ELECTRICAL ABBREVIATIONSAAFAFFAFGAFIAICALARCHASAWGBLDGBKBDCCABCATC/BCKTCLGCOCOMMCONNCUDEMODISCDNDWGEAELECELEVEMER, EMEMTEOLREQUIPEX, EXISTFBOFCUFFFIXTFLEXFLUORFTGFIGNDHPHVACIGIMCINISCJB, J-BOXKCMILKVAKW
AMPEREAMP FUSEABOVE FINISHED FLOORABOVE FINISHED GRADEARC-FAULT CIRCUIT-INTERRUPTERAMPERE INTERRUPTING CAPACITYALUMINUMARCHITECT(URAL)AMP SWITCHAMERICAN WIRE GAUGEBUILDINGBACKBOARDCONDUITCABINETCATALOG/CATEGORYCIRCUIT BREAKERCIRCUITCEILINGCONDUIT ONLYCOMMUNICATIONCONNECTIONCOPPERDEMOLITION/DEMOLISHDISCONNECTDOWNDRAWINGEACHELECTRICALELEVATOREMERGENCYELECTRICAL METALLIC TUBINGEND OF LINE RESISTOREQUIPMENTEXISTINGFURNISHED BY OTHERSFAN COIL UNITFINISHED FLOORFIXTUREFLEXIBLE METALLIC CONDUIT (STEEL)FLUORESCENTFEET OR FOOTGROUND FAULT INTERRUPTERGROUNDHORSEPOWERHEATING, VENTILATING & AIR CONDITIONINGISOLATED GROUNDINTERMEDIATE METAL CONDUITINCH(ES)SHORT CIRCUIT AMPERES, KAJUNCTION BOXTHOUSAND CIRCULAR MILSKILOVOLT AMPEREKILOWATT
LTGMAXMCBMECHMFRMINMLOMTDNECNECANEMANEUTNFCNCNICNLNONTSOCPPPHPNLPWRQTYRECEPREQ'DRGSCRMSCHEDSECTSPSNSPECSWSWBDSWGRSYSTEMPTELEXFMRT-STATTWPTWSPTYPUBCULUMCUNOVVAWW/WGWP
LIGHTINGMAXIMUMMAIN CIRCUIT BREAKERMECHANICALMANUFACTURERMINIMUMMAIN LUGS ONLYMOUNTEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATIONNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEUTRALNATIONAL FIRE CODENORMALLY CLOSEDNOT IN CONTRACTNIGHT LITENORMALLY OPENNOT TO SCALEOVERCURRENT PROTECTIONPOLEPHASEPANELPOWERQUANTITYRECEPTACLEREQUIREDRIGID GALVANIZED STEEL CONDUITROOMSCHEDULESECTIONSINGLE POLESOLID NEUTRALSPECIFICATIONSWITCHSWITCHBOARDSWITCH GEARSYSTEMTEMPORARYTELEPHONETRANSFORMERTHERMOSTATTWISTED PAIRTWISTED SHEILDED PAIRTYPICALUNIFORM BUILDING CODEUNDERWRITERS LABORATORYUNIFORM MECHANICAL CODEUNLESS NOTED OTHERWISEVOLT OR VOLTAGEVOLT AMPEREWATTWITHWIRE GUARDUL LISTED WEATHERPROOF, NEMA 3R or 4
S
P
3
4
X
3ØUP
3ØUS
UT
UTV
SITE ELECTRICAL
"x" POLE SWITCH - ARC FAULT INTERRUPTER
WALL MOUNT FIXTURE
THREE WAY SWITCH
FOUR WAY SWITCH
WALL MOUNT OCCUPANCY SENSOR: ADAPTIVE TECHNOLOGY
OCCUPANCY SENSOR
PHOTOCELL
QUANTITY OF CONDUCTORS: SHORT LINES = PHASE /SWITCH,LONG LINES = NEUTRAL
HOME-RUN
DISTRIBUTION PANEL
PANELBOARD
3-PHASE UNDERGROUND PRIMARY POWER
3-PHASE UNDERGROUND SECONDARY POWER
UNDERGROUND TELEPHONE
UNDERGROUND TV
POINT OF DISCONNECTION
POINT OF CONNECTION
OT OVERHEAD TELEPHONE
1ØOP 1-PHASE OVERHEAD PRIMARY POWER
DIMMER SWITCH: INCANDESCENT; 1000 W MINIMUM
F DIMMER SWITCH: FLUORESCENT; 100 W MINIMUM
P PILOT LIGHT SWITCH
POLE LIGHT; ONE HEAD
POLE LIGHT; TWO HEAD
DECORATIVE POLE LIGHT
TIME CLOCK
POWER AND DISTRIBUTION
LIGHTING FIXTURES
LIGHTING CONTROL
BRANCH CIRCUITING
ELECTRICAL LEGEND
SINGLE POLE SWITCH; "x" INDICATES SWITCH GROUP
X
OTV OVERHEAD TV
METER / METER SOCKET
S OCCUPANCY SENSOR: DUAL TECHNOLOGY
S OCCUPANCY SENSOR: PASSIVE INFRARED
S OCCUPANCY SENSOR: ULTRASONIC
DT
PR
US
1ØUP
1ØUS
1-PHASE UNDERGROUND PRIMARY POWER
1-PHASE UNDERGROUND SECONDARY POWER
UTILITY POLE
PUSH BUTTON
L DIMMER SWITCH: LED; 600 W MINIMUM
S OCCUPANCY SENSOR: # INDICATES WATTSTOPPER CAT# FORCOVERAGE PATTERN OR EQUIVALENT AS SPECIFIED
#
DETAIL CALL-OUT; TOP "X" REFERS TO DETAIL NUMBER & BOTTOM"XXX" REFERS TO SHEET NUMBER
ANNOTATIONS
XXXX
3ØOP
3ØOS
3-PHASE OVERHEAD PRIMARY POWER
3-PHASE OVERHEAD SECONDARY POWER
(E)3ØOP 3-PHASE OVERHEAD PRIMARY POWER : EXISTING
3-PHASE UNDERGROUND PRIMARY POWER : EXISTING(E)3ØUP
(E)UT UNDERGROUND TELEPHONE : EXISTING
DL SWITCH: DAYLIGHT ZONE AS DETAILED
2P SWITCH: SINGLE-THROW; DOUBLE-POLE
LSX/SYDIGITAL LIGHTING CONTROL SWITCH; SX = SWITCH CONTROLTYPE #1; SY = SWITCH CONTROL TYPE #2; ETC.
P PHOTOCELL: INTEGRATED TO LIGHTING CONTROL SYSTEM;P# = LIGHTING CONTROL TYPEP#
S OCCUPANCY SENSOR: LIGHTING CONTROL SYSTEM; O# =LIGHTING CONTROL TYPELO#
S OCCUPANCY SENSOR: HIGH BAYHB
3-PHASE UNDERGROUND PRIMARY POWER: DEMO
3-PHASE UNDERGROUND SECONDARY POWER: DEMO
(D)3ØUP
(D)3ØUS
3-PHASE UNDERGROUND SECONDARY POWER : EXISTING(E)3ØUS
(D)UT UNDERGROUND TELEPHONE : DEMO
(D)UTV UNDERGROUND TV : DEMO
(E)UTV UNDERGROUND TV : EXISTING
P PHOTOCELL: DAYLIGHT RESPONSIVE FOR CONTINUOUS DIMMINGAPPLICATIONS.DR
1ØUF 1-PHASE UNDERGROUND FEEDER
DIMMER SWITCH WITH WALL MOUNT OCCUPANCY SENSOR: ADAPTIVETECHNOLOGY
# KEYED NOTE CALLOUT
EQUIPMENT CALLOUT
K SWITCH: KEYED
PRODUCTION EQUIPMENT CALLOUT
#-#
#-#
WALL MOUNT OCCUPANCY SENSOR: VACANCY SENSOR FUNCTION
S OCCUPANCY SENSOR: VACANCY SENSOR FUNCTIONVS
WALL MOUNT OCCUPANCY SENSOR: OCCUPANCY SENSORFUNCTION
S OCCUPANCY SENSOR: OCCUPANCY SENSOR FUNCTIONOS
VS
OS
1ØOS 1-PHASE OVERHEAD SECONDARY POWER
3ØOT 3-PHASE OVERHEAD TRANSMISSION LINES
GENERAL PROJECT NOTES1. ALL ELECTRICAL INSTALLATIONS TO CONFORM TO THE LATEST NEC AND LOCAL CODES.
