILS

BTWN. JOIST BEARING AT JOIST BEARING

BEARING ELEVATION

SLOPED BEARING ELEVATION

SEE PLANFOR REINF.

(2) #5 CONT.INSTALLED 2"BELOW JOIST SEAT

#3 "U-BAR" - SPLICE MIN.OF 12" TO BEAM TIES.INSTALL ONE ON EACHSIDE OF JOIST BEARINGPOCKET & MATCH BEAMTIES IN BETWEEN

SEE PLANFOR REINF.T/CONC. BM.EL. = VARIES

3/16 3STEEL JOIST- SEE PLAN

(2) #5 BARS CONT.INSTALLED 2" BELOWJOIST SEAT

PL 1/2"x6"x8" W/(2) 1/2"ø x 6" LONGHEADED STUDS

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:28

PM

1442

S3.06TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

63

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

5-301TYP. DECK REINF. @ ROOFDRAIN W/O SUMP PAN

SEE NOTE #1

NOTE:

1. SEE DETAIL 5-302 FOR STEEL REINFORCINGAROUND ROOF DRAIN OPENING.

METAL ROOF DECK,SEE PLAN

ROOF DRAIN, SEEARCH. DWG'S

30X30 SHEET METAL- 10 GA.MIN. FIELD WELDED TO M.D.CENTER ON ROOF DRAIN. 6- 1/2" ø FUSION WELDS MIN.(2 PER RIB) AT OPP. ENDSOF 30X30 SHT.

5-302TYP. ROOF OPN'G DETAIL

SEAT DETAIL

SHOP WELD

OPN'G

FRAME DETAIL

SEAT

BM OR JOIST

NOTE #1

"W"

"W"

NOTES:

1. ANGLES ALL SIDES UNLESS BEAMS SHOWN ON PLAN:L2X2X1/4 FOR "W" < 2'-0"L3X3X1/4 FOR "W" < 4'-0"L4X4X1/4 FOR "W" < 6'-0"

2. FOR "W" > 6'-0" USE L OR "W" BEAM. L SIZE OR DEPTH OFW BEAM. EQUAL TO SPAN DIMENSION IN INCHES.MINIMUM THICKNESS = 1/4".

3. FOR W > 10'-0" CONTACT ENGINEER OF RECORD FORDETAIL.

PROVIDE FRAMESFOR OPENINGS 8"OR MORE (LARGERDIMENSION OR DIA.)INCLUDING ROOFDRAINS & SUMPS

SEAT SAME SIZE ASSUPPORT FRAME 1/4 2

TYPICAL METAL DECK DETAILS 5-304

DECK DIRECTION SYMBOL

TYP. EDGE ANGLE DECK SUPPORT

TYP. FLOOR DECK SUPPORT AT COLUMNS

TYP. DET. @ DECK DIRECTIONCHANGE BETWEEN JOIST SEATS

TYP. ROOF EDGE ANGLE (BY METALDECK CONTRACTOR) WHERE DECK ISPARALLEL TO WALLS & UNSUPPORTEDPROVIDE L3 1/2" x 3 1/2" x 1/4" CONT. OR12 GA. BENT PLATE CONT. FIELD WELDTO STEEL JOISTS OR RAISED BEAMS

PROVIDE DECKSUPPORTS @COLUMNS BY MET.DK. CONTR. (MAY BESHEET METAL)

L5" x 3" x 1/4" CONT.-CUTVERT. LEG AS REQUIREDAT JOIST SEAT

BEAM & JOISTSSEE PLAN

COL. BM. OR JOIST SIZESEE FRAMING PLAN

DIRECTION OF METAL DK.PERPENDICULAR TO THESUPPORTING MEMBERS

METAL DECK CONTRACTOR TO PROVIDERIDGE AND VALLEY PLATES AS REQUIRED.

CONT. SHEET METALCLOSURE PLATE

BEAM & COLUMNSEE PLAN

BEAM & JOISTSSEE PLAN

TYP. 1 1/2" DECKFASTENER LAYOUT 5-305A

EXAMPLE

36/3-1

36/7

36/5

36/4

36/3

NO. OF SIDE LAP FASTENERS

NO. OF SUPPORT FASTENERS

WIDTH OF METAL DECK

NOTES:

1. USE 5/8"ø PUDDLE WELD AT SUPPORTS AND #12 SCREWS ATSIDE LAPS.

2. USE 36/7-4 UNLESS NOTED OTHERWISE IN PLANS.

TYP. 4" DECK FASTENERLAYOUT 5-305B

EXAMPLE

24/6-24

24/3

24/6

SIDE LAP FASTENER SPACING

NO. OF SUPPORT FASTENERS

WIDTH OF METAL DECK

NOTES:

1. USE 3/4"ø PUDDLE WELD AT SUPPORTS AND #12 SCREWS ATSIDE LAPS.

2. USE 24/6-24 UNLESS NOTED OTHERWISE IN PLANS.

5-321TYPICAL ADDITIONAL WEB REINFORCEMENT FORCONCENTRATED LOAD (WHEN POINT LOAD IS GREATER THAN 40 POUNDS)

