MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
D
A
1 2
CA
DD
D
3-R
5
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764
www.stanleyconsultants.com
01
23
AT FULL SIZE
IN
cm0 12
3 45
67
8
IOWA DEPARTMENT OF TRANSPORTATION
WAUKON MAINTENANCE FACILITY
IN-FLOOR HEATING SYSTEM UPGRADES
A
28332.05
MAY 30, 2018
PLUMBING/PIPING FITTINGS
NORMALLY
OPEN
NORMALLY
CLOSED
SOLENOID AUTOMATED VALVE
CONTROL VALVE ASSEMBLY
FOUR-WAY (WITH
TYP FAIL POSITION)
THREE-WAY (WITH
TYP FAIL POSITION)
PRESSURE REDUCING
WITH EXTERNAL TAP
(ARROW INDICATES FLOW
DIRECTION)
PRESSURE REDUCING,
SELF-CONTAINED
(ARROW INDICATES FLOW
DIRECTION)
BACK PRESSURE REGULATOR
SELF-CONTAINED
(ARROW INDICATES FLOW
DIRECTION)
POPPET OR TELESCOPING
BACK PRESSURE
REGULATOR EXTERNAL TAP
(ARROW INDICATES FLOW
DIRECTION)
PITCH DOWN IN
DIRECTION OF FLOW
TIE POINT TO EQUIPMENT OR ANOTHER CONTRACT
X = EQUIPMENT OR CONTRACT DESIGNATOR
YY = P&ID NUMBER
ZZZ = TIE POINT NUMBER
TIE POINT INTO AN EXISTING SYSTEM
YYY = P&ID DRAWING NUMBER
XX = TIE POINT NUMBER
VALVES
TIE POINT DESIGNATORS
GENERAL
BALL CHECK
AUTOMATIC RECIRCULATION
ANGLE SAFETY RELIEF
BACKFLOW PREVENTER
GAGE COCK
VACUUM RELIEF
BALANCING
FLAP GATE
PINCH
FLOAT
WAFER CHECK
VALVES
SWING CHECK
HOSE BIBB
W/ HYDRANT
PLUMBING LINE TYPES
TRAP (LAV, DRAIN, ECT.)
SHOCK ABSORBER OR
WATER HAMMER ARRESTOR
ALL FITTINGS AND VALVES MAYBE SHOWN AS INDICATED UNLESS
STATED (PLAN) ONLY.
SCHEMATIC/FITTINGS AND VALVES
VTR
GENERAL NOTES
XX
XYY
ZZZ
-TPYYY XX
F
F
F
*
V
*
ED
FD
HB
TAG
M
A
W
NEW WORK
EXISTING
FUTURE
STREAM IDENTIFICATION
FLOW ARROW
QUICK OPEN
UTILITY STATION
(LETTER, IF ANY, DESIGNATES TYPE)
FLOW STRAIGHTENING VANE
Y-STRAINER
Y-STRAINER W/ DRAIN
CAPPED Y-STRAINER W/ N.C.
BALL VALVE
SIMPLEX STRAINER
DUPLEX STRAINER
START-UP STRAINER
TEMPORARY STRAINER IN-LINE
DRAIN
SPRAY NOZZLE
VENT THRU ROOF (PLAN)
AIR VENT
STEAM VENT
(MANUAL VENT) MV
(AUTOMATIC VENT) AV
CONSERVATION VENT
FIRE HOSE VALVE
CENTRIFUGAL PUMP
INLINE PUMP
BUCKET STRAINER
SEAL WATER CONTROL UNIT
SLUICE GATE
GLOBE
BALL
STOP CHECK
PLUG
BUTTERFLY
DIAPHRAGM
NEEDLE
ANGLE GATE
KNIFE GATE
ANGLE GLOBE
V-BALL
SLIDE GATE
PARALLEL SLIDE GATE
GATE
BLIND FLANGE
WELDED CAP
THREADED CAP
PIPE PLUG
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ROOF DRAIN
EQUIP DRAIN
FLOOR DRAIN
FLOOR CLEANOUT
WALL CLEANOUT
EXPANSION JOINT
EXPANSION JOINT SINGLE
END
EXPANSION JOINT
DOUBLE END
FLEX CONNECTION
FLEX CONNECTOR W/SPARE
QUICK DISCONNECT
MT = MOISTURE TRAP
ST = STEAM TRAP
LF = LINE FILTER
METER
90° BEND PIPE TURN DOWN
90° BEND PIPE TURN UP
45° BEND
UNION
PIPE GUIDE
PIPE ANCHOR
VENT THRU
ROOF
HOT WATER
COLD WATER
DOMESTIC HOT
WATER CIRCULATING
1. ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS LEGEND
MAY NOT APPEAR ON THIS SET OF DRAWINGS.
