GE Power Quality EP Series UPS. GE C&I PWQ AsiaSep., 20062 EP series family Tower Model Standard...

Post on 15-Jan-2016

234 views 0 download

Tags:

Transcript of GE Power Quality EP Series UPS. GE C&I PWQ AsiaSep., 20062 EP series family Tower Model Standard...

GE Power Quality

EP Series UPS

GE C&I PWQ AsiaSep., 2006 2

EP series family

Tower ModelStandard Model

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• With internal battery providing 5~7 mins back time

Long runtime model

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• Without internal battery

• With high capacity internal battery chargerRack Model

Standard Model (Only)

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• With internal battery providing 5~7 mins back time

• Battery is in additional cabinet for 2000/3000/6000VA

GE C&I PWQ AsiaSep., 2006 3

Feature

General

• Double conversion, on line (VFI)

• LED display – overload, on-line & battery status

• Full digital microprocessor controlled

• Programmable computer shutdown

• Lightning and transient surge protection

• Automatic bypass switch

• Battery Start (cold start)

Performance

• Input Power Factor: 0.97/0.98

• Wide input voltage window (115~300Vac/0.7~3K, 176~276Vac/6KVA)

• Frequency (50/60HZ), Voltage (220/230/240), auto sensing

Battery

• Programmable automatic test

• Protection against deep discharge

• Extended runtime available and auto-recognition

Communication

• RS232, USB

• SNMP

GE C&I PWQ AsiaSep., 2006 4

Cabinet view

700/1000VA

Front Panel

2000/3000VA

6000VA

700/1000VA (2U)

2000/3000VA (2U)

6000VA (3U)

GE C&I PWQ AsiaSep., 2006 5

Cabinet view Rear Panel (Tower)

GE C&I PWQ AsiaSep., 2006 6

Cabinet view Rear Panel (Tower)

GE C&I PWQ AsiaSep., 2006 7

Cabinet view Rear Panel (Rack)

GE C&I PWQ AsiaSep., 2006 8

EMI I/P

Rectifier

Booster

InverterEMI O/P

Charger

Push-Pull

Battery

Block Diagram

700/1000VA

2000/3000VA

6000VA

EMI I/P

Rectifier

PFC/Booster

Inverter EMI O/P

Battery Charger

Charger

SCR

GE C&I PWQ AsiaSep., 2006 9

Battery

Model EP 700 T/R EP 1000 T/R EP 2000 T/R EP 3000 T/R EP 6000 T/R

Num. & Model

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

Model 100% Load

50% Load

EP 700 T/R 5 mins 10 mins

EP 1000 T/R

5 mins 10 mins

EP 2000 T/R

5 mins 10 mins

EP 3000 T/R

5 mins 10 mins

EP 6000 T/R

7 mins 14 mins

Standard Model

Tower & Rack

Long Runtime Tower Model

Model EP 700 LRT EP 1000 LRT

EP 2000 LRT

EP 3000 LRT

EP 6000 LRT

Charging Current (max)

7A 8A 9.6A 9.6A 4.3A

GE C&I PWQ AsiaSep., 2006 10

Battery Connection of LRT Model (Anderson)

700/1000VA

2000/3000VA6000VA

GE C&I PWQ AsiaSep., 2006 11

Communication

Connection

• RS232, USB

• LAN (SNMP)

• Internet

GE C&I PWQ AsiaSep., 2006 12

Communication

GE C&I PWQ AsiaSep., 2006 13

Package

• Olympics• Product pictures• Key features• Back panel labeling

Listing all connectivity and electrical connections

• Internal CD packaging for software connectivity.

Box Labeling