GREATER6" OR

GREATER6" OR

POINTLOADMETAL DECKING

SEE PLAN

LOAD AT TOP CHORD

STEEL JOISTSEE PLAN

L2x2x3/16 EACH SIDEFOR POINT LOAD TOJOIST PANEL POINT

LOAD AT BOTTOM CHORD

METAL DECKINGSEE PLAN

POINTLOAD

STEEL JOISTSEE PLAN

L2x2x3/16 EACH SIDEFOR POINT LOAD TOJOIST PANEL POINT

5-400

EXTERIOR METAL STUD WALL DESIGN NOTES:

1. CALCULATE PROPERTIES AND LOAD CAPACITIES OF MEMBERS PER THEAISI SPECIFICATIONS FOR DESIGN OF COLD-FORMED STEEL STRUCTURALMEMBERS.

2. DESIGN EXTERIOR CURTAIN WALL TO SUSTAIN WIND LOADS INDICATED INTHE SCHEDULE OF LOADS DRAWING.

3. LIMIT LATERAL DEFLECTIONS UNDER DESIGN LOADS TO L/800 OR 3/8"WHICH EVER IS SMALLER FOR THOSE AREAS WITH BRICK CLADDING ANDL/360 FOR ALL OTHER AREAS.

4. PROVIDE SLIDE CLIPS OR DEFLECTION TRACKS ON THE UNDERSIDE OFTHE ELEVATED LEVELS TO ALLOW FOR A MAXIMUM LIVE LOAD VERTICALDEFLECTION OF APPROXIMATELY L/360 AT MID SPAN BETWEENCOLUMNS.

5. DIAGONAL KICKERS ARE NOT ALLOWED, UNLESS APPROVED IN WRITINGBY ARCHITECT AND ENGINEER OF RECORD.

6. DESIGN ALL CONNECTIONS TO SUSTAIN THE MAXIMUM DESIGN LOADS.7. ALL DETAILS DRAWINGS SHOWN ARE MINIMUMS REQUIRED FOR

PARTICULAR CONDITIONS. CONTRACTOR IS RESPONSIBLE TO SUBMITSIGN AND SEALED DRAWINGS AND CALCULATIONS FOR A WALL SYSTEMTHAT COMPLIES WITH THESE NOTES, THE SPECIFICATIONS AND THECONTRACT DOCUMENTS INCLUDING BUT NOT LIMITED TO STRUCTURALAND ARCHITECTURAL DRAWINGS.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:31

PM

1442

S3.07TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

64

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

STUD LATERAL BRACINGSCREW ATTACHMENT 5-401(3 5/8" THRU 8" MEMBERS)

(3 5/8" THRU 8" MEMBERS)

3/4"BOTHSIDES

"CSJ" STUD

1/2"

3/4"

SIDESBOTH

3/4"

3/4"

3/4"

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERS ANDCONNECTIONS USED SHALL BE AS DESIGNEDBY SPECIALTY CONTRACTOR ENGINEER. SEEDETAIL 5-400 THIS DRAWING.

1 1/2" X 2" X 16 GACLIP ANGLE 1/4"LESS THAN STUDWIDTH (4) 5/8" S-12SCREWS REQ'D.

1 1/2" COLD-ROLLEDCHANNEL

STUD LATERAL BRACINGWELD ATTACHMENT(3 5/8" OR SMALLER MEMBERS IN16 GA OR HEAVIER THICKNESS)

STUD LATERAL BRACINGWELD ATTACHMENT

1 1/2" X 2" X 16 GA.CLIP ANGLE 1/4"LESS THAN STUDWIDTH

"CSJ" STUD

1 1/2" COLD-ROLLEDCHANNEL

"CSJ" STUD

1 1/2" COLD-ROLLEDCHANNEL

TYPICAL STUD TOCONCRETE CONNECTION 5-402

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERSAND CONNECTIONS USED SHALL BE ASDESIGNED BY SPECIALTY CONTRACTORENGINEER. SEE DETAIL 5-400 THIS DRAWING.

"CSJ" STUD

16 GA. MIN.CONT. TRACK

WELD FULL WIDTH ATBOTH STUD FLANGES,OR USE #10 SCREWEA. STUD FLANGE (TYP)

5/32"ø POWER DRIVENFASTENERS @ EA. STUD OR 12" O.C. MAX. (STAGGER)W/ MIN 1 1/4" PENETRATION

NOTE:PROVIDE ONE ADDT'L FASTENER AT NO MORE THAN 3" FROM THEEND OF THE TRACK. TERMINATE TRACKS AT MID POINT BETWEENSTUDS SPACING SPLICE BY SCREWING A STUD SECTION BETWEENVERTICAL STUDS TO THE RUNNER TRACK USING #10 SCREWS.

