Post on 11-Feb-2017
clean agent fire suppression
www.firefluiDs.cominfo@firefluids.com
+1.720.583.3925
MISSION CRITICAL
AREAS
Medical Equipment/Facilities
Merchant Marine Vessels
Mix Rooms
Network Centers
Turbine Enclosures
Electric Utility Facilities
Engine Protection
IT Systems/Software
Gas Compressor Rooms
Manufacturing Facilities
Offshore Oil Rigs
Paint Rooms
Pleasure Craft
Pump Stations
Mass Transit Vehicles
Clean Rooms
Combat Vehicles
Computer Rooms
Data Storage Facilities
Libraries & Museums
Archives
Automobiles
Cable Spreading Rooms
Cellular Sites
Generators
INDUSTRIESSERVED
Power Generation
Oil and Gas
Petrochemical
Data Centers
Marine and Offshore
Mining
Manufacturing
Health Care
Telecommunication
Actuators OptionsMultiple actuators may be
required, depending on size and placement of system.
Pneumatic Actuator
Electrical Actuator
Manual Actuator
Integrated Pneumatic Manual Actuator
Check Valves
Discharge Pressure Switch
NozzlesSidewall + Central
MISSION CRITICAL FIRE PROTECTION MANUFACTURER AND SUPPLIERFFT has become a leader in innovation for special hazard fire protection in industries from power generation to oil and gas to marine applications. FFT opened its doors in 2003 for the research and development of liquid clean agent fire protection systems to replace Halon and HFC systems. In 2009, FFT was the first company to develop an IMO (International Maritime Organization) approved system at 35 bar. With a global technical support team and unparalleled service, FFT is mastering complex projects throughout the world.
ADDITIONAL hARDwARE(as requireD)
Monitoring and Centralized systems available for use with FFT-1230 System.
FFT-1230 SYSTEMThe FFT-1230 Clean Agent Fire Protection System is a total flooding system utilizing 3M™ Novec 1230™ Fire Protection Fluid. This unique system uses cylinder valve assemblies with 25bar (360psi) up to 42bar (610psi) storage pressure. Nozzles designed with a hazard coverage area of up to 500m3 per nozzle.
ADVANTAGES OF FFT-1230 SYSTEMS· Welded Cylinder sizes up to 345L capacity· High Flow rate valves· Longer pipe runs· Remote Cylinder Location· Multiple hazard protection zones
The FFT-1230 system has been designed and tested according to International Standards and maintains International approvals, according to NFPA2001, ISO, and IMO.
FFT-1230 TEChNOLOGYWe use 3M™ Novec™ 1230 Fire protection fluid because it’s safe for humans and the environment. Liquid at room temp allows for simple onsite refilling.
3M Blue Sky Warranty: 20year protection against regulatory bans or restrictions on the use of 3M™ Novec™ 1230 Fire Protection Fluid
www.firefluiDs.com | info@firefluiDs.com
Liquid Level Indicator
Selector Valve
ISO 9001
Cylinder Valve Assembly Shown with Integrated Pressure Gauge & Low Pressure Switch
STANDARD hARDwARE
© 2013 Fire Fluids Technologies. All rights reserved.
i3 Series Detector
Control Panel
P2R Horn/Strobe
DETECTION + CONTROLConventional agent release and control panels offer immediate activation and notification of system discharge.
Release & Abort Station
3M™ Novec™ 1230 Fire Protection Fluid NOVEC 1230 Halon 1301 HFC-125 HFC-227ea
ENVIRONMENTAL PROPERTIES
Ozone Depletion Potential1 0.0 12.0 0.0 0.0
Global Warming Potential2 1 7140 3500 3220
Atmospheric Lifetime (Years) 0.014 (5 Days) 65 34.2 29
SNAP (Yes/No) Yes N/A Yes Yes
SAFETY MARGINS
Use Concentration 4-6% 5% 8.7-12.1% 7-8.7%
NOAEL3 10%4 5% 7.5% 9%
Safety Margin 71-138% Nil Nil 3-20%1 Word Meteorological Organization (WMO) 1998, Model-Derived Method
3 NOAEL for Cardiac Sensitization2 Intergovernmental Panel on Climate Change (IPCC) 2007 Method, 100-year ITH
4 NOAEL for acute toxicity, including cardiac sensitization
Bell
International Approvals
TESTING STANDARD APPROVAL AGENCY
UL2166 UL, ULC, FM
ISO12094 CE
IMO 848/1267 DNV, ABS, BV, LR, USCG