2. ELECTRICAL CONTRACTOR'S PROJECT MANAGER AND ON-SITE PROJECT FOREMAN SHALL REVIEWVENDOR SUBMITTALS FOR ACCURACY PRIOR TO SUBMITTING TO ENGINEER. INACCURACIES SHALL BECORRECTED PRIOR TO ENGINEER SUBMITTAL.
3. SUBMITTALS FOR EACH SYSTEM WILL BE REVIEWED BY ENGINEER UP TO TWO TIMES--ONE FULLSUBMITTAL FOR OVERALL COMPLIANCE AND ONE RESUBMITTAL. ADDITIONAL REVIEWS WILL BECHARGED TO CONTRACTOR AT ENGINEER'S STANDARD BILLING RATE.
4. SUBMITTALS TO ENGINEER SHALL INCLUDE ALL SPECIFIED SYSTEMS IN FIRST SUBMITTAL. PARTIALSUBMITTALS WILL BE RETURNED TO CONTRACTOR AS INCOMPLETE AND WILL BE CONSIDERED ONE OFTWO INCLUDED SUBMITTAL REVIEWS.
5. THE CLARITY OF RECORD DRAWING CHANGES MADE BY THE CONTRACTOR SHALL BE EQUAL TO THEORIGINAL DRAWINGS AS JUDGED BY THE ARCHITECT OR THE RECORD SET WILL BE RETURNED TO THECONTRACTOR FOR CLARIFICATION.
6. WHEN THE GENERAL CONTRACT CALLS FOR “RECORD” OR “AS-BUILT” DRAWINGS TO BE FURNISHED BYTHE CONTRACTOR AT JOB COMPLETION, THE ELECTRICAL CONTRACTOR SHALL BE REQUIRED TOFURNISH A COMPLETE SET OF “BLUE-PRINT READY” AUTOCAD ELECTRICAL DRAWINGS FOR ALLCONTRACTOR GENERATED CHANGES FROM THE DRAWINGS OF A CLARITY EQUAL TO THE ORIGINALDRAWINGS AS JUDGED BY THE ENGINEER. CONTACT ARCHITECT FOR DISKS OR REPRODUCIBLEORIGINAL MEDIA. PROVIDE DRAWINGS ON CD IN AUTOCAD FORMAT.
7. DO NOT SCALE ELECTRICAL FLOOR OR SITE PLANS. SEE ARCHITECTURAL DRAWINGS FOR ACCURATEBUILDING DIMENSIONS AND FIELD VERIFY ALL EXTERIOR DIMENSIONS.
8. ELECTRICAL DEVICES CANNOT BE SHOWN TO SCALE AND SOMETIMES OVERLAP BUILDING AND SITEELEMENTS. REFER TO ARCHITECTURAL ELEVATIONS FOR ACCURATE MOUNTING LOCATIONS
9. EMT IS NOT ALLOWED OUT OF DOORS.
10. DO NOT INSTALL IN-GRADE JUCTION BOXES UNLESS SPECIFICALLY SHOWN ON DRAWINGS.CONDUCTORS SHALL BE RUN CONTINOUS WITHOUT SPLICING FROM SOURCE OR DEVICE TO NEXTDEVICE.
11. CIRCUIT WIRE SIZES MUST MATCH BRANCH CIRCUIT BREAKERS PER NEC. VERIFY WITH PANELSCHEDULES BEFORE PULLING WIRE.
12. HOME RUNS MUST BE RUN EXACTLY AS SHOWN ON PLANS UNLESS OTHERWISE NOTED. DO NOTCOMBINE HOME RUNS INTO ONE CONDUIT THAT ARE NOT SHOWN COMBINED ON THE DRAWINGS.
13. THE ELECTRICAL CONTRACTOR SHALL RUN BRANCH CIRCUIT CONDUITS IN ATTIC SPACES IN A NEAT ANDWORKMANLIKE MANNER SO AS TO CONSERVE OPEN SPACES AS MUCH AS POSSIBLE. HVAC DUCTWORKAND PLUMBING SHALL HAVE LOCATION PRIORITY OVER BRANCH CIRCUIT CONDUIT RUNS.
14. CIRCUIT WIRING SHALL BE INSTALLED AS SHOWN ON THE DRAWINGS. ANY DEVIATIONS SHALL BEINITIATED BY A CHANGE ORDER FROM THE ARCHITECT. OTHERWISE THE RECORD SET SHALL MATCHTHE CONSTRUCTION SET.
15. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR, PULLED INTO THE CONDUIT WITH THE PHASECONDUCTOR, IN ALL SERVICE, FEEDER, AND BRANCH CIRCUITS.
16. PROVIDE A NEUTRAL CONDUCTOR FOR EACH BREAKER TRIP HANDLE. NEUTRALS SHALL NOT BE SHAREDBETWEEN BRANCH CIRCUITS.
17. ALL SITE LIGHTING CIRCUITS TO BE MINIMUM #12 CU IN MINIMUM 3/4” CONDUIT UNLESS OTHERWISENOTED.
18. MC CABLE IS NOT AN APPROVED ALTERNATE TO CONDUCTORS IN CONDUIT.
19. DO NOT INSTALL MORE THAN THREE PHASE CONDUCTORS IN ANY HOME-RUN CONDUITS UNLESSSPECIFICALLY INDICATED ON DRAWINGS.
20. INCLUDE AS PART OF THE JOB THE INSTALLATION OF AN EXTRA 200 FT OF 3/4” EMT WITH 4 #10 WIRESINSTALLED AND TWO J-BOX TERMINATIONS.
21. REMOVE ALL OLD AND/OR UNUSED EXISTING CONDUIT AND ELECTRICAL APPARATUS FROM EXTERIOR ORINTERIOR EXPOSED SURFACES.
22. WHERE EXISTING ELECTRICAL EQUIPMENT IS TO REMAIN BUT THE SURFACE THAT IT IS MOUNTED ON ISTO BE REWORKED UNDER OTHER CONTRACTS, THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLETO REMOVE AND INSTALL OR MODIFY THE EXISTING EQUIPMENT AS REQUIRED TO MEET THE DESIGNINTENT. SEE ARCHITECTURAL DRAWINGS FOR ROOF, CEILINGS, WALLS, SOFFITS, FLOORS, ETC.
23. REMOVE ALL UNUSED CONDUITS AND CIRCUITS IN THE DEMOLTIONED AREA AS THEY ARE IDENTIFIED ASUNUSED OR ABANDONED.
24. REMOVE ALL EXISTING ELECTRICAL DEVICES, EQUIPMENT, AND APPARATUS AS THEY ARE IDENTIFIED ASUNUSED OR ABANDONED.
25. RELOCATE EXISTING CONDUITS AND CIRCUITS AS REQUIRED THAT ARE PRESENTLY SERVINGEQUIPMENT THAT IS INTENDED TO REMAIN IN SERVICE BUT SAID CONDUITS ARE CURRENTLY RUNNINGTHROUGH AREAS TO BE DEMOLITIONED.