5-405TYPICAL EXTERIOR FRAMING AT ROOF

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERSAND CONNECTIONS USED SHALL BE ASDESIGNED BY SPECIALTY CONTRACTORENGINEER. SEE DETAIL 5-400 THIS DRAWING.

NOTE: 6

NOTE: 5

NOTE: 5 NOTE: 5NOTES:

1. FASTEN ALL TRACKS TO CONCRETE SLABS,SEE DETAIL 5-402.

2. FASTEN ALL END STUDS TO CONCRETECOLUMNS W/ POWDER ACTUATED FASTENERS5/32"ø @ 12" O.C. (1 1/4" MIN PENETRATION).

3. ALL BUILD UP MEMBERS ARE TO BEFASTENED TOGETHER W/ SCREWS @ 6" O.C.(MAX.).

4. CONNECTION OF HEADER TO JAMB SHALL BEW/ MINIMUM DOUBLE 14 GA - 2 X 2 CLIPSW/ (2) 1/2" TYPE S-12 SCREWS.

5. MINIMUM (3) CR CHANNELS BUILD UPMEMBERS. ACTUAL QUANTITY, SIZE AND GAGEAS REQUIRED.

6. MINIMUM (2) CR CHANNELS AND (1) CSJBUILD UP MEMBER. ACTUAL QUANTITY,SIZE AND GAGE AS REQUIRED.

TYPICAL STUDAT 16" O.C.

BEYOND

HORIZ. BRACINGAT 4'-0" O.C. MAX.SEE TYP. DETAIL5-401

TYPICAL STUDAT 16" O.C.

CRIPPLES CSJ STUDAT 16" O.C. MAX.

16 GA. MIN. CONT.TRACK - SEE DETAIL5-402

BOXED HEADER TOJAMB CONNECTION 5-406

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERSAND CONNECTIONS USED SHALL BE ASDESIGNED BY SPECIALTY CONTRACTORENGINEER. SEE DETAIL 5-400 THIS DRAWING.

JAMB ASREQUIRED

BUILT-UP HEADERAS REQUIRED

SECURE TO HEADEREACH SIDE ASREQUIRED

SIDE VIEW

1"

1"

1/2"

1/2"

5-409

BOXED HEADER TO JAMBCONNECTION W/ CLIP ANGLES

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERSAND CONNECTIONS USED SHALL BE ASDESIGNED BY SPECIALTY CONTRACTORENGINEER. SEE DETAIL 5-400 THIS DRAWING.

(2) 2"x12" 16 GA CLIPANGLES ONE TOP ANDONE BOTTOM OF HEADER1/2" LESS THAN STUD WIDTH.USE (2) #10 SCREWS ON EACHLEG OF CLIP

BUILT-UP HEADERAS REQ'D.

JAMB ASREQ'D.

SIDE VIEW

1"

1"

1/2"

1/2"

5-410

SILL TO JAMBCONNECTION

METAL STUDS MEMBERS AND CONNECTIONSSHOWN ARE MINIMUMS. FINAL MEMBERSAND CONNECTIONS USED SHALL BE ASDESIGNED BY SPECIALTY CONTRACTORENGINEER. SEE DETAIL 5-400 THIS DRAWING.

(2) 2"x12" 16 GA CLIPANGLES ONE TOP ANDONE BOTTOM OF HEADER1/2" LESS THAN STUD WIDTH.USE (2) #10 SCREWS ON EACHLEG OF CLIP

BUILT-UP HEADERAS REQ'D.

JAMB ASREQ'D.

NO

TE:

IN C

ASE

OF

CO

NFL

ICT

BETW

EEN

INFO

RM

ATIO

N S

HO

WN

ON

TH

IS D

RAW

ING

, SEC

TIO

N D

RAW

ING

S O

R A

RC

HIT

ECTU

RAL

DR

AWIN

GS,

IT IS

TH

E C

ON

TRAC

TOR

'S R

ESPO

NSI

BILI

TY T

O IN

FOR

M T

HE

ARC

HIT

ECT

AND

EN

GIN

EER

OF

SUC

H C

ON

FLIC

T IN

OR

DER

TO

REC

EIVE

A C

LAR

IFIC

ATIO

N B

EFO

RE

PRO

CEE

DIN

G T

O W

OR

K. D

IMEN

SIO

NS,

SIZ

ES A

ND

REI

NFO

RC

EMEN

T O

FST

RU

CTU

RAL

ELE

MEN

TS S

HO

WN

IN T

HIS

DR

AWIN

G A

RE

MIN

IMU

M T

O B

E U

SED

UN

LESS

NO

TED

OTH

ERW

ISE

(U.N

.O.)

IN P

LAN

S.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:35

PM

1442

S3.08TYPICAL DETAILS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

65

RBIDJM

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

T/PARAPET WALL13' - 4"

AB

FILL ALL CELLS SOLID W/ GROUTBELOW FIN FLR, TYP.

CONT WALL FOOTING, SEEPLAN FOR REINF

VAPOR BARRIER

WELDED WIRE MESH,TYP.

