Flooded Water Cooled Screw ChillerFOCSWATER.C Series460-3400kW (130-970 Tons)
FOCSWATER.CWater cooled screw chiller
Multiple applicationsStandard chilled water applied for HVAC system;By adopting brine or glycol solution, the outlet temperature of evaporator can be in the range of -8~15℃, either for ice storage application or for industrial process purpose;Heat recovery function is optional.
Safety of electrical devicesInner structure of electrical cabinet, electrical components and circuit layout are designed according to EN60204-1/IEC204-1 standard. Controlling power is separated from main power by transformer so as to protect from impact and interfere of electrical current. The power section uses a bar-type distribution system and interlock-door mains isolator for safety and reliability. Each load of compressor is equipped with its own overload protector, fuse and contactor. Electric elements are with features of excellent insulation, dust-proof and humidity proof, and suitable for various inferior environments. Electrical system of the unit is in compliance with EMC code.
Gaseous refrigerant
Liquid refrigerant
1
UNIT FEATURERS
CompressorsSemi-hermetic screw compressors specifically designed for R134a & flooded evaporation application, featuring in high efficiency and energy saving.Precisely manufacturing technology and least moving component result in rel iable performance and simple maintenance.The compressor, w i th i t s own capac i t y regu la t i ng electromagnet ic valve and sl ide valve together wi th Climaveneta's micro-computer controlling system, can adjust load output automatically according to the requirement of processing, realize 10~100% stepless of precision variable adjustment and reduce power consumption.
Dedicated Flooded Evaporator/CondenserFlooded evaporator/condenser with integral rippled tube are modified to enhance the initiation of nucleate boiling sites and surface area, improving turbulent flow, resulting in increasingly overall heat transfer coefficient and high unit efficiency.The evaporator is characterized by low pressure drops on both the gas side and the water side. The level of refrigerant inside the flooded evaporator is guaranteed by dedicate sensor level and modulating electronic valve.Single circuit design even for multiple compressor improves unit part load efficiency.Chilled water inside tube make maintanence work convinient and simple.
Maximum ReliabilityDesign, manufacturing, testing comply with the several regulations such as AHRI, EN, UNI, JIS and Chinese standard GB/T18430.1.The built-in 3 stages oil separator and external efficient second separator ensure the constant presence of oil inside. Besides, unique device is designed by CLIMAVENETA dedicated to guaranty oil return.The unit has been charged with R134a and oil before shipped out from factory, and tested and inspected strictly according to UNI9218 standard. Only after water and electrical power being connected on site, the unit can be put into production for providing chilled water.
Optimized and Efficient PartsThe electronic valve is adopted to grant the ideal operation of the evaporator in all conditions. The complete flooding of tubes is granted with a sophisticated detection of the refrigerant level in the heat exchangers. The fast processing of the acquired data allow a quick, fluctuation-free regulation, and therefore a highly accurate adjustment to the swings of load and ambient conditions.Economizer has been adopted to improve unit efficiency.
FOCSWATER.CWater cooled screw chiller
● Friendly interfaceFully computer-controlled with no necessity of person duty;Objective user operational panel with multiple windows clearly displaying parameters of different categories;Graphical symbol inputting and displaying with convenient operation;Convenient adjusting and setting of data input through menu and fast key combination.● Control functions of the unitThe unit adopts W3000 intelligent microcomputer control system with setting, adjusting and controlling functions, such as: stepless regulation of cooling capacity; inlet/outlet chilled water temperature regulation; Starting, unloading and stopping functions of compressor; starting delay function of compressor; time limiting function of each hour start of the compressor; operation timing function of compressor; and running time balance function of compressor.
● Protecting and alarming functions of unitSelf-test when power on to avoid running with problem.Three lever password protection to prevent from mal-operation of persons without authorization.Overload, overheat and overvoltage protection and alarming of compressor; high discharge temperature protection and alarming of compressor.Water antifreeze protection, antifouling protection and alarming of evaporator;Protection and alarming of over high and low chilled water and cooling water temperature; protection and alarming of low water flow;Protection and alarming of low and high pressure of refrigeration system, and alarming of refrigerant leakage. ● Fault processing functionAutomatically functioning protection of acousto-optic alarming, load reducing of compressor, stopping of compressor and stopping of unit according to each fault grade. Automatically identifying fault and instructing fault category.Automatically recording fault with record capacity as much as 400 faults.Black box function which automatically record on-site state and all data of fatal fault for providing analyzing data.