26. WHERE EXISTING CONDUIT RUNS ARE RE-USED BY SPECIAL PERMISSION FROM THE ARCHITECT, ASEPARATE GREEN, INSULATED GROUND WIRE SHALL BE PULLED IN THE CONDUIT AND BONDED AT EACHEND AS REQUIRED.
27. ALL PATCH, REPAIR, REPAINT AND COVER UP REQUIRED AS A RESULT OF ELECTRICAL REMODEL IS TO BETHE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, BUT ACTUAL WORK IS TO BE PERFORMED BYQUALIFIED PERSONNEL.
28. FIELD VERIFY CONDITIONS FOR NEW WIRING. SURFACE RACEWAYS MUST RECEIVE PRIOR APPROVALFROM THE ARCHITECT BEFORE BID AND MUST BE PAINTED TO MATCH THE SURFACE ON WHICH THEYARE MOUNTED.
29. PROVIDE NEUTRAL CONNECTION TO 208/240/480V, SINGLE-PHASE EQUIPMENT. RUN SEPARATE GROUNDWIRE TO ALL OUTDOOR UNITS AND BOND TO THE EQUIPMENT GROUND LUG.
30. REVIEW THE STATE DESIGN REQUIREMENTS MANUAL PRIOR TO BID.
31. REVIEW THE USU A&E DESIGN MANUAL PRIOR TO BID.
32. WHERE THERE ARE CONFLICTS IN THE DRAWINGS AND/OR SPECIFICATIONS THE CONTRACTOR SHALLNOTIFY THE ARCHITECT/ENGINEER PRIOR TO BID. WHERE NO NOTIFICATION IS GIVEN THE MORESTRINGENT INTERPRETATION (GENERALLY INTERPRETED TO BE THE MORE COSTLY) WILL BE ENFORCED.
3 6 0 w e s t a s p e n a v e n u es a l t l a k e c i t y , u t a h 8 4 1 0 18 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # : 18.0405
d a t e : April 18, 2019
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE ANDDATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND ISNOT INTENDED FOR CONSTRUCTION, RECORDINGPURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDINGALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &MODELS THEREOF, ARE PROPRIETARY & CAN NOT BECOPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED INWHOLE OR IN PART WITHOUT THE SOLE AND EXPRESSWRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
USU EASTERNCAPITALIMPROVEMENTSSITE LIGHTING
4/18/2019
CONSTRUCTIONDOCUMENTS
LAS
T S
AV
ED
: 18
Apr
19
LAS
T S
AV
E 4
/18/
2019
T:\J
OB
S\2
0180
82 U
SU
EA
STE
RN
MIS
CE
LLA
NE
OU
S\0
1 D
RA
WIN
GS
\05
ELE
CTR
ICA
L\S
INE
SO
UR
CE
PR
OJE
CT\
SH
EE
TS\E
E00
1 A
BB
RE
VIA
TIO
NS
, G.P
.N.,
LEG
EN
D &
SH
EE
T IN
DE
X.D
WG
EE001
ABBREVIATIONS,G.P.N., LEGEND& SHEET INDEX
SHEET INDEX# Sheet Title
EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEXES101 ELECTRICAL SITE PLANES102 ELECTRICAL SITE PLANES501 ELECTRICAL SITE DETAILSES601 LIGHTING SCHEDULE & ELEVATION
BID SET
BLE
AC
HE
RS
WM
400 NORTH STREET
500 E
AST
STRE
ET
600 NORTH STREET
300 E
AST
STRE
ET
BDAC
COLLEGE CENTER
WORKFORCESERVICES
FACILITIESMAINTENANCE
ARMORY
ATHLETIC FIELD WITHTRACK
DORMITORY
CAREERCENTER
PARKING
PURCHASE &RECEIVING
SUBSTATION
SERVICEYARD
SERVICEYARD CAREER
CENTERSTORAGE
G.J. REEVESBUILDING
TRANSTRANS
SESSIONSHALL
elec
elec
elecvoltage
Storm Drain
B BB B
B
switchhigh
STEAM HEAT TUNNEL
LP
unde
rgrou
nd po
wer
GEARYTHEATER
LIBRARY
LDS CHURCH
LP
B B B B
B
B
B
B
B
B
B
HEATPLANT
402
403
405
407
408
409
410
411
413
414415
416
417
420 421 422
B
B
B
BLEA
CHER
S
"TP""TL"
GEARY THEATER
ART BUILDING
MH
MH
MH
BBB
B
BB
BB
30'
30'
30'
30'
3' BASE
3' BASE
3' BASE
30'
F
FF F
F
F
FFF
F
FF
F
F
F
F
B1
FFF
F
F
F
F
F F F
F
F
B1B1
F
F
B1
B
A
B
A
BABA
B
A
B
A
A
B
15'
EX. PNL
SWTICH
RAB
RAB
GB RAB RAB RAB
RAB
GB
GB
P4-L7K(B1)1
P5-L7K(B1)1
4
P5-L7K(B1)1
4
P5-L7K(B1)1
4
P5-L
7K(B
1)1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
P5-L
7K(B
1)
1
F
4
1
P5-L7K(B1F)
1
P5-L7K(B1F)
41
P4-L7K(B1F)
4 1
P4-L7K(B1F)
4 1
P4-L7K(B1F)
4 1
P5-L7K(B1F)
4
2
P5-L7K(B1)1
P5-L7K(B1)3
6 7
9
P3-L7K
14
P5-L7K
14
4 4
1P3-L7S
41
P3-L7S
41
P3-L7S
41
P3-L7S
41
P3-L7S
41
P3-L9K
4
14
P5-L9L
14
P5-L9L
14
P5-L9L
14
P4-L7K
14
P3-L7K
14
P3-L7K
14
P3-L7K
14
P2-L7K
1. REPLACE EXISTING POLE WITH NEW OF TYPE INDICATED.
2. REMOVE EXISTING POLE AND CONCRETE BASE.
3. PROVIDE NEW POLE AND CONCRETE BASE.
4. PROVIDE ADAPTER PLATE FOR NEW POLE MOUNTING ON EXISTING BOLT PATTERN. SEEDETAIL B/ES501.
5. PROVIDE 12"x18" FLUSH-MOUNTED PULL-BOX, WITH LIGHTING LOGO COVER, IN LOCATIONOF REMOVED POLE AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY.
6. CONNECT TO EXISTING LIGHTING CONTROL INDICATED.
7. CONNECT TO EXISTING CIRCUIT INDICATED.
8. EXTEND CIRCUIT SERVING REMOVED POLE TO NEW LOCATION INDICATED. RE-PULLCONDUCTORS COMPLETE FROM NEAREST POLE ON CIRCUIT.
9. TUNNEL UNDER OR REMOVE AND REPLACE SECTIONS OF EXISTING CONCRETE FOR NEWCIRCUIT INSTALLATION. SEE GENERAL NOTE #8 BELOW FOR CONCRETE REPLACEMENTREQUIREMENTS.
10. PATH OF WATER LINE UPGRADE. COORDINATE EXISTING POLE REMOVAL WITH WORKBEING DONE UNDER SEPARATE CONTRACT.
11. REMOVE AND REINSTALL POLE AND BASE TO ALLOW FOR CHILLED WATER UPGRADESUNDER SEPARATE PROJECT.
12. REMOVE POLES TO PREVENT DAMAGE BY EXCAVATION EQUIPMENT FOR CHILLED WATERUPGRADES UNDER SEPARATE PROJECT. PROTECT CIRCUITS AND BASES AS REQUIRED.RE-INSTALL POLES UPON PROJECT COMPLETION.