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

KNOCK-OUT BLOCK ATSILL REINF. W/ (2)-#5 CONT.(EXTEND 8" PAST EA. SIDEOF OPENING)

PRECAST LINTEL, SEE TYPDETAIL 4-033/S3.03

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

8" CMU WALL, SEE PLAN &WALL SCHEDULE FORREINF.

S3.065-212

S3.065-203

S3.044-012

STEEL SUPPORTCOLUMN, SEE PLAN

CON'T 8"x8"x1/2" DECKCLOSURE ANGLE

8"x52" CONC. BEAM,SEE SCHEDULEFOR REINFORCING.SEE ARCH DWGSFOR CHAMFER

3/163/16

TYP.

T/WALL15' - 0"

UMD11' - 6 1/2"

UMD19' - 3 1/2"

3/163/16

TYP.

CJP.

EMBED PL 8x16x3/4W/(6) 3/4" Ø x 6" LONGHEADED STUDS

EMBED PL 8x8x1/2w/(4) 3/4" Ø 6" LONGHEADED STUDS

1/4" CAP PLATE

HSS 6x4x1/4 (LSH)

CONT. L4x4x1/4

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

B

VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF BEAM,SEE PLAN

STEEL SUPPORT COLUMN,SEE PLAN

S3.044-017

1/4" CAP PLATE

CON'T L8"x8"x1/2" DECKCLOSURE ANGLE

8"x20" CONC. BEAM,SEE SCHEDULE FORREINFORCING. SEEARCH DWGS FORCHAMFER

STEEL COLUMN,SEE PLAN

8" ATLAS BRICK WALL,SEE PLAN & WALLSCHEDULE FOR REINF.

4' - 0"

8' - 0"

12' - 0"T/ BOND BEAM

T/ BOND BEAM

T/ BOND BEAM

THICKENED SLABBEYOND, SEE PLAN

3/16" 2"-12"3/16" 2"-12"

6" EACH END

CLIP ANGLE 4x4x5/16x4"W/ (1-) 3/4" Ø EXP. BOLT5" MIN. CONC. EMBED

T/WALL15' - 0"

UMD19' - 3 1/2"

CJP.

3/163/16

TYP.

EMBED PL 8x16x3/4W/(6) 3/4" Ø 6" CONC.HEADED STUDS

CONT. L4x4x1/4

HSS 6x4x1/4 (LSH)

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:40

PM

1442

S4.01WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

66

RBIDJM

SCALE: 3/4" = 1'-0"S4.01WALL SECTION 2S2

SCALE: 3/4" = 1'-0"S4.01WALL SECTION 1S1

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

T/PARAPET WALL13' - 4"

11

FILL ALL CELLS SOLID W/GROUT BELOW FIN FLR, TYP.

CONT WALL FOOTING, SEEPLAN FOR REINF

VAPOR BARRIER

WELDED WIRE MESH,TYP.

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

KNOCK-OUT BLOCK ATSILL REINF. W/ (2)-#5 CONT.(EXTEND 8" PAST EA. SIDEOF OPENING)

SOLDIER COURSE LINTEL,SEE TYP DETAIL4-033/S3.05

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

8" ATLAS BRICK WALL, SEEPLAN AND WALL SCHEDULEFOR REINF.

T/ OPENING

T/BOND BEAM

S3.044-012

S3.065-203

12' - 0"

UMDVARIES

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

10

FILL ALL CELLS SOLID W/GROUT BELOW FIN FLR, TYP.

CONT WALL FOOTINGBEYOND, SEE PLAN.

VAPORBARRIER

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

KNOCK-OUT BLOCK AT SILLREINF. W/ (2)-#5 CONT.

4" ATLAS BRICK BONDBEAM W/ (2) #5

ROOF DECK, SEE PLAN

T/BOND BEAM

CONT. 8" BOND BEAMW/ (2) #5 BARS

S3.044-015

8" ATLAS BRICK WALL, SEEPLAN AND WALL SCHEDULEFOR REINF.

T/BOND BEAM

8"x20" CONC. BEAM, SEESCHEDULE FOR REINF. SEEARCH. DWGS FOR CHAMFER

S3.065-203

S3.055-001

CONT. L8"x8"x1/2" DECKCLOSURE ANGLE

STEEL SUPPORTCOLUMN, SEE PLAN

16" SOLDIER COURSE W/ (2)#6 T&B #3 TIES @ 8" O.C.

T/BOND BEAM

T/BOND BEAM

STEEL BEAM, SEE PLAN

13' - 4"

8' - 0"

4' - 0"

UMDVARIES

COLUMNFOOTING,SEE PLAN.

T/WALL15' - 0"

UMD12' - 0"

12' - 0"

3/163/16

TYP.