F
F
F
F
CO
SYSTEM CODES
HWR
HWS
WTR
PG
HEATING WATER RETURN
HEATING WATER SUPPLY
WATER
PROPYLENE GLYCOL
MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL LEGEND SHEET
M1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
1. CUT-IN BOILER Y-STRAINERS AND VALVES. REMOVE Y-STRAINER SCREENS.
2. REMOVE EXISTING STRAINER SCREENS AT EACH IN-FLOOR HEATING MANIFOLD (EIGHT TOTAL).
3. REMOVE HEATING SYSTEM INLINE PUMPS (FIVE TOTAL). USE MATING FLANGES TO CONNECT
FLUSHING MACHINE OR WATER SUPPLY AND DRAIN HOSES.
4. CLOSE BOILER ISOLATION VALVES. VALVES SHALL REMAIN CLOSED FOR DURATION OF
IN-FLOOR MANIFOLD FLUSHING PROCESS TO PREVENT CONTAMINATION OF BOILER WATER
AND DAMAGE TO ALUMINUM HEAT EXCHANGER.
5. MAINTENANCE FACILITY SYSTEM FLUSH (MANIFOLDS 1 THROUGH 7):
A.APPROXIMATE VOLUME: 270 GALLONS.
B.ISOLATE ALL BUT ONE MANIFOLD AND FLUSH WITH CITY WATER. FLUSH WITH FLUSHING
MACHINE OR 1-1/2” HOSE FROM WASH BAY CONNECTION. MONITOR DRAIN AND CONTINUE
FLUSHING UNTIL DISCHARGE IS CLEAR. REPEAT PROCESS FOR OTHER MANIFOLDS.
C.ADD CLEANING SOLUTION AT RECOMMENDED CONCENTRATION USING FLUSHING MACHINE.
D.CIRCULATE THROUGH ALL SEVEN MANIFOLDS SIMULATANEOUSLY FOR EIGHT HOURS
MINIMUM.
E. ISOLATE ALL BUT ONE MANFOLD AND CIRCULATE CLEANER FOR ONE HOUR MINIMUM.
REPEAT PROCESS FOR OTHER MANIFOLDS.
F. REPEAT STEPS D AND E ABOVE.
G.FLUSH ALL SEVEN MANIFOLDS SIMULATANEOUSLY WITH CITY WATER USING FLUSHING
MACHINE OR 1-1/2” HOSE FROM WASH BAY CONNECTION. CONTINUE FLUSHING UNTIL
DISCHARGE IS CLEAR AND pH IS EQUAL TO CITY WATER.
H.CLOSE DRAIN VALVE AND TOP OFF SYSTEM WITH CITY WATER.
6. BRINE BUILDING SYSTEM FLUSH (MANIFOLD 8):
A.APPROXIMATE VOLUME: 22 GALLONS.
B.FLUSH WITH FLUSHING MACHINE OR 1” HOSE FROM WASH BAY CONNECTION. MONITOR
DRAIN AND CONTINUE FLUSHING UNTIL DISCHARGE IS CLEAR.
C.ADD CLEANING SOLUTION AT RECOMMENDED CONCENTRATION USING FLUSHING MACHINE.
D.CIRCULATE FOR TWENTY-FOUR HOURS.
E.FLUSH WITH CITY WATER USING FLUSHING MACHINE OR 1” HOSE FROM WASH BAY
CONNECTION. CONTINUE FLUSHING UNTIL DISCHARGE IS CLEAR AND pH IS EQUAL TO CITY
WATER.
F. CLOSE DRAIN VALVE AND TOP OFF SYSTEM WITH CITY WATER.
7. BOILER LOOP SYSTEM FLUSH:
A.APPROXIMATE VOLUME: 10 GALLONS.
