Fisa Calcul SAMSON

Post on 15-Nov-2015

216 views 0 download

Transcript of Fisa Calcul SAMSON

  • Valve Sizing Version 7.06e

    Propsl./order no.: CustomerProject: Date: 30.03.2015 Data entered by: dell 2

    Item no. Tag no. Process medium Steam State of medium at inlet: vapor

    Process and medium data Case 1 Case 2 Case 3Flow Inlet pressure

    Inlet temperature

    W p1

    Outlet pressure p2t1

    [kg/h][bar(g)][bar(g)][C]

    1300126191,66

    600126191,66

    300126191,66

    Spec. volume Isentropic exponent Viscosity

    v1gammaeta

    [m/kg]

    [mPas]

    0,1511,290,0154

    0,1511,290,0154

    0,1511,290,0154

    Results and factors Valve coeff. calculatedMin. req. size Outlet velocity SPL VDMA 24422 mod.

    Kv

    LA

    Req. DNw

    [mm][Mach][dB(A)]

    8,43 3,84 1,91

    83 75 70

    29,60,164

    20,10,0756

    14,20,0378

    Safety factor Different. pressure ratio FL value xT value Valve style factor

    SFxFLxT

    1,900,460,930,74

    4,170,460,960,78

    8,390,460,970,79

    Fd 0,43 0,40 0,31Level exponent Slope exponent

    G1G2

    -3,40 -3,73 -3,841,50 1,50 1,50

    Valve data Body type Flanged regul. Actuator type PressureSeries Type 44-0BValve coefficient Kvs 16Nominal size DN [mm] 40Pressure ratings PN 16

    Body material EN-JL1040Noise reduction withoutOperation Direct

    Pipe data Type of pipe Steel pipe Pipe insulation none D1 [mm] 40 D2 [mm] 40cR 5100 rho 7800 di 43,1 s 2,6[m/s] [kg/m] [mm] [mm]