HSS OUTRIGGERS INSIDEMETAL DECK FLUTES, SEEPLAN. CUT METAL DECK ATROOF PURLIN LOCATIONSTO WELD OUTRIGGERS TOPURLINS

EMBED PL 8x16x3/4W/(6) 3/4" Ø x 6" LONGHEADED STUDS

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:44

PM

1442

S4.02WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

67

RBIDJM

SCALE: 3/4" = 1'-0"S4.02WALL SECTION 3S3

SCALE: 3/4" = 1'-0"S4.02WALL SECTION 4S4

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

T/PARAPET WALL13' - 4"

1 2 3

T/BOND BEAM4' - 0"

T/BOND BEAM12' - 0"

FILL ALL CELLS SOLID W/GROUT BELOW FIN FLR, TYP.

CONT WALL FOOTING,SEE PLAN FOR REINF

VAPOR BARRIER

WELDED WIRE MESH,TYP.

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

8" ATLAS BRICK WALL, SEEPLAN AND WALL SCHEDULEFOR REINF.

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT WALL FOOTING,SEE PLAN FOR REINF

VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

ROOF DECK, SEE PLAN

8"X20" CONC. BEAM,SEE SCHEDULEFOR REINF. SEEARCH. DWGS FORCHAMFER

S3.065-203

S3.065-203

S3.044-015

S3.044-012

HSS OUTRIGGERS INSIDEMETAL DECK FLUTES, SEEPLAN. CUT METAL DECK ATROOF PURLIN LOCATIONS TOWELD OUTRIGGERS TOPURLINS

STEEL ROOF BEAM,SEE PLAN

LT GAUGE MTL STUDWALL, SEE ARCH DWGS

CON'T L8"x8"x1/2" DECKCLOSURE ANGLE

T/BOND BEAM8' - 0"

UMD11' - 5"

T/BOND BEAM15' - 0"

UMD

UMD

3/163/16

TYP.

T/CONC. BEAM15' - 0"

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

T/PARAPET WALL13' - 4"

B

T/BOND BEAM

T/BOND BEAM

FILL ALL CELLSSOLID W/ GROUTBELOW FIN FLR, TYP.

CONT WALLFOOTING, SEEPLAN FOR REINF

BOND BEAM W/ (2) #5 BARSAT TOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

8" ATLAS BRICK WALL,SEE PLAN AND WALLSCHEDULE FORREINF.

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

T/BOND BEAM

12' - 0"

8' - 0"

4' - 0"

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

VAPORBARRIER

SLAB ON GRADE,SEE PLAN

UMDVARIES

S3.044-012

S3.065-202

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:49

PM

1442

S4.03WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

68

RBIDJM

SCALE: 3/4" = 1'-0"S4.03WALL SECTION 5S5

SCALE: 3/4" = 1'-0"S4.03WALL SECTION 6S6

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

76

S3.044-015

T/BOND BEAM

8" ATLAS BRICK WALL,SEE PLAN AND WALLSCHEDULE FOR REINF.

T/BOND BEAM

T/BOND BEAM

S3.065-005

8" CONC. BEAM,TOP/BEAM EL. VARIES.SEE ARCH. DWGS FORCHAMFER

ROOF DECK,SEE PLAN

STEEL BEAM,W/ 1/2"x24 1/2" CONT.PLATE EACH SIDE SEEPLAN

VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

LEAVE OFF SIDE PLATESTO MAKE CONNECTIONSFIELD WELD PLATES ANDGRIND WELD SMOOTH

4' - 0"

8' - 0"

12' - 0"

13' - 4"T/BOND BEAM

T/ FRAMINGVARIES

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. EMBED PL 1/2"TH. x 6"W. W/ 1/2"Øx6" LONG HEADED STUDS @ 24" O.C.

SLAB ON GRADE0' - 0"

G

STEEL ROOFBEAM, SEE PLAN

ROOF DECK,SEE PLAN

VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

STEEL BEAM,SEE PLAN

CONT 16 GA DECLCLOSURE VALLEYPLATE

3/16"TYP.

3/16"3/16"

TYP.

T/BEAM18' - 6"

STEEL ROOFBEAM, SEE PLAN

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

B

ROOF DECK,SEE PLAN

8"x20" CONC.BEAM, SEESCHEDULEFOR REINF.SEE ARCHDWGS FORCHAMFER

HSS BEAM,TYP. SEE PLAN

CONC. SLAB,SEE PLAN

THICKENED SLAB,SEE PLAN

CONCRETE FOOTING,SEE PLAN VAPOR

BARRIER

CON'T L8"x8"x1/2" DECKCLOSURE ANGLE

T/ CONC. BEAM15' - 0"

UMD.

STEEL SUPPORTCOLUMN, SEE PLAN.

C.J.P.