B.PROVIDE TEMPORARY MANIFOLD TO CONNECT FLUSHING MACHINE DISCHARGE TO ALL
THREE BOILER INLETS. PROVIDE TEMPORARY MANIFOLD TO CONNECT FLUSHING MACHINE
RETURN TO ALL THREE BOILER INLINE PUMP SUCTION MATING FLANGES.
C.FLUSH EACH BOILER SEPARATELY WITH CITY WATER UNTIL DISCHARGE IS CLEAR USING
BOILER ISOLATION VALVES TO ISOLATE TWO OF THE THREE BOILERS.
D. ADD CLEANING SOLUTION AT RECOMMENDED CONCENTRATION USING FLUSHING MACHINE
AND CIRCULATE THROUGH ALL THREE BOILERS SIMULTANEOUSLY. CIRCULATE CLEANING
SOLUTION FOR FOUR HOURS OR LESS AS RECOMMENDED BY CLEANING SOLUTION
VENDOR FOR ALUMINUM HEAT EXCHANGERS.
E. IMMEDIATELY FLUSH ALL THREE BOILERS SIMULTANEOUSLY WITH CITY WATER USING
FLUSHING MACHINE. CONTINUE FLUSHING UNTIL DISCHARGE IS CLEAR AND pH IS EQUAL
TO CITY WATER.
F. DO NOT EXCEED 30 PSIG WATER PRESSURE AT BOILER. HEAT EXCHANGER MAY BE
DAMAGED BY PRESSURES EXCEEDING 30 PSIG.
8. PURGE WATER FROM ENTIRE SYSTEM USING COMPRESSED AIR REGULATED TO 30 PSIG
MAXIMUM. THE INTENT IS TO REMOVE AS MUCH RAW CITY WATER FROM THE SYSTEM AS
POSSIBLE TO MINIMIZE MINERAL CONTENT AND CONTAMINANTS. THE MAJORITY OF THE WATER
MUST BE REMOVED TO ACCOMMODATE THE MINIMUM VOLUME OF PURE GLYCOL TO BE ADDED
TO THE SYSTEM. THE CONTRACTOR MAY PERFORM A TEST FILL USING CITY WATER TO
CONFIRM (OPTIONAL). SEE STEP 12 BELOW.
9. REMOVE EXISTING CITY WATER MAKEUP CONNECTION AND INSTALL GLYCOL MAKEUP SYSTEM.
10. REINSTALL STRAINER SCREENS, BOILER INLINE PUMPS, AND BRINE BUILDING INLINE PUMP.
11. PRECHARGE EXPANSION TANK TO 8 PSIG.
12. CONNECT FLUSHING MACHINE TO INLINE PUMP DISCHARGE MATING FLANGE OF MAINTENANCE
FACILITY PIPING SYSTEM (MANIFOLDS 1 THROUGH 7). VENT AIR FROM THE AIR SEPARATOR OR
ANOTHER SUITABLE HIGH-POINT VENT. USE FLUSHING MACHINE TO ADD 125 GALLONS OF PURE
GLYCOL TO SYSTEM VIA MANIFOLDS 1 THROUGH 7. MONITOR OPEN VENT TO CONFIRM ONLY
AIR OR WATER DISCHARGES (NO GLYCOL).
13. FILL REMAINDER OF SYSTEM WITH DEIONIZED WATER, UP TO 175 GALLONS MAXIMUM. IF THE
SYSTEM IS STILL NOT FULL, TOP OFF WITH 40% GLYCOL SOLUTION. ESTIMATED TOTAL SYSTEM
VOLUME IS 300 GALLONS.
14. INSTALL REPLACEMENT MAINTENANCE FACILITY SYSTEM INLINE PUMP HWSP-1.
15. PROVIDE INITIAL FILL OF GLYCOL FOR GLYCOL MAKEUP SYSTEM TANK. USE 40% GLYCOL
SOLUTION.
16. OPERATE SYSTEM FOR ONE HOUR MINIMUM TO AID MIXING OF THE GLYCOL AND WATER. VENT
ANY REMAINING AIR FROM THE AIR SEPARATOR.
