Post on 02-Apr-2018
GE Full-Voltage Manual Starters
CR101H, CR101Y Manual Motor StartersSingle-Phase
1 Horsepower Maximum at 115 or 230 Volts% Horsepower Maximum at 277 Volts for 2-Pole Forms
25 to 60 Hertz
Single-Speed Open and NEMA Type 1 Forms
No. ofPoles
Catalog Number
Open®
For Flushor OutletBox Mtg.
List Price,GO-10G3®
NEMA Type 1
SurfaceMounting
List Price,GO-10G3®
Surface MountingWind. Light®
List Price,GO-10G3®
Toggle-Operated12
CR101Y®CR101H®
$33.0039.00
CR101Y1® $39.0C R 1 0 1 H 1 ® 45.0
I0 CR101Y110 C R 1 0 1 H 1 1
$57.0063.00
Key-Operated12
CR101YOOOKCR101HOOOK
45.0051.00
CR101Y100K 51.0CR101H100K 57.0
0 C R 1 0 1 Y 1 1 0 K0 C R 1 0 1 H 1 1 0 K
69.0075.00
Single-Speed NEMA Type 3/4/12 FormsNo. ofPoles Catalog Number List Price,
GO-10G3®
Lever-Operated — %-inch Hub on One End12
CR101Y400HCR101H400H
Lever-Operated — 3A-inch Hub on Both12
EndsCR101Y400JCR101H400J
$138.00144.00
150.00156.00
Factory Modification: Indicating light, Type 4 forms, add $210.00, GO-10G3 to list price.
Two-Speed Surface and Flush-Mounted NEMA Type 1 Forms
No. ofPoles
1122
IndicatingLights(230VMax.)
NoneTwo®None
Two®
Catalog Number
SurfaceMounting
CR101Y600BCR101Y610BCR101H600BCR101H610B
List Price,GO-10G3®
$172.00255.00187.00270.00
GrayFlush-Plate
CR101Y600ACR101Y610ACR101H600ACR101H610A
List Price,GO-10G3®
$165.00247.00180.00262.00
Stainless-SteelFlush-Plate
CR101Y608ACR101Y618ACR101H608ACR101H618A
List Price,GO-10G3®
$172.00255.00187.00270.00
Combination Device, NEMA Type 1 For Surface MountingNo. ofPoles
22
Catalog Number
CR101H12 (CR101H + Hand-Auto Switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C R 1 0 1 H 1 3 ( T w o C R 1 0 1 H ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List Price,GO-10G3®
$102.00108.00
© Open starters include an unmounted nameplate.® List prices do not include heater(s). Heaters can be selected from table at right and ordered as a separate item
at $6.00 each, GO-10H: One heater is required per starter (two for 2-speed forms and for combination starter,CR101H13).
® Includes a 115/230-Volt neon lamp(s). Not available at 277 Volts.® Units are individually boxed and "Poly-Packed" 10 per carton as standard.
Maximum Horsepower Ratings—AC or DCContinuous Carry—16 Amperes
StarterCatalog Number
CR101Y
CR101H
No. ofPoles
Single
Double
AC Voltage
32
1/4
1/4
1 1 5
1
1
230
1
1
277
-
Vt
DC Voltage
1 1 5
1
1
230
1/4
1
Prices and data subject to change without notice 1999 Issue
Overload Heater UnitsForCR101H,YAll CR123H heaters arepackaged as single units.
Catalog Number
CR123H(all)
List Price Each,GO-1 OH
$6.00
The table below gives a propersize heater to trip the switch onapproximately 125 percentmotor current.Listed values are for motorswith 1.15-1.25 service factor.For motors with 1.0 servicefactor continuously, multiplyfull-load current of motor by0.9 and use this value toselect heater. Contact nearestGE Industrial Systems—Electrical Distribution andControl Representative forrecommendation for heaters tobe used with definite-purposemotors. If motor full-loadAmperes falls between tworatings, select heater for thehighest of those two.For 1.35 service factor motors,multiply full-load current ofmotor by 1 .15 and use thisvalue to select heater(s).
Maximum MotorFull-Load Amperes
.48
.53
.58
.65
.71
.78
.86
.951.041 . 1 41.251.371.491.631.781.952.132.322.532.763.013.273.563.884.224.605.005.435.906.416.987.608.258.959.75
10.61 1 . 412.513.614.816.0
HeaterCatalog Number
CR123H055ACR123H061ACR123H067ACR123H074ACR123H082ACR123H090ACR123H099ACR123H108ACR123H120ACR123H132ACR123H144ACR123H158ACR123H172ACR123H188ACR123H205ACR123H224ACR123H245ACR123H267ACR123H291ACR123H317ACR123H346ACR123H377ACR123H410ACR123H446ACR123H486ACR123H529ACR123H575ACR123H625ACR123H680ACR123H739ACR123H802ACR123H873ACR123H950ACR123H103BCR123H112BCR123H122BCR123H132BCR123H144BCR123H157BCR123H171BCR123H186B
7-3
GE Full-Voltage Manual Starters
CH101H, CHW1Y Manual Motor StartersSingle-Phase1 Horsepower Maximum at 115 or 230 Volts3/4 Horsepower Maximum at 277 Volts for 2-Pole Forms25 to 60 Hertz
OpenStarter
Manual Starter inNEMA Type 1 General-
Purpose Enclosure
Manual Starter WithIndicating Light
HAND
CombinationGeneral-PurposeManual Starter
NEMA Type 4Water- and Dust-Tight
Manual Starter
Two-Speed Surface-MountedManual Starter
ApplicationDesigned for starting and stopping single-phase fractionalhorsepower motors. These manual starters have provision foroverload protection and their low cost provides economical starterselection for applications where no undervoltage protection isrequired. This line of starters may be used on such equipment asgrinders, conveyors, fans, mixers, and blowers.
Features• Terminal design—box terminals provide easy access for
wiring.• Molded plastic switch housing—protects starter mechanism.• Small size—open starter fits GEM or handy box.
Heater SelectionTables........ . page 7-3
Ordering DirectionsOrder starter by complete Catalog Number and specify overloadheater as a separate item by complete Catalog Number.
Examples:1. A general-purpose enclosed starter for surface wall mounting is
desired. The starter is to break both lines. Motor to be startedwith this device has a full-load current of 0.6 Ampere.
Order1 CR101H1 manual motor starter at $45.00 each, GO-10G3.1 CR123H074A heater at $6.00 each, GO-10G3.
2. The complete combination surface-mounted station,CR101H12, may also be ordered by components, e.g. order1—CR101X10 flush plate, at $71.00 each, GO-10G3; 1—CR101X14 box at $6.00 each, GO-10G3; and 1—CR101Hmanual starter at $39.00 each, GO-10G3. The othercomplete general-purpose manual starters may be brokendown in this manner.
7-2 1999 Issue Prices and data subject to change without notice
I