EMBED PL8x16x3/4 W/(6) 3/4"Ø x 6" LONGHEADED STUDS

19' - 3 1/2"

HSS 6x4x1/4 (LSH)

CONT. L4x4x1/4

HSS10X4X3/16 SEETYP. DETAIL5-005/S3.06 FORCONNECTIONS

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:53

PM

1442

S4.04WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

69

RBIDJM

SCALE: 3/4" = 1'-0"S4.04WALL SECTION 7S7

SCALE: 3/4" = 1'-0"S4.04WALL SECTION 8S8

SCALE: 3/4" = 1'-0"S4.04WALL SECTION 9S9

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

T/PARAPET WALL13' - 4"

A

CONC. SLAB,SEE PLAN

THICKENED SLAB,SEE PLAN

CONCRETE FOOTING,SEE PLAN

VAPORBARRIER

T/BOND BEAM

ATLAS BRICK LINTEL, SEETYP DETAIL 4-033/S3.05

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP) ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

12' - 0"

S3.065-202

S3.013-013

UMDVARIES

STEEL COLUMN,SEE PLAN

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

10

T/BEAM15' - 0"

CONC. SLAB,SEE PLAN

CONCRETE FOOTING,SEE PLAN

VAPORBARRIER

8"x20" CONC.BEAM, SEESCHEDULE FORREINF. SEEARCH DWGSFOR CHAMFER.

ATLAS BRICK LINTEL, SEETYP DETAIL 4-033/S3.05

STEEL BEAM,SEE PLAN

ROOF DECK, SEE PLAN

ROOF DECK, SEE PLAN

STEEL ROOF JOIST,SEE PLAN

FILL ALL CELLS SOLIDW/ GROUT BELOW FINFLR, TYP.

S3.065-203

S3.044-017

UMD

UMD18' - 11 1/2"

3/163/16

TYP.

VARIES

HSS OUTRIGGERS INSIDE METALDECK FLUTES, SEE PLAN. CUT METALDECK AT ROOF PURLIN LOCATIONSTO WELD OUTRIGGERS TO PURLINS

SLAB ON GRADE0' - 0"

LOW ROOF FRAMING11' - 5"

2

4" SLAB ON GRADE,SEE PLAN

8" CONC. SLAB ONGRADE, SEE PLAN.

ROOF DECK,SEE PLAN

HSS OUTRIGGERS INSIDE METALDECK FLUTES, SEE PLAN. CUT METALDECK AT ROOF PURLIN LOCATIONSTO WELD OUTRIGGERS TO PURLINS

U.M.D.18' - 6"

T/CONC BEAM15' - 0"

STEEL BEAM,SEE PLAN

S3.055-001

ATLAS BRICKLINTEL, SEE TYP.DETAIL 4-033/S3.05

STEEL COLUMN,SEE PLAN

S3.065-203

3/163/16

TYP.

CON'T L8X8X1/2CLOSURE ANGLE

8"X20" CONCBEAM, SEESCHEDULE FORREINF. SEEARCH DWGSFOR CHAMFER

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:32:57

PM

1442

S4.05WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

70

RBIDJM

SCALE: 3/4" = 1'-0"S4.05WALL SECTION 10S10

SCALE: 3/4" = 1'-0"S4.05WALL SECTION 11S11

SCALE: 3/4" = 1'-0"S4.05WALL SECTION 12S12

STEEL ROOFJOIST, SEE PLAN

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

LOW ROOF FRAMING11' - 5"

T/PARAPET WALL13' - 4"

L M

T/ OPENINGSEE ARCH.

T/ CONC. BEAM15' - 0"

T/ FRAMINGVARIES

12' - 0"T/ BOND BEAM

8" CMU WALL, SEE PLANAND WALL SCHEDULE

CONT. 8" BOND BEAMW/ (2) #5 BARS

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

ROOF DECK,SEE PLAN

CON'T L8"x8"x1/2" DECKCLOSURE ANGLE

ROOF DECK,SEE PLAN

CONC. BEAM,SEE PLAN

KNOCK-OUT BLOCK ATSILL REINF. W/ (2)-#5 CONT.(EXTEND 8" PAST EA. SIDEOF OPENING)

PRECAST LINTEL, SEE TYPDETAIL 4-033/S3.05

FILL ALL CELLS SOLID W/GROUT BELOW FIN FLR, TYP.

CONT WALL FOOTING, SEEPLAN FOR REINF

VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

STEEL SUPPORTCOLUMN, SEEPLAN

S3.044-012

L4x4x1/4" CONT. CLOSUREANGLE W/ 3/4"Ø EXP. BOLTSAT 24" O.C. 5" MIN. CONC.EMBED

3" M

IN.

3/163/16

TYP.

CJP

EMBED PL 8x16x3/4W/(6) 3/4" Ø 6" CONC.HEADED STUDS

HSS 6x4x1/4 (LSH)

CONT. L4x4x1/4

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

7 86

T/ BOND BEAM

T/ BOND BEAM

T/ BEAM

12' - 0"

4' - 0"

UMDVARIES

FILL ALL CELLS SOLID W/GROUT BELOW FIN FLR, TYP.VAPOR BARRIER

SLAB ON GRADE,SEE PLAN

8" ATLAS BRICK WALL,SEE PLAN AND WALLSCHEDULE FOR REINF.