Group Control DeviceA group composed of various hydronic units permits better management for the lowest running cost.Coordinating the units for optimized operating times assumes fundamental importance and provides significant advantages in terms of reliability (e.g. the compressors) while also permitting energy savings and delivering water flows constantly at the right temperature without fluctuation.Resources are a lways used according to the user 's requirements without needless compressor cycles or power absorption peaks. The unit pumps are intelligently managed.The number of hours of operation is balanced for more efficient maintenance. Resource priority assignment gives precedence to the unit with greater efficiency: such as chillers with free-cooling function. The stand-by mode grants response to possible peaks in load.The elevated characteristics offered by the serial interface keypad are the highest currently available in the market.
Convenient application and maintenanceFully computer controlling, menu displaying, self-checking of unit, running, load adjusting and safety protection are all completed by computer control system. Daily operation is only to switch on starter. Multiple refrigerating systems are available for standby equipment. The unit is available of functions such as fault protection, memorizing and alarming. All faults are clearly displayed. Each return circuit has inspection valve with "pump down" function which is convenient for repairing.
Sequencer Manager 3000
Latest Control System
2
FOCSWATER.CWater cooled screw chiller
3
FWS3000 Field Web ServerDevice for supervising Climaveneta units. Supervision
takes place via a direct link with the computer or via
LAN: hence this option can also be managed through
internet resources thanks to the built-in webserver and
the availability of suitably defined graphical pages.
Thus the resulting supervision does not entail installing
any additional software on the computer and, moreover,
employs the most common types of browser; this means
any networked computer can be used.
√ StandardOPT AvailableonrequestPar. Availablemodifyingavalueoftheconfigurationparameters
Microprocessor Microprocessor
Electronic control features
Remote on/off with external volt-free contact
Multi-language Menu
Phase sequence relay
Cumulative fault alarm
Alarms Code function
“BLACK BOX” function for alarm events
Self-test when power on
Real time programming of daily/weekly program
Evaporator inlet/outlet water temp. display
Compressor/unit failure display
General unit alarms display
Entering water temp. ratio control
Start/stop operation timer
Double-mode operation timer
“PUMP-DOWN” when stopped
W3000
√
√
√
√
√
√
√
Par.
√
√
√
√
Par.
Par.
√
W3000
OPT
√
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
OPT
√
√
Energy limit function
Manual control
ModBus communication protocol
BACNET communication protocol
LonWorks communication protocol
Pump control
Backup pump control
Water temp. set-point regulation from external signal(4-20mA)
Remote electric relay control
Local/remote monitor(FWS)
Remote double set-point regulation
Set-point regulation from external signal(0-10V)
Compressor run-timer, time balance & FIFO
Compressor start scheduling
FOCSWATER.CWater cooled screw chiller
4
Cooling capacity
Power input
Evaporator water flow
Evaporator water pressure drop