13. REPLACE EXISTING WALL MOUNT FIXTURE WITH NEW IN SAME LOCATION.
14. PROVIDE LINE ITEM PRICING FOR WORK ASSOCIATED WITH CHILLED WATER UPGRADEPRICING.
15. REPAIR ASPHALT AND CONCRETE SURFACES WHERE POLE BASE WAS REMOVED FROMHARDSCAPE.
16. PROVIDE LINE ITEM PRICING FOR EACH AREA INDICATED AREAS ARE NUMBERED INORDER OF PRIORITY.
SHEET KEYED NOTES
1. DEMOLITION PLAN IS ENGINEER'S ATTEMPT TO ASSIST BIDDERS IN ESTIMATING REMOVALCOSTS OF EXISTING EQUIPMENT. PLAN IS NOT INTENDED TO BE ALL-INCLUSIVE, AND IT ISTHE BIDDERS RESPONSIBILITY TO VERIFY ALL EXISTING EQUIPMENT AND DEVICES TO BEREMOVED PRIOR TO BIDDING.
2. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMS TO REMAINARE SHOWN AS LIGHT/SOLID.
3. MAINTAIN CIRCUIT CONTINUITY FOR DEVICES DOWNSTREAM OF ITEMS TO BE REMOVED.
4. CIRCUIT ROUTING IS SCHEMATIC UNLESS OTHERWISE NOTED.
5. NEW WALKWAY POLE BASES TO BE INSTALLED PER DETAIL A/ES501 UNLESS OTHERWISEINDICATED.
6. SITE LIGHTING CIRCUITS TO BE MINIMUM #6 CU IN 1" MINIMUM CONDUIT UNLESSOTHERWISE INDICATED.
7. CONTRACTOR MAY OPT TO REPLACE SECTIONS OF CONCRETE INSTEAD OF TUNNELINGUNDER EXISTING CONCRETE WHERE NOTED.
8. REMOVE, AND REPLACE WITH NEW, ENTIRE SECTIONS OF CONCRETE SURFACESCOMPLETE TO COLD JOINTS FOR NEW ELECTRICAL INSTALLATIONS. ONLY REMOVESECTIONS WHERE REQUIRED TO INSTALL NEW CIRCUITING.
9. CUT, PATCH AND REPAIR EXISTING SURFACES AS NEEDED FOR NEW CIRCUITINSTALLATIONS. INCLUDE ALL LANDSCAPING AND FLATWORK RESTORATION COSTS ASNEEDED TO REPAIR SURFACES DAMAGED BY CONSTRUCTION.
10. PROTECT EXISTING TREE ROOTS ALONG CIRCUIT PATHS. HAND DIG AS REQUIRED.
11. CONTRACTOR SHALL VERIFY THE VOLTAGE AT ALL FIXTURE LOCATIONS PRIOR TOORDERING FIXTURES. EXISTING VOLTAGES ARE BELIEVED TO BE 208V, 1ɸ, 3W.
12. LEGALLY DISPOSE OF REMOVED FIXTURES & POLES UNLESS OTHERWISE DIRECTED BYOWNER.
13. EXISTING POLE BASE BOLT CIRCLES ARE A MIX OF APPROXIMATELY 8" DIAMETER, 4-BOLTIN CIRCULAR PATTERN AND 8", 3-BOLT IN TRIANGULAR PATTERN. ADAPTER PLATES HAVEBEEN NOTED TO BE PROVIDED FOR ALL 3-BOLT BASES. PROVIDE ADAPTER PLATES FORALL 4-BOLT BASES TO REMAIN OR ARRANGE WITH FIXTURE MANUFACTURER FOR NEWPOLE BOLT PATTERNS TO MATCH EXISTING BOLTS. INCLUDE A MINIMUM OF 20% OF QUADBOLT POLES TO BE USED AT OWNER/ENGINEER DISCRETION TO RE-CENTER POLES.
14. NOTIFY ENGINEER OF ANY POLE BASES LESS THAN 16" DIAMETER SHOWN TO REMAIN.
15. RESTORE ALL IRRIGATION SYSTEM COMPONENTS DAMAGED BY CONSTRUCTION.
16. CONTRACTOR SHALL COORDINATE POLE OPTICAL ORIENTATION WITH ENGINEER PRIORTO POLE BASE INSTALLATION FOR ALL P2, P3 AND/OR P4 SERIES POLES.
17. PROVIDE GRASS/HARDSCAPE TRANSITIONS PER DETAILS D/ES501 AND E/ES501 WHENPOLES ARE LOCATED ADJACENT TO HARDSCAPE.
18. BACKFILL HOLES OF ALL REMOVED POLE BASES WITH COMPACTED STRUCTURAL FILL TOWITHIN 6" OF GRADE. FILL FROM STRUCTURAL BACKFILL TO GRADE WITH HARDSCAPE ORLANDSCAPE MATCHING ADJACENT AREAS.
GENERAL SHEET NOTES
2P4-L1L3
222
P4-L1L3
P4-L1L3
P4-L1L3
1P5-L9K
4
1P5-L9K
4
1P5-L9K
4
1P5-L9K
4
P3-L7K(H)31
4
P4-L7K
P4-L7K(H)
14
P3-L7K
14
P3-L7K(H) P4-L7K(H)
14
14
P5-L9L
14
P5-L9L
14
P4-L7K
14
P4-L7K
14
P4-L7K
25
14
P3-L7K
3P4-L7K
25
1P4-L7K
4
1P3-L7K
4
25
25
2 2P4-L12
33
3P5-L7K
3P5-L7K 3 P5-L7K
3P3-L7K
2P4-L12
3
2
P4-L1232
3 P2-L7KP2-L7K1
4
P4-L7K1
4
P2-L7K(H)2 3
P2-L3K(H)1
4
P4-L9K1
4
P2-L3K(H)1
4
P4-L9K(H)1
4
P2-L3K(H)1
4
P4-L9K(H)1
4
P4-L9K(H)1
4
P2-L3K(H)1
4
P2-L3K(H)1
4
P3-L7K
14
P3-L7K(H)
3
P3-L7K(H)
322
P3-L7K
14
P3-L7K
32
8 8 8 8
14
14
14
P4-L7K
P4-L7K
P5-L7K
P4-L12
67
9
9
5
67
8
14
P4-L
9K
P4-L7K(H)
P4-L7K(H)
14
215
215
24
67
14
P4-L9L
2
10
AB
12
12
AB
1114
1214
1214
1214
1114
3P4-L12
6
13
13
ES6011
PANEL "A"
PANEL "K"
PANEL "C"PANEL "D"PANEL "F"
PANEL "Q"PANEL "G"
PANEL "H"
PANEL "J"PANEL "S"
PANEL "B"
OW3-L10
OW3-L10
14
5
5
7
116
216
516
616
9
8
3164
16
CHILLED WATERPROJECT
Scale: 1"=50'-0"1
N
W E
ELECTRICAL SITE PLAN
3 6 0 w e s t a s p e n a v e n u es a l t l a k e c i t y , u t a h 8 4 1 0 18 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # : 18.0405
d a t e : April 18, 2019
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE ANDDATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND ISNOT INTENDED FOR CONSTRUCTION, RECORDINGPURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDINGALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &MODELS THEREOF, ARE PROPRIETARY & CAN NOT BECOPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED INWHOLE OR IN PART WITHOUT THE SOLE AND EXPRESSWRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
USU EASTERNCAPITALIMPROVEMENTSSITE LIGHTING
6/28/2019
CONSTRUCTIONDOCUMENTS
LAS
T S
AV
ED
: 28
Jun
19LA
ST
SA
VE
6/2
8/20
19 T
:\JO
BS
\201
8082
US
U E
AS
TER
N M
ISC
ELL
AN
EO
US
\01
DR
AW
ING
S\0
5 E
LEC
TRIC
AL\
SIN
E S
OU
RC
E P
RO
JEC
T\S
HE
ETS
\ES
101
ELE
CTR
ICA
L S
ITE
PLA
N.D
WG
BID ADDENDUM 06/28/20191
ES101
ELECTRICALSITE PLAN
1
1
400 NORTH STREET
500 NORTH STREET
600 NORTH STREET
300 E
AST
STRE
ET
200 E
AST
STRE
ET
PARKING
NURSING HOME
TUCKERHALL
PRICE CITY SWIMMINGPOOL
COMPUTER BUSINESS
PARKING
TENNIS COURTS
PURREC
S
BURTENSHAWHALL
412
418419
MH
MH
15'20'15'
20'
