©2016 Johnson Controls | The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

© 2016 AirFixture, LLC1

FlexSys Underfloor Air Terminal (Variable Volume)MIT3 - CRModel:

DeSCRIpTIon:MIT3-CR (Modular Integrated Terminal) is a variable volume air terminal for use in raised floor air systems. It features 20 gauge (1mm) galvanized steel construction, pre-painted flat black.

The air valve uses time modulation to vary total air delivered to a conditioned space. Air velocity is constant any time the valve is open; the short time duration between air pulses results in a sensation of continuous air delivered with consistent flow. The air valve is rated for 24V (18-30VAC) operation. One (1) PAP-1 Plug & Play Cable is included.

The nominal 10" (254mm) diameter cast aluminum grille includes two separate inserts, which can be configured to create alternate air throw patterns. Ten (10) standard colors are available; custom colors and finishes can be provided to match architectural design (specify on order).

FEATURES:• Robust cast aluminum grille frame• DC synchronized magnetic motor• Welded and riveted pre-painted galvanized steel• Multi-function circuit board for varying control strategies

SpeCIFICaTIonS: Application: Underfloor Cooling | Raised Access Floors 8" (203mm) +Grille Dimensions: Diffuser: 10"Ø (254mm) | Face: 11.3"Ø (287mm)Diameter (Nominal) Floor Tile Cut-Out: 10.25"Ø [+.125/-.00] (260mm [+3.175/-.00])Grille Rating: Cast Aluminum | Conforms to NFPA 90a | 1250 lbs. (567 Kg) Load Strength Supply Press. / Temp.: 0.02–0.1 in. H2O (5–25 Pa) | 40–120°F (4–49°C)Capacity (Nominal): 130 cfm @ 0.05 in. H2O (221 m3/hr @ 12.5 Pa)Noise Criterion: ≤ NC-17 (All Flow Conditions)

ALL DIMENSIONS NOMINAL +/- 0.1" (2.5mm)

Data SheetV160701

10.2ӯ259mm

12.5”318mm

14.3”363mm

8”203mm

16.2”411mm

5.5”140mm

11.3ӯ287mm

10ӯ254mm

80

100

120

140

160

180

200

0 0.02 0.04 0.06 0.08 0.1 0.12

Air

Flo

w (C

FM)

Sta�c Pressure (Inch W.G.)

©2016 Johnson Controls | The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

© 2016 AirFixture, LLC2

FlexSys Underfloor Air Terminal (Variable Volume)MIT3 - CRModel:

Data SheetV160701

FIGURE A

• Both Grille Inserts show the flair/angled opening facing UP

AIR FLOW = REDUCED

FIGURE B

• Left Side of the Grille Insert shows the flair/angled opening facing UP; Right Side of the Grille Insert shows the flair/angled opening facing DOWN

– OR –

• Both Grille Inserts show the flair/angled opening facing DOWN

With the Grille Inserts in either of these positions: AIR FLOW = INCREASED