Condenser water flow
Condenser water pressure drop
Microprocessor
Number of compressors
Refrigerating circuit
Capacity regulating
Refrigerant charge
Oil charge
Unit Weight
Operating weight
Dimension
Length
Width
Height
1301C
459.9
82.5
79.2
48
93.1
55
1
1
97
35
2930
3080
2900
1180
1960
1651C
591.8
103.9
101.9
51
119.4
55
1
1
126
35
3090
3280
2900
1180
1960
2001C
691.2
121.0
119.0
50
139.4
56
1
1
143
35
3360
3580
2930
1190
2100
2501C
837.0
149.3
144.1
50
169.3
55
1
1
172
38
3690
3980
2990
1310
2200
3002C
1062.1
186.9
182.8
52
214.4
54
2
2
222
70
6020
6500
4430
1270
2210
3502C
1217.7
214.0
209.6
51
245.7
56
2
2
252
70
6490
7070
4470
1270
2250
4002C
1382.4
242.1
238.0
50
278.9
53
2
2
286
70
6660
7300
4470
1270
2280
4202C
1470.3
252.2
253.1
48
295.7
51
2
2
309
73
7050
7760
4565
1320
2380
4502C
1521.6
268.1
262.0
52
307.2
55
2
2
309
76
7110
7820
4650
1320
2380
5002C
1689.5
298.7
290.1
53
341.3
55
2
2
343
76
7230
8000
4680
1320
2380
6004C
2124.2
373.8
365.6
59
428.8
62
4
4
444
140
12440
13400
4825
2670
2210
7004C
2435.4
427.9
419.2
59
491.4
65
4
4
504
140
13220
14380
5200
2730
2250
8004C
2764.9
484.1
476.0
58
557.8
61
4
4
572
140
13560
14840
5200
2730
2280
8404C
2940.6
504.4
506.2
55
591.4
58
4
4
618
146
14600
16020
4960
2734
2380
9004C
3043.2
536.1
524.0
59
614.4
63
4
4
618
152
14720
16140
4960
2734
2380
10004C
3379.1
597.4
580.2
60
682.6
63
4
4
686
152
14960
16500
4960
2734
2380
FOCSWATER.C
KW
KW
m3/h
KPa
m3/h
KPa
n
n
kg
kg
kg
kg
mm
mm
mm
W3000
25-100% stepless 12.5-100% stepless 6-100% stepless
Remarks:Chilled water (in/out) 12/7℃Condenser water (in/out) 30/35℃Standard water side pressure of evaporator and condenser is 1.0MPa, 2.0MPa as optional.
General Technical Data
FOCSWATER.CWater cooled screw chiller
5
449.6
578.5
675.7
818.3
1038.3
1190.4
1351.5
1437.3
1487.5
1651.7
2076.6
2380.8
2703.0
2874.6
2975.0
3303.4
84.3
108.4
126.7
153.4
194.6
223.1
253.3
269.4
278.8
309.6
389.2
446.2
506.6
538.8
557.6
619.2
91.3
117.0
136.7
165.9
210.1
240.9
273.3
289.8
301.1
334.5
420.3
481.7
546.6
579.7
602.2
669.0
267.6
344.3
402.2
486.8
617.9
708.2
804.1
853.9
884.5
982.3
1235.8
1416.4
1608.2
1707.8
1769.0
1964.6
226.9
292.0
341.0
412.3
523.8
600.5
681.9
723.4
749.1
831.9
1047.6
1201.0
1363.8
1446.8
1498.2
1663.8
82.2
103.4
120.5
148.6
186.1
213.0
241.0
251.1
266.9
297.4
372.2
426.0
482.0
502.2
533.8
594.8
62.4
66.8
65.9
65.5
67.7
67.6
66.2
63.1
67.6
68.9
77.9
77.7
76.1
72.6
77.7
79.2
52.4
53.0
53.8
52.6
51.7
54.0
50.8
48.7
52.6
52.6
59.4
62.0
58.4
56.0
60.5
60.5
69.0
85.5
99.6
122.2
156.4
176.3
199.4
207.3
219.6
244.7
312.8
352.6
398.8
414.6
439.2
489.4
67.2
82.9
96.6
118.0
152.8
170.9
193.3
200.5
212.0
236.2
305.6
341.8
386.6
401.0
424.0
472.4
FOCSWATER1301C-ST
FOCSWATER1651C-ST
FOCSWATER2001C-ST
FOCSWATER2501C-ST
FOCSWATER3002C-ST
FOCSWATER3502C-ST
FOCSWATER4002C-ST
FOCSWATER4202C-ST
FOCSWATER4502C-ST
FOCSWATER5002C-ST
FOCSWATER6004C-ST
FOCSWATER7004C-ST
FOCSWATER8004C-ST
FOCSWATER8404C-ST
FOCSWATER9004C-ST
FOCSWATER10004C-ST
Normal cooling Evaporator Condenser Ice-storage(a) Ice-storage(b)
Chillers with Ice Storage System
Used the anti-freeze solutions such as Ethylene Glycol, propylene glycol Mixture as the chilled water, and scheduled the control system,
the Climaveneta chiller is uniquely suited to low temperature applications like ice storage and industry cooling process.