CONT. 8" BOND BEAMW/ (2) #5 BARS

BOND BEAM W/ (2) #5 BARS ATTOP OF WALL, PROVIDEMATCHING CORNER BARS ATWALL INTERSECTIONS (TYP)

ROOF DECK,SEE PLAN

8" CONC. BEAM,TOP/BEAM EL.VARIES. SEE ARCH.DWGS FORCHAMFER

CONT WALL FOOTING, SEEPLAN FOR REINF

CONT. 8" BOND BEAMW/ (2) #5 BARS

CONT. 8" BOND BEAMW/ (2) #5 BARS

VAPOR BARRIER

CONT. EMBED PL 1/2"TH. x 6"W. W/ 1/2" DIA.x6" LONG HEADED STUDS @ 24" O.C.

S3.044-015

B/ CONC BEAM13' - 4"

ADDITIONAL BONDBEAM AT HSS BEAMCONNECTION

HSS BEAM,SEE PLAN

S3.065-005

3/16TYP.

9' - 6 5/8"

T/ BOND BEAM8' - 0'

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:33:01

PM

1442

S4.06WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

71

RBIDJM

SCALE: 3/4" = 1'-0"S4.06WALL SECTION 13S13

SCALE: 3/4" = 1'-0"S4.06WALL SECTION 14S14

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

12 13

CONT. WALL FOOTING,SEE PLAN

VAPOR BARRIER

4" CONC. SLAB ONGRADE, SEE PLAN

S3.065-203

8" PRECASTLINTEL W/ (2) #5

TYPE R1 TOPCHORD EXTENSION

U.M.D.10' - 8"

S3.044-017S3.04

4-012

8" CMU WALL, SEEPLAN FOR REINF.

CONT. 8" BONDBEAM W/ (2) #5TYP. EVERY 4 FT.

T/BOND BEAM4' - 0"

T/BOND BEAM8' - 0"

FOUNDATION-1' - 4"

SLAB ON GRADE0' - 0"

S3.065-203

CONT. L4x4x1/4CLOSUREANGLE, TYP.

MTL DECK,SEE PLAN

STEEL JOIST,SEE PLAN

CONT. DOUBLEBOND BEAM ATT/WALL W/ (2) #5

U.M.D.11' - 2"

RQP

S3.044-012S3.04

4-015

JOIST BRIDGING,SEE PLAN

8" CMU WALL, SEEPLAN FOR REINF.

CONT. 8" BONDBEAM W/ (2) #5TYP EVERY 4' - 0"

8X16 CONC.BEAM W/ (2) #5T&B & #3 TIES @8" O.C. TYP.

S3.065-202

STEEL JOIST,SEE PLAN

S3.065-202

CONT. WALL FOOTING,SEE PLAN

SLAB ON GRADE0' - 0"

FOUNDATION-1' - 4"

T/BOND BEAM4' - 0"

T/BOND BEAM8' - 0"

4" CONC. SLAB ONGRADE, SEE PLAN

VAPOR BARRIER

S3.044-012

S3.065-202CONT. L4x4x1/4

CLOSUREANGLE TYP. MTL DECK,

SEE PLAN

8X16 CONC. BEAMW/ (2) #5 T&B & #3TIES @8" O.C.TYP.

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:33:05

PM

1442

S4.07WALL SECTIONS

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

72

RBIDJM

SCALE: 3/4" = 1'-0"S4.07WALL SECTION 15S15

SCALE: 3/4" = 1'-0"S4.07WALL SECTION 16S16

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016

FOUNDATION FOUNDATION

-1' - 4" -1' - 4"

SLAB ONGRADE

SLAB ONGRADE

0' - 0" 0' - 0"

T/INTERIORWALLS

T/INTERIORWALLS

9' - 4" 9' - 4"

LOW ROOFFRAMING

LOW ROOFFRAMING

11' - 5" 11' - 5"

T/PARAPETWALL

T/PARAPETWALL

13' - 4" 13' - 4"

ROOFFRAMING

ROOFFRAMING

19' - 5" 19' - 5"

ColumnLocations A-11 B-2 B-4 B(-0' - 11 5/8")-4 B-5 B(-0' - 11 5/8")-5 B-7(0' - 4 3/8") B(-5' - 7

3/8")-8(-0' - 3") B-9 B-10 G-2G(-2' - 5

1/4")-7(3' - 67/8")

G(1' - 41/2")-9(-5' - 11")

G(1' - 41/2")-9(-8' - 9

3/4")G-10 L(0' - 5 7/8")-2 L-4 L(0' - 11 5/8")-4 L-5 L(0' - 11 5/8")-5 L-7 L-9 L-10

S5S3S2 S9 S10 S22S20S19 S25 S26S12 S16

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8.

HSS

8X8X

3/8

HSS

8X8X

3/8.

BP-1

S1

HSS

8X8X

3/8

BP-1

S4 S6 S21 S23

BP-1 BP-1 BP-1 BP-1

HSS

8X8X

3/8

HSS

8X8X

3/8

HSS

8X8X

3/8

HSS

8X8X

3/8

HSS

8X8X

3/8

S7 S24

HSS

8X8X

3/8.