BROKEN GLASS
WP
WP
1. REPLACE EXISTING POLE WITH NEW OF TYPE INDICATED.
2. REMOVE EXISTING POLE AND CONCRETE BASE.
3. PROVIDE NEW POLE AND CONCRETE BASE.
4. PROVIDE ADAPTER PLATE FOR NEW POLE MOUNTING ON EXISTING BOLT PATTERN. SEEDETAIL B/ES501.
5. PROVIDE 12"x18" FLUSH-MOUNTED PULL-BOX WITH LIGHTING LOGO COVER IN LOCATIONOF REMOVED POLE FOR LOCATIONS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY.
6. CONNECT TO EXISTING LIGHTING CONTROL INDICATED.
7. CONNECT TO EXISTING CIRCUIT INDICATED.
8. EXTEND CIRCUIT SERVING REMOVED POLE TO NEW LOCATION INDICATED. RE-PULLCONDUCTORS COMPLETE FROM NEAREST POLE ON CIRCUIT.
9. TUNNEL UNDER OR REMOVE AND REPLACE SECTIONS OF EXISTING CONCRETE ORASPHALT FOR NEW CIRCUIT INSTALLATION. SEE GENERAL NOTE #9 BELOW FORCONCRETE REPLACEMENT REQUIREMENTS.
10. REPLACE EXISTING WALL MOUNT FIXTURE WITH NEW IN SAME LOCATION.
11. PROVIDE LINE ITEM PRICING FOR EACH AREA INDICATED AREAS ARE NUMBERED INORDER OF PRIORITY.
SHEET KEYED NOTES
1. DEMOLITION PLAN IS ENGINEER'S ATTEMPT TO ASSIST BIDDERS IN ESTIMATING REMOVALCOSTS OF EXISTING EQUIPMENT. PLAN IS NOT INTENDED TO BE ALL-INCLUSIVE, AND IT ISTHE BIDDERS RESPONSIBILITY TO VERIFY ALL EXISTING EQUIPMENT AND DEVICES TO BEREMOVED PRIOR TO BIDDING.
2. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMS TO REMAINARE SHOWN AS LIGHT/SOLID.
3. MAINTAIN CIRCUIT CONTINUITY FOR DEVICES DOWNSTREAM OF ITEMS TO BE REMOVED.
4. CIRCUIT ROUTING IS SCHEMATIC UNLESS OTHERWISE NOTED.
5. NEW WALKWAY POLE BASES TO BE INSTALLED PER DETAIL A/ES501 UNLESS OTHERWISEINDICATED.
6. SITE LIGHTING CIRCUITS TO BE MINIMUM #6 CU IN 1" MINIMUM CONDUIT UNLESSOTHERWISE INDICATED.
7. CONTRACTOR MAY OPT TO REPLACE SECTIONS OF CONCRETE INSTEAD OF TUNNELINGUNDER EXISTING CONCRETE WHERE NOTED.
8. REMOVE, AND REPLACE WITH NEW, ENTIRE SECTIONS OF CONCRETE SURFACESCOMPLETE TO COLD JOINTS FOR NEW ELECTRICAL INSTALLATIONS. ONLY REMOVESECTIONS WHERE REQUIRED TO INSTALL NEW CIRCUITING.
9. CUT, PATCH AND REPAIR EXISTING SURFACES AS NEEDED FOR NEW CIRCUITINSTALLATIONS. INCLUDE ALL LANDSCAPING AND FLATWORK RESTORATION COSTS ASNEEDED TO REPAIR SURFACES DAMAGED BY CONSTRUCTION.
10. PROTECT EXISTING TREE ROOTS ALONG CIRCUIT PATHS. HAND DIG AS REQUIRED.
11. CONTRACTOR SHALL VERIFY THE VOLTAGE AT ALL FIXTURE LOCATIONS PRIOR TOORDERING FIXTURES. EXISTING VOLTAGES ARE BELIEVED TO BE 208V, 1ɸ, 3W.
12. LEGALLY DISPOSE OF REMOVED FIXTURES & POLES UNLESS OTHERWISE DIRECTED BYOWNER.
13. EXISTING POLE BASE BOLT CIRCLES ARE A MIX OF APPROXIMATELY 8" DIAMETER, 4-BOLTIN CIRCULAR PATTERN AND 8", 3-BOLT IN TRIANGULAR PATTERN. ADAPTER PLATES HAVEBEEN NOTED TO BE PROVIDED FOR ALL 3-BOLT BASES. PROVIDE ADAPTER PLATES FORALL 4-BOLT BASES TO REMAIN OR ARRANGE WITH FIXTURE MANUFACTURER FOR NEWPOLE BOLT PATTERNS TO MATCH EXISTING BOLTS. INCLUDE A MINIMUM OF 20% OF QUADBOLT POLES TO BE USED AT OWNER/ENGINEER DISCRETION TO RE-CENTER POLES.
14. NOTIFY ENGINEER OF ANY POLE BASES LESS THAN 16" DIAMETER SHOWN TO REMAIN.
15. RESTORE ALL IRRIGATION SYSTEM COMPONENTS DAMAGED BY CONSTRUCTION.
16. CONTRACTOR SHALL COORDINATE POLE OPTICAL ORIENTATION WITH ENGINEER PRIORTO POLE BASE INSTALLATION FOR ALL P2, P3 AND/OR P4 SERIES POLES.
17. PROVIDE GRASS/HARDSCAPE TRANSITIONS PER DETAILS D/ES501 AND E/ES501 WHENPOLES ARE LOCATED ADJACENT TO HARDSCAPE.
18. BACKFILL HOLES OF ALL REMOVED POLE BASES WITH COMPACTED STRUCTURAL FILL TOWITHIN 6" OF GRADE. FILL FROM STRUCTURAL BACKFILL TO GRADE WITH HARDSCAPE ORLANDSCAPE MATCHING ADJACENT AREAS.