17. CONFIRM SYSTEM GLYCOL MIXTURE IS BETWEEN 30% AND 50%.
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
PROPOSED FLUSH AND FILL
PROCEDURE (NOTE 1):
D
A
1 2
CA
DD
D
3-R
5
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764
www.stanleyconsultants.com
01
23
AT FULL SIZE
IN
cm0 12
3 45
67
8
IOWA DEPARTMENT OF TRANSPORTATION
WAUKON MAINTENANCE FACILITY
IN-FLOOR HEATING SYSTEM UPGRADES
A
28332.05
MAY 30, 2018
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
EXST BOILER C
EXST BOILER A
EXST BOILER B
GLYCOL MAKEUP
SYSTEM
EXST AIR
COMPRESSOR
MECHANICAL
ROOM
PIPING PLAN
SCALE: 1/2"=1'-0"
1. CLEANING PROCEDURE MAY BE MODIFIED AS RECOMMENDED BY CLEANINGSOLUTION VENDOR. COORDINATE WITH OWNER.
2. PROVIDE 2-POLE, 1-PHASE, 15AMP BREAKERS IN PANEL "A" AT SPACES 25 AND 27.PROVIDE 2-#12 AND #12 GROUND IN 1/2" RGS TO PUMP HWSP-1.
GENERAL NOTES:
MECHANICAL ROOM PLAN
M2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
NO
RT
H
EXST PRESSURE
WASHER
PUMP
HWSP-1
ELECTRICAL
ROOM
MDB ATS
PANEL A (NOTE 2)
TI
MAINTENANCE
FACILITY
(MANIFOLDS 1-7)
MAINTENANCE
FACILITY
(MANIFOLDS 1-7)
FROM BRINE BUILDING
(MANIFOLD 8)
TO BRINE BUILDING
(MANIFOLD 8)
TI
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
REMOVE
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
LEGEND:
D
A
1 2
CA
DD
D
3-R
5
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764
www.stanleyconsultants.com
01
23
AT FULL SIZE
IN
cm0 12
3 45
67
8
IOWA DEPARTMENT OF TRANSPORTATION
WAUKON MAINTENANCE FACILITY
IN-FLOOR HEATING SYSTEM UPGRADES
A
28332.05
MAY 30, 2018
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
BOILER C BOILER A BOILER B
3/4" WTR
1 1/2" HWR
1 1/2" HWS
1 1/2" H
WR
1 1/2" H
WS
1 1/2" H
WR
1 1/2" H
WS
EXPANSION
TANK
AIR SEPARATOR
2" HWR
2" HWS
1" HWS
1" HWR
INLINE PUMP (TYP)
HEATING WATER
DEMO P&ID
P1
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
TI
MAINTENANCE
FACILITY
(MANIFOLDS 1-7)
MAINTENANCE
FACILITY
(MANIFOLDS 1-7)
FROM BRINE BUILDING
(MANIFOLD 8)
TO BRINE BUILDING
(MANIFOLD 8)
TI
DP
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
D
A
1 2
CA
DD
D
3-R
5
C
B
3 4 5
F
E
G
D
6 7 8 9
REV.
10 11
CHECKED
DESIGNED
APPROVED
APPROVED
DATE
DRAWN
SCALE:
NO.
A
DATENO. REVISIONS APVDCHKDDSGN
B
C
E
F
G
C STANLEY CONSULTANTS
225 Iowa Avenue, Muscatine, Iowa 52761-3764
www.stanleyconsultants.com
01
23
AT FULL SIZE
IN
cm0 12
3 45
67
8
IOWA DEPARTMENT OF TRANSPORTATION
WAUKON MAINTENANCE FACILITY
IN-FLOOR HEATING SYSTEM UPGRADES
A
28332.05
MAY 30, 2018
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
BOILER C BOILER A BOILER B
3/4" WTR
1 1/2" HWR
1 1/2" HWS
1 1/2" H
WR
1 1/2" H
WS
1 1/2" H
WR
1 1/2" H
WS
EXPANSION
TANK
AIR SEPARATOR
2" HWR
2" HWS
1" HWS
1" HWR
INLINE PUMP (TYP)
NOTE 2
3/4" PG
GLYCOL
MAKEUP
SYSTEM
NOTE 1
NOTE 1
NOTE 1
1. CONTRACTOR TO CONFIRM EXISTING PIPE SIZES.
2. PROVIDE GALVANIZED STEEL PIPE CAP AND NIPPLE.
GENERAL NOTES:
HEATING WATER
P&ID
P2
AS NOTED
TA SCHMITT
BK GROTHE
RJ LUKKARINEN
TA SCHMITT
PUMP
HWSP-1
DIFFERENTIAL
PRESSURE
TRANSMITTER
1/2"