General Technical Data of Ice Storage System
Model Cooling capacity
Cooling capacity
Cooling capacity
Water flow
Water flow
Power input
Power input
Power input
Press.Drop
Press.Drop
KW KW KWKW KWKW KW KWKW KW
Data referred to 1. Normal cooling: chilled water (in/out) 12/7℃, condenser water (in/out) 30/35℃ (with 25% Glycol solution) 2. Ice storage: a. chilled water (in/out) -2.3/-5.3℃, condenser water (in/out) 27/31℃ (with 25% Glycol solution) b. chilled water (in/out) -5/-8℃, condenser water (in/out) 27/31℃ (with 30% Glycol solution)
FOCSWATER.CWater cooled screw chiller
6
Remarks: 1. Chilled water (in/out) 12/7℃, condenser water (in/out) 30/35℃, heat recovery water (in/out) 40/45℃ 2. FOCSWATER.C-R condenser water flow rate of condenser water flow is equal to FOCSWATER.C 3. Please consult CLIMAVENETA office for detail data
Chillers with Total Heat Recovery
While in the refrigeration unit to a lot of condensation heat as waste heat released into the atmosphere, Climaveneta with total heat
recovery technology, 100% recycling of waste heat from refrigeration, heating domestic hot water, low-cost or even free for the user save
a lot of hot water running costs. Heat recovery unit built-in independent circuits, independent heating hot water.
General Technical Data of Total Heat Recovery
Model FOCSWATER.C-R
Capability
Cooling capacity
Power input
Evaporator water flow
Evaporator water pressure drop
Condenser water flow
Condenser water pressure drop
Refrigeration+heat recovery capability
Cooling capacity
Power input
Heat recovery capacity
Heat recovery water flow
Heat recovery water pressure drop
Microprocessor
Number of compressors
Number of circuits
Capacity regulating
Refrigeration charge
Oil charge
Unit weight
Operating weight
Dimension
Length
Width
Height
KW
KW
m3/h
Kpa
m3/h
Kpa
KW
KW
KW
m3/h
Kpa
n
n
n
Kg
Kg
Kg
Kg
mm
mm
mm
1301
453.0
83.7
78.0
46.0
92.1
53.4
403.3
100.6
497.9
86.5
44.6
1
1
137
35
3550
3850
4500
1230
2070
1651
592.0
108.5
101.9
50.9
120.2
55.9
532.4
131.1
655.6
113.9
48.3
1
1
176
35
4000
4400
4530
1230
2120
1901
686.5
123.9
118.2
49.4
139.1
55.7
617.4
149.8
758.2
131.8
47.2
1
1
200
35
4250
4650
4530
1240
2200
2351
819.9
152.6
141.1
47.8
166.9
53.2
736.7
183.9
909.6
158.1
47.0
1
1
239
38
4750
5250
4530
1340
2300
3002
1050.0
190.8
180.8
50.3
212.9
53.0
941.7
227.4
1155.4
200.8
47.2
2
2
311
70
7250
7950
4600
1520
2320
3402
1184.0
216.9
203.8
48.6
240.4
53.7
1064.7
262.2
1311.2
227.9
48.3
2
2
352
70
8150
8950
4600
1550
2420
3902
1372.9
247.7
236.4
49.7
278.1
52.6
1234.7
299.4
1516.1
263.5
47.2
2
2
400
70
8400
9350
4600
1550
2420
4302
1499.7
284.1
258.2
50.0
306.0
54.3
1345.8
340.3
1665.7
289.5
48.6
2
2
433
76
9100
10200
4770
1770
2500
4702
1639.8
305.1
282.3
49.4
333.7
52.3
1457.2
379.7
1814.1
315.2
46.7
2
2
478
76
9350
10500
4770
1770
2500
W3000
25%-100% stepless 12.5%-100% stepless
FOCSWATER.CWater cooled screw chiller
7
F.L.I
(kW)
122
155
175
216
138
155
175
175/196
196
216
138
155
175
175/196
196
216
F.L.A
(A)
197
247
286
351
223
247
286
286/318
318
351
223
247
286
286/318
318
351
L.R.A
(A)
404
465
586
805
436
465
586
586/650
650
805
436
465
586
586/650
650
805
F.L.I
(kW)
122
155
175
216
275
310
350
371
391
432
552
620
700
742
784
864
F.L.A
(A)
197
247
286
351
446
494
572
604
636
702
892
988
1144
1208
1272
1404
S.A
(A)
404
465
586
805
659
712
872
936
968
1156
1105
1206