GENERAL SHEET NOTES
2P5-L9K
33
P5-L9K2 2
P3-L9K
33P5-L9K
9
67 8
2,OW3-L6K10
22,OW3-L6K10
OW2-L6K10
OW2-L6K10
2,OW4-L6K10
2,OW4-L6K10
OW4-L6K10
OW4-L6K10
2
1P3-L7K
4
1P3-L7K
4
1P3-L7K
4
1P3-L7K
41
P4-L7K
4
1P5-L7K
4
1P4-L7K
4
1P5-L7K
4
1P5-L7K
4
2P5-L12
3
1P5-L12
4
2P5-L12
32
P5-L12
32P5-L12
3
2P5-L12
3 3P5-L12
9
67
1P3-L7K
4
1P3-L7K
4
1P3-L7K
4
1P3-L7K
4
4,OW4-L6K10
3,OW4-L6K10
OW3-L6K10
2,OW4-L6K10
1P4-L7K
4
1P4-L7K
41
P3-L7K
4
3P3-L7K
2
9
85
12,P5-L7K
4
5
711
Scale: 1"=50'-0"1
N
W E
ELECTRICAL SITE PLAN
3 6 0 w e s t a s p e n a v e n u es a l t l a k e c i t y , u t a h 8 4 1 0 18 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # : 18.0405
d a t e : April 18, 2019
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE ANDDATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND ISNOT INTENDED FOR CONSTRUCTION, RECORDINGPURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDINGALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &MODELS THEREOF, ARE PROPRIETARY & CAN NOT BECOPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED INWHOLE OR IN PART WITHOUT THE SOLE AND EXPRESSWRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
USU EASTERNCAPITALIMPROVEMENTSSITE LIGHTING
6/28/2019
CONSTRUCTIONDOCUMENTS
LAS
T S
AV
ED
: 27
Jun
19LA
ST
SA
VE
6/2
7/20
19 T
:\JO
BS
\201
8082
US
U E
AS
TER
N M
ISC
ELL
AN
EO
US
\01
DR
AW
ING
S\0
5 E
LEC
TRIC
AL\
SIN
E S
OU
RC
E P
RO
JEC
T\S
HE
ETS
\ES
102
ELE
CTR
ICA
L S
ITE
PLA
N.D
WG
BID ADDENDUM 06/28/20191
ES102
ELECTRICALSITE PLAN
1
1
1/2"(MINIMUM)x24" ANCHOR BOLTS2" BEND
1/2" ROUND ALL EDGES
CONCRETE BASE 3000 PSI. BASEINSTALLED BY PROFESSIONAL
CONCRETE TRADE UNDERELECTRICAL CONTRACT.
4 - #5 REBARWITH #2 TIES
2'-7" MIN.3'-0" MIN
4" BOLT PROJECTION
FRONTSIDE
SEE SITEPLAN FORWIRE SIZE
CONTINUOUS #8 CU
1" PVC MINIMUM1" GRC (MINIMUM)
A
24"
5" RAISE 5" MOW STRIP
GROUT UNDER BASE
(MIN
)
DECORATIVE BASE COVER
FIXTURE HEAD
5" DIAMETER 12' ALUMINUM POLE.
12'-0"
FLAG HOLDER(WHERE NOTED - "F" ACCESSORY)
REBAR CONNECTION
FINISH GRADE6" NATIVE SOIL(MIN)WITH LANDSCAPE TO MATCH EXISTING
SIDEWALK SIDEWALK
STEEL PLATE
NEW POLE PLATE(FACTORY WELDED TO POLE)
EXISTING CONCRETEPOLE BASE
EXISTINGPOLE BOLTS
(TYPICAL OF 4)
NEW POLE BOLTS(TYPICAL OF 4)
DETAIL NOTES1. CUT EXISTING BOLTS TO ALLOW NEW POLE PLATE TO SIT TIGHT TO NEW LEVELING NUTS.
2. PROVIDE SECURING NUTS TO FASTEN PLATE TO EXISTING POLE BASE.
3. PROVIDE 1/2" GALVANIZED STEEL ADAPTER PLATE. NEW PLATE SHALL BE FULLYCONCEALED BY BASE COVER.
4. CUT ROUNDED END OF NEW POLE BOLTS OR PROVIDE STRAIGHT BOLTS OF EQUIVALENTDIAMETER. DRILL AND EPOXY NEW BOLTS INTO EXISTING BASE.
5. PROVIDE NUTS TO SECURE NEW BOLTS TO ADAPTER PLATE (TYPICAL OF 4 LOCATIONS).
6. PROVIDE DOUBLE NUT ON NEW BOLTS BETWEEN ADAPTER PLATE AND NEW POLE PLATE.TOP NUT SHALL BE USED AS LEVELING NUT (TYPICAL OF 4 LOCATIONS).
7. PROVIDE UPPER NUTS ON NEW BOLTS PER MANUFACTURER RECOMMENDATIONS TOSECURE NEW POLE IN PLACE.
NEW POLE
4
1
3
DIMENSIONS:A = 48" FOR POLES 15'-0" OR LESSA = 72" FOR POLES TALLER THAN 15'-0"
(2)BREAK-AWAY, CLAMP-ONBANNER ARMS
(WHERE NOTED -"B1 ACCESSORY)
FLAG
GENERAL NOTES1. NEW ADAPTER PLATE SHALL BE CUT TO FIT BENEATH NEW POLE BASE COVER.
2. NOTIFY ENGINEER OF ANY POLE BASES LESS THAN 16" DIAMETER SHOWN TO REMAIN.
3. GROUT UNDER BASES AS SHOWN IN POLE BASE DETAILS.
4. ALLOW ADAPTER PLATE ADJUSTMENTS SO NEW POLES CENTER ON EXISTING BASES.
2
5
6
6"(M
AX)
3'-0" MIN12" MIN
STRUCTURAL FILL(ROAD BASE OR PIT RUN)
COMPACTED TO 95% MAXIMUMDENSITY
UNDISTURBEDEARTH
CONCRETE FORMS TANGENTTO SONOTUBE
MONOTHIC POUR
SONOTUBE DIAMETER(CUT TO BOTTOM OF SLAB)
SIDEWALK, CURB OR OTHERHARDSCAPE
5" RAISE
6" CONCRETE SLAB TANGENT TO BASE RADIUSAND SQUARE TO SIDEWALK
POLE BASE BOLT CIRCLE
SIDEWALK, CURB OR OTHERHARDSCAPE
5" RAISE
POLE BASE BOLT CIRCLE
MOW STRIP
SONOTUBE DIAMETER
CONCRETE FORMS TANGENT TO BASE RADIUSAND SQUARE TO SIDEWALK
SONOTUBE DIAMETER(CUT TO BOTTOM OF SLAB)
6" CONCRETE SLAB
12" MIN12" MIN
A POLE BASE DETAIL: SIDEWALKSCALE: NO SCALEB ADAPTER PLATE DETAIL
SCALE: NO SCALE
D POLE BASE GRASS/HARDSCAPE FINISH DETAIL: CORNER POLESCALE: NO SCALE
E POLE BASE GRASS/HARDSCAPE FINISH DETAIL: INTERIOR SECTIONSCALE: NO SCALE
TRANSPO 4100 COUPLING4 PER POLE, TYPICAL
N.T.S.
2-3/4
"
1"-8 UNC NUT PER ASTM A563 GRADE DH
1/8" X 1-1/8" X 1-1/8" X 2"FLAT WASHER PER ASTM F436
1/8" X 1-1/8" X 1- 1-1/8 X 2"FLAT WASHER PER ASTM F436
1" BREAKAWAY COUPLING
1/8" X 1-1/8" X 2"FLAT WASHER PER ASTM F436
GALVANIZED ANCHOR BOLT1"-8 UNC THREADS
1-1/2" (+/-) 1/8"
6-11
/16"
POLE BASE PLATE
UPPER WRENCH FLATS
TRANSPO 4075 COUPLING4 PER POLE, TYPICAL
GALVANIZED STEEL SHIM14g AND/OR 18g THICKNESS(IF NEEDED FOR LEVELING)
2 SHIMS MAXIMUM
TOP OF FOUNDATION
N.T.S.