HSS

8X8X

3/8.

S15S14S13S8

BP-2 BP-2 BP-2 BP-2

HSS

4X4X

5/16

HSS

4X4X

5/16

HSS

4X4X

5/16

HSS

4X4X

5/16

BP-1

3" C

LR.

SCH

EDU

LE

SEE

BEAM

SEE SCHEDULE

COLUMN ANDBASE PLATE

SEE

SCH

EDU

LE

CO

LUM

N A

ND

BASE

PLA

TE

AIR HOLE FORGROUT - SAME SIZEAS ANCHOR BOLTHOLE (U.N.O.)

COLUMN -SEE PLAN

PL WASHER 1/4"x4"x4"W/ STANDARD NUT -TACK WELD NUT ANDPLATE TO BOLT

FULL PEN.

GR

OU

T2"

NO

N-S

HR

INK

DISTANCE1 1/2" EDGE

3" C

LR.

SCH

EDU

LE

SEE

BEAM

SEE SCHEDULE

COLUMN ANDBASE PLATE

SEE

SCH

EDU

LE

CO

LUM

N A

ND

BASE

PLA

TE

AIR HOLE FORGROUT - SAME SIZEAS ANCHOR BOLTHOLE (U.N.O.)

COLUMN -SEE PLAN &SCHEDULE

PL WASHER 1/4"x4"x4"W/ STANDARD NUT -TACK WELD NUT ANDPLATE TO BOLT

FULL PEN.

GR

OU

T2"

NO

N-S

HR

INK

DISTANCE1 1/2" EDGE

THIS DRAWING AND ALL INFORMATION CONTAINED HEREIN IS THESOLE PROPERTY OF MASTER CONSULTING ENGINEERS, INC. ANDMAY NOT BE REPRODUCED, COPIED, ALTERED OR USED IN ANYWAY WITHOUT THE EXPRESS WRITTEN AUTHORIZATION FROMMASTER CONSULTING ENGINEERS, INC.

© COPYRIGHT 2016

5523 WEST CYPRESS ST., STE.200TAMPA, FLORIDA 33607-1735P | 813.287.3600 F | 813.287.3622

CA: 8426

No 33860

STATE OF

JAMES

R. MEHLTR ETTL I C E N S E

F L O R I D A

PR

OF

E S S I O NA L E NG

I NE

ER

E R

11111-

R E V I S I O N SDATE:DATE:DATE:

PAGESEL.

LOCATION:

BM No.FIELD BOOK No.CHECKED BY:DRAWN BY:DESIGNED BY: BY DATE

DRAWING No.

SCALE:

DATE:ENGINEERING & CAPITALIMPROVEMENTS DEPARTMENTCITY OF ST. PETERSBURG

ENGINEER OF RECORDNAME:P.E. No.:

THE ARCHITECT'S COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTSARE HEREBY RESERVED IN THE IDEAS, DESIGNS, PLANS, DRAWINGS, ANDSPECIFICATIONS PRODUCED BY THE ARCHITECT. THESE IDEAS, DESIGNS,PLANS, DRAWINGS, AND SPECIFICATIONS SHALL NOT BE REPRODUCED ORCONVEYED IN ANY MANNER NOR ASSIGNED TO ANY THIRD PARTY WITHOUTFIRST OBTAINING THE EXPRESS WRITTEN PERMISSION OF THE ARCHITECT.CONSENT IS HEREBY GRANTED TO GOVERNMENTAL AGENCIES TOREPRODUCE THE CONSTRUCTION DRAWINGS IN COMPLIANCE WITH STATESTATUTES. TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUMBUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS ASDETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTERS553 AND 633 OF THE FLORIDA STATUTES.

Project number

Wannemacher Jensen Architects, Inc.180 Mirror Lake Drive NorthSt. Petersburg, Florida 33701-3214(727) 822-5566 fax (727) 822-5475www.wjarc.com AA0002277 JAMES R. MEHLTRETTER

33860PROJ NO. 3104-086

AS NOTED

9/28/2

016 1

:33:11

PM

1442

S5.01SCHEDULES

875 64TH AVENUE NORTH, ST. PETERSBURG, FL 33702

FOSSIL PARK - FIRE STATION #707-29-2016 PERMIT07-29-2016

07-29-201607-29-2016

73

RBIDJM

SCALE: 1/4" = 1'-0"STEEL COLUMN SCHEDULE

SCALE: 1/2" = 1'-0"S5.01BASE PLATE - BP17

SCALE: 1/2" = 1'-0"S5.01BASE PLATE - BP28

BASE PLATE SCHEDULE

BASE PLATE SIZE ANCHOR BOLTS REMARKSBP-1 14x14x3/4 (4) F1554BP-2 10x10x3/4 (4) F1554

DESIGN DEVELOPMENT 01-26-201650% CDS 04-15-2016100% CDS REVIEW 06-10-2016PERMIT 07-29-2016