1444
1572
1604
1858
1301
1651
2001
2501
3002
3502
4002
4202
4502
5002
6004
7004
8004
8404
9004
10004
1
1
1
1
2
2
2
2
2
2
4
4
4
4
4
4
Total unitCompress(each)
Maximum values
FOCSWATER.C
n
F.L.I
(kW)
144.5
188.1
213
260
161.7
188.1
213
240
260
F.L.A
(A)
234
306
345
423
258
306
345
388
423
L.R.A
(A)
436
586
650
917
465
586
650
805
917
F.L.I
(kW)
144.5
188.1
213
260
323.4
376.2
426
480
520
F.L.A
(A)
234
306
345
423
516
612
690
776
846
S.A
(A)
436
586
650
917
723
892
995
1193
1340
1301
1651
1901
2351
3002
3402
3902
4302
4702
1
1
1
1
2
2
2
2
2
Total unitCompress(each)
Maximum values
FOCSWATER.C-R
n
Electrical Data
F.L.I. Power inputF.L.A. Current absorptionL.R.A. Locked rotor current for single compressorS.A Starting current
Electrical source: 380-3ph-50HzVoltage tolerance: 10%Maximum voltage unbalance: 3%Safety values to be considered when cabling the unit for power supply and line-protections
FOCSWATER.CWater cooled screw chiller
8
Dimension Drawing
Remark:1.①Evaporator water inlet ③Condensers water inlet ⑤Lift points ⑦Main islator ②Evaporator water outlet ④Condensers water outlet ⑥Power inlet 2.Shadows are the maintenance clearance and pipe connector area.( If pipe connector direction need to be exchange to the opposite side, please consult local CLIMAVENETA office.) 3. Please contact CLIMAVENETA office for detail drawings.
FOCSWATER1301C~2501C
1301
1651
2001
2501
A(mm)
2900
2900
2930
2990
B(mm)
1180
1180
1190
1310
H(mm)
1960
1960
2100
2200
P . / W . ( kg )
2930
3090
3360
3690
WeightDimensionFOCSWATER.C
Water Connection Size
①/②
4"
4"
5"
6"
③/④
4"
4"
5"
6"
5
1
2
3
4
7
6
A B
H
2500 1000
500
900
FOCSWATER.CWater cooled screw chiller
9
Dimension Drawing
FOCSWATER3002C~5002C
3002
3502
4002
4202
4502
5002
A(mm)
4430
4470
4470
4565
4650
4680
B(mm)
1270
1270
1270
1320
1320
1320
H(mm)
2210
2250
2280
2380
2380
2380
P . / W . ( kg )
6020
6490
6660
7050
7110
7230
FOCSWATER.C ①/②
6"
6"
6"
8"
8"
8"
③/④
6"
6"
6"
8"
8"
8"
4000 1000
500
900
A
H
B
5
1
2
3
4
6
7
WeightDimension Water Connection Size
Remark:1.①Evaporator water inlet ③Condensers water inlet ⑤Lift points ⑦Main islator ②Evaporator water outlet ④Condensers water outlet ⑥Power inlet 2. Shadows are the maintenance clearance and pipe connector area.( If pipe connector direction need to be exchange to the opposite side, please consult local CLIMAVENETA office.) 3. Please contact CLIMAVENETA office for detail drawings.
FOCSWATER.CWater cooled screw chiller
10
FOCSWATER6004C ~ 10004C
Model
FOCSWATER.C
6004
7004
8004
8404
9004
10004
A(mm)
4,825
5,200
5,200
4,960
4,960
4,960
B(mm)
2,670
2,730
2,730
2,734
2,734
2,734
H(mm)
2,210
2,250
2,280
2,380
2,380
2,380
P./W.(kg)
12,440
13,220
13,560
14,600
14,720
14,960
①/②
8"
10"
10"
10"
10"
10"
③/④
8"
10"
10"
10"
10"
10"
4000
900
1000
900
6
7
5
5
1
2
3
4
A
H
B
Dimension Drawing
WeightDimension Water Connection Size
Remark:1.①Evaporator water inlet ③Condensers water inlet ⑤Lift points ⑦Main islator ②Evaporator water outlet ④Condensers water outlet ⑥Power inlet 2.The unit need to be hoisted separately in twice. And the pipe connection should be processed after the suspending. 3.Shadows are the maintenance clearance and pipe connector area.( If pipe connector direction need to be exchange to the
opposite side, please consult local CLIMAVENETA office.) 4.Please contact CLIMAVENETA office for detail drawings.