3/4"-10 UNC NUT PER ASTM A563 GRADE DH
1/8" X 13/16" X 1-7/16"FLAT WASHER PER ASTM F436
3/4" BREAKAWAY COUPLING
1/8" X 13/16" X 1-7/16"FLAT WASHER PER ASTM F436
GALVANIZED ANCHOR BOLT3/4"-10 UNC THREADS
1-3/8" (+/-) 1/8"
1/8" X 13/16" x 1-7/16"FLAT WASHER PER ASTM F436
LOWER WRENCH FLATS
2-1/4
"5-
15/16
"
NOTES:3/4" OR 1" COUPLING PER POLE MANUFACTURER'SRECOMMENDED MOUNTING BOLT SIZE.
TRANSPO 4100 COUPLING4 PER POLE, TYPICAL
N.T.S.
2-3/4
"
1"-8 UNC NUT PER ASTM A563 GRADE DH
1/8" X 1-1/8" X 1-1/8" X 2"FLAT WASHER PER ASTM F436
1/8" X 1-1/8" X 1- 1-1/8 X 2"FLAT WASHER PER ASTM F436
1" BREAKAWAY COUPLING
1/8" X 1-1/8" X 2"FLAT WASHER PER ASTM F436
GALVANIZED ANCHOR BOLT1"-8 UNC THREADS
1-1/2" (+/-) 1/8"
6-11
/16"
POLE BASE PLATE
UPPER WRENCH FLATS
TRANSPO 4075 COUPLING4 PER POLE, TYPICAL
GALVANIZED STEEL SHIM14g AND/OR 18g THICKNESS(IF NEEDED FOR LEVELING)
2 SHIMS MAXIMUM
TOP OF FOUNDATION
N.T.S.
3/4"-10 UNC NUT PER ASTM A563 GRADE DH
1/8" X 13/16" X 1-7/16"FLAT WASHER PER ASTM F436
3/4" BREAKAWAY COUPLING
1/8" X 13/16" X 1-7/16"FLAT WASHER PER ASTM F436
GALVANIZED ANCHOR BOLT3/4"-10 UNC THREADS
1-3/8" (+/-) 1/8"
1/8" X 13/16" x 1-7/16"FLAT WASHER PER ASTM F436
LOWER WRENCH FLATS
2-1/4
"5-
15/16
"
NOTES:3/4" OR 1" COUPLING PER POLE MANUFACTURER'SRECOMMENDED MOUNTING BOLT SIZE.
BOLT COVER
SQUARE POLE(SEE FIXTURE SCHEDULE)
HAND HOLE COVER
1" X 36" X 4" HOOKANCHOR BOLT
GROUT UNDER BASE
FRONT
2'-0" MIN
SIDE
2'-0" MIN 3'-0" MIN.
5'-0"
FINISH GRADE
1" GRC (MINIMUM)1" PVC (MINIMUM)
SEE SITE PLANFOR WIRE SIZE
4 - #5 REBARWITH #2 TIES
CONTINUOUS #8 CU1/2" ROUND ALL EDGES
REBAR CONNECTION
CONCRETE BASE 3000 PSI INUNDISTURBED EARTH OR EARTH
COMPACTED TO 95% MAXIMUMDENSITY. BASE INSTALLED BY
PROFESSIONAL CONCRETE TRADEUNDER ELECTRICAL CONTRACT
2'-0"(MIN)
2'-6"
BREAK-AWAY BOLT DETAILSCALE: NO SCALEC
BREAK-AWAY BOLT DETAIL - PARKING LOTSCALE: NO SCALEC
3 6 0 w e s t a s p e n a v e n u es a l t l a k e c i t y , u t a h 8 4 1 0 18 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # : 18.0405
d a t e : April 18, 2019
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE ANDDATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND ISNOT INTENDED FOR CONSTRUCTION, RECORDINGPURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDINGALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &MODELS THEREOF, ARE PROPRIETARY & CAN NOT BECOPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED INWHOLE OR IN PART WITHOUT THE SOLE AND EXPRESSWRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
USU EASTERNCAPITALIMPROVEMENTSSITE LIGHTING
4/18/2019
CONSTRUCTIONDOCUMENTS
LAS
T S
AV
ED
: 13
Mar
19
LAS
T S
AV
E 3
/13/
2019
T:\J
OB
S\2
0180
82 U
SU
EA
STE
RN
MIS
CE
LLA
NE
OU
S\0
1 D
RA
WIN
GS
\05
ELE
CTR
ICA
L\S
INE
SO
UR
CE
PR
OJE
CT\
SH
EE
TS\E
S50
1 E
LEC
TRIC
AL
SIT
E D
ETA
ILS
.DW
G
ES501
ELECTRICALSITE DETAILS
F USU PARKING LOT POLE BASE DETAILSCALE: NO SCALE
BID SET
LIGHT FIXTURE SCHEDULETYPE MANUFACTURER/CATALOG NO. DESCRIPTION MOUNTING POWER LAMPS TYPE MANUFACTURER/CATALOG NO. DESCRIPTION MOUNTING POWER LAMPS
OW2- L6K GARDCO PWS-48L-300-NW-G2-2-UNV-SCBA EXTERIOR WALL FIXTURE; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; WALL 47 W 6000 LUMEN P4- L7K LUMEC MPTCCR-70W64LED4K-G2-LE4-UNV-CLO-(HS)-GY3TX/APR5W-12-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMENEQUIVALENT WITH PRIOR APPROVAL TYPE 2 OPTICAL DISTRIBUTION NOMINAL LED P4- L7K(B1) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED
4000K P4- L7K(B1F) COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KP4- L7K(H) FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS; HOUSE SIDE
SHIELD WHERE (H) OPTIONS SHOWN ON DRAWINGS
OW3- L6K GARDCO PWS-48L-300-NW-G2-3-UNV-SCBA EXTERIOR WALL FIXTURE; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; WALL 47 W 6000 LUMEN P4- L72 LUMEC MPTCCR-80W48LED4K-R-LE4-UNV-CDMGP-CLO-GY3TX/APR5W-18-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 79W 7000 LUMENEQUIVALENT WITH PRIOR APPROVAL TYPE 3 OPTICAL DISTRIBUTION NOMINAL LED P4- L72D NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; FIELD PROGRAMMABLE SMART DIMMING FACTORY POLE BASE NOMINAL LED
4000K SET AS COORDINATED WITH OWNER; 18' ALUMINUM POLE; DECORATIVE BASE 4000KCOVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE
BANNER ARMS WHERE NOTED ON DRAWINGS--PRE-DRILLED FOR BANNER ARMS WITH BLANKCOVER IF ACCESSORY NOT SPECIFIED.