FOCSWATER.CWater cooled screw chiller
11
FOCSWATER1301C ~ 2351C-R
1
3
4
2500 1000
500
900
B
H
7
6
52
9
8
A
FOCSWATER.C-R
1301
1651
1901
2351
A
4,500
4,530
4,530
4,530
B
1,230
1,230
1,240
1,340
H
2,070
2,120
2,200
2,300
P./W.(kg)
3,550
4,000
4,250
4,750
①/②
4"
4"
5"
6"
③/④
4"
5"
5"
6"
⑥/⑦
4"
5"
5"
6"
Dimension Drawing
Remark:1.①Evaporator water inlet ③Condensers water inlet ⑤Total heat recovery water inlet ⑦Lifting point ⑨Main isolator ②Evaporator water outlet ④Condensers water outlet ⑥Total heat recovery water outlet ⑧Power inlet 2.Shadows are the maintenance clearance and pipe connector area.( If pipe connector direction need to be exchange to the opposite side, please consult local CLIMAVENETA office.) 3.Please contact CLIMAVENETA office for detail drawings.
Dimension Water Connection SizeModel Weight
FOCSWATER.CWater cooled screw chiller
12
FOCSWATER3002C ~ 4702C-R
A
H
B
500
900
4000
1
2
3
45
6
9
8
1000
7
FOCSWATER.C-R
3002
3402
3902
4302
4702
A
4,600
4,600
4,600
4,770
4,770
B
1,520
1,550
1,550
1,770
1,770
H
2,320
2,420
2,420
2,500
2,500
P./W.(kg)
7,250
8,150
8,400
9,100
9,350
①/②
6"
6"
6"
8"
8"
③/④
4"
4"
5"
6"
6"
⑥/⑦
4"
4"
5"
6"
6"
Dimension Drawing
Dimension Water Connection SizeModel Weight
Remark:1.①Evaporator water inlet ③Condensers water inlet ⑤Total heat recovery water inlet ⑦Lifting point ⑨Main isolator ②Evaporator water outlet ④Condensers water outlet ⑥Total heat recovery water outlet ⑧Power inlet 2.Shadows are the maintenance clearance and pipe connector area.( If pipe connector direction need to be exchange to the opposite side, please consult local CLIMAVENETA office.) 3.Please contact CLIMAVENETA office for detail drawings.
FOCSWATER.CWater cooled screw chiller
Field Wiring Diagram
13
Climaveneta Italy:36061 BASSANO DEL GRAPPA (VICENZA) ITALIA - VIA SARSON 57/cTEL. +39 / 0424 509 500 (r.a.) - TELEFAX +39 / 0424 509 509E-mail:info@climaveneta.com http://www.climaveneta.com
Climaveneta China:No,88 Baiyun Road Xinghuo Developing Zone ,Shanghai,China Post Code:201419TEL: +86-21-57505566 FAX: +86-21-57505797E-mail:info@climaveneta.com.cn http://www.climaveneta.com.cn
Climaveneta Hongkong:Room 2003,CCT Telecom Building, 11 Wo Shing Street,Fotan,Shatin,N.T.,HongkongTEL: +852-26871755 FAX: +85-2-26873078E-mail:info@climaveneta.com.cn http://www.climaveneta.asia
Climaveneta Vietnam:381A1 Cong Hoa Street Ward 13 Tan Binh District, HCM City, VietnamTEL: +84-8-38497529 FAX: +84-8-38124190E-mail:info@climaveneta.com.cn http://www.climaveneta.asia
B215 CCU/01-01-2012EN-SHAllspecificationanddataaresubjecttochangewithoutnotice