OW3- L10 GARDCO PWS-48L-500-NW-G2-3-UNV-SCBA EXTERIOR WALL FIXTURE; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; WALL 76 W 10000 LUMEN P4- L9K LUMEC MPTCCR-90W80LED4K-G2-LE4-UNV-CLO-(HS)-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 91W 9000 LUMENEQUIVALENT WITH PRIOR APPROVAL TYPE 3 OPTICAL DISTRIBUTION NOMINAL LED P4- L9K(H) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE PARKING POLE BASE NOMINAL LED
4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS; HOUSE-SIDE SHIELD
WHERE (H) OPTION SHOWN ON DRAWINGS
OW4- L6K GARDCO PWS-48L-300-NW-G2-4-UNV-SCBA EXTERIOR WALL FIXTURE; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; WALL 47 W 6000 LUMEN P4- L9L LUMEC MPTCCR-90W80LED4K-G2-LE4-UNV-CLO-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 91W 9000 LUMENEQUIVALENT WITH PRIOR APPROVAL TYPE 3 OPTICAL DISTRIBUTION NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED
4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
OW4- L10 GARDCO PWS-48L-500-NW-G2-4-UNV-SCBA EXTERIOR WALL FIXTURE; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; WALL 76 W 10000 LUMEN P4- L12 LUMEC MPTCCR-135W80LED4K-G2-LE4-UNV-CLO-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 136W 12000 LUMENEQUIVALENT WITH PRIOR APPROVAL TYPE 3 OPTICAL DISTRIBUTION NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE PARKING POLE BASE NOMINAL LED
4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
P2- L3K LUMEC MPTCCR-35W32LED4K-G2-LE3-UNV-CLO-(HS)-GY3TX/APR5W-12-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 2 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMEN P4- L1L LUMEC MPTCCR-135W80LED4K-G2-LE4-UNV-CLO-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 4 OPTICAL DISTRIBUTION; UNIVERSAL POLE 136W 12000 LUMENP2- L3K(H) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED
COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS; HOUSE SIDE FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
SHIELD WHERE (H) OPTIONS SHOWN ON DRAWINGS
P2- L7K LUMEC MPTCCR-70W64LED4K-G2-LE2-UNV-CLO-(HS)-GY3TX/APR5W-12-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 2 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMEN P5- L7K LUMEC MPTCCR-70W64LED4K-G2-LE5-UNV-CLO-(HS)-GY3TX/APR5W-12-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 5 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMENP2- L7K(H) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED P5- L7K(B1) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED
COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
P3- L7K LUMEC MPTCCR-70W64LED4K-G2-LE3-UNV-CLO-(HS)-GY3TX/APR5W-12-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 3 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMEN P5- L9K LUMEC MPTCCR-90W80LED4K-G2-LE5-UNV-CLO-(HS)-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 5 OPTICAL DISTRIBUTION; UNIVERSAL POLE 91W 9000 LUMENP3- L7K(B1) NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE PARKING POLE BASE NOMINAL LEDP3- L7K(H) COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K
FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS; HOUSE SIDE FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
SHIELD WHERE (H) OPTIONS SHOWN ON DRAWINGS
P3- L7S LUMEC MPTCCR-70W64LED4K-G2-LE3-UNV-CLO-(HS)-GY3TX/APR5W-MOD(12") DECORATIVE WALKWAY LUMINAIRE; TYPE 3 OPTICAL DISTRIBUTION; UNIVERSAL POLE 73W 7000 LUMEN P5- L9L LUMEC MPTCCR-90W80LED4K-G2-LE5-UNV-CLO-(HS)-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 5 OPTICAL DISTRIBUTION; UNIVERSAL POLE 91W 9000 LUMENNO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 12" ALUMINUM POLE SLIPFITTER OVER EXISTING EXISTING PIPE STUB NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE LANDSCAPE BASE NOMINAL LED
EMBEDDED POST; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
P3- L9K LUMEC MPTCCR-90W80LED4K-G2-LE3-UNV-CLO-(HS)-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 3 OPTICAL DISTRIBUTION; UNIVERSAL POLE 91W 9000 LUMEN P5- L12 LUMEC MPTCCR-135W80LED4K-G2-LE5-UNV-CLO-GY3TX/APR5W-20-LBC3 DECORATIVE WALKWAY LUMINAIRE; TYPE 5 OPTICAL DISTRIBUTION; UNIVERSAL POLE 136W 12000 LUMENNO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE PARKING POLE BASE NOMINAL LED NO EQUIVALENTS VOLTAGE, ELECTRONIC DRIVER; 20' ALUMINUM POLE; DECORATIVE BASE PARKING POLE BASE NOMINAL LED
COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000K COVER; COLOR AS SELECTED BY OWNER TO MATCH ORIGINAL SELECTION SAMPLE; 4000KFIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS FIELD INSTALLED BANNER ARMS WHERE NOTED ON DRAWINGS
NOTES
LIGHT FIXTURE ACCESSORY APPENDB1 LUMEC (RETRO-309)-129151-120-PLANTSUP-PS-BRTX LETTER APPENDED TO FIXTURE TYPE; DOUBLE BREAK-AWAY, BANNER ARMS (SINGLE SIDED); AS SPECIFIED N/A PER FIXTURE H HOUSE SIDE SHIELD INTERNALLY MOUNTED, HOUSE-SIDE SHIELD ACCESSORY FACTORY MOUNT N/A PER FIXTURE
BANNERARMS.COM MORSETTO BA-4-1-1-2-DIAMETER-3-LENGTH-1-COLOR SPREAD 58" ANTICIPATED SEPARATION TOP TO BOTTOM ARM; ARM EXTENSION IN DIRECTION TYPE IN FIXTURE TYPEEQUIVALENT ONLY WITH PRIOR APPROVAL INDICATED ON DRAWINGS; 39" ANTICIPATED LENGTH (CONTRACTOR TO VERIFY WITH
EXISTING FIXTURES; DECORATIVE BALL ENDCAP; DIAMETER TO MATCH POLE; FINISH
TO MATCH POLE (CUSTOM FINISH WHERE ARM NOT SOURCED FROM POLE MANUFACTURER)
F FLAG HOLDER LETTER APPENDED TO FIXTURE TYPE; FLAGHOLDER ACCESSORY FOR TILT-MOUNT FLAG; FACTORY MOUNT N/A PER FIXTUREFINISH TO MATCH POLE ON FIXTURE TYPE
NOTES-FIXTURE APPENDS ARE ADDED TO STANDARD FIXTURE TYPES. APPENDS ARE INTENDED TO MODIFY FIXTURE CATALOG NUMBERS GIVEN ABOVE AS NOTED IN APPEND DESCRIPTION
OW4-L102 3 1
OW4-L102
OW4-L102314
1. REMOVE WALL PACK FIXTURE.
2. PROVIDE NEW WALL MOUNT FIXTURE.
3. EXTEND EXISTING CIRCUIT SERVING REMOVED LIGHTS TO NEW FIXTURES. CONCEALCIRCUITING IN EXISTING BUILDING FINISHES. CUT, PATCH AND REPAIR AS REQUIRED.
4. CONNECT TO EXISTING CIRCUIT/LIGHTING CONTROL INDICATED.
ELEVATION KEYED NOTES
3 6 0 w e s t a s p e n a v e n u es a l t l a k e c i t y , u t a h 8 4 1 0 18 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # : 18.0405
d a t e : April 18, 2019
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE ANDDATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND ISNOT INTENDED FOR CONSTRUCTION, RECORDINGPURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDINGALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &MODELS THEREOF, ARE PROPRIETARY & CAN NOT BECOPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED INWHOLE OR IN PART WITHOUT THE SOLE AND EXPRESSWRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
USU EASTERNCAPITALIMPROVEMENTSSITE LIGHTING
4/18/2019
CONSTRUCTIONDOCUMENTS
LAS
T S
AV
ED
: 18
Apr
19
LAS
T S
AV
E 4
/18/
2019
T:\J
OB
S\2
0180
82 U
SU
EA
STE
RN
MIS
CE
LLA
NE
OU
S\0
1 D
RA
WIN
GS
\05
ELE
CTR
ICA
L\S
INE
SO
UR
CE
PR
OJE
CT\
SH
EE
TS\E
S60
1 LI
GH
TIN
G S
CH
ED
ULE
.DW
G
ES601
LIGHTINGSCHEDULE &ELEVATION
1 SESSIONS HALL EAST ELEVATIONSCALE: 1/8" = 1'-0"
BID SET