Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Room Name
Project Name
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Washroom, Patient/Visitor
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Colour Tunable
Room Name
Project Name
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
SECURITY SYSTEM:
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
provide master zone lighting controller. Provide specialty lighting - LED under cabinet & cove lighting
LIGHTING:
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
SECURITY SYSTEM:
Colour Tunable
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Room Name
Workstation, Learners
STC Rating/NIC
Project Name
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Workstation, Touchdown
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Photocopy Room
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Project Name
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Food Servery
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Washable
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
1 Counter Gooseneck Lever Blade
PLUMBING:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
SECURITY SYSTEM:
Examination Light
Shower Light
Circadian Lighting
30A, 208Volt, 3 Phase 1 4 wire connection / future retherm unitsConditional 2
30A, 208Volt, 1 Phase 1 3 wire connection / future retherm unitsConditional 3
Program Number
Room Name
Rehabilitation Room
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
1
1
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
quantity mounting type faucet type control typePLUMBING:
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
quantity
Quad 6 provide recep. on 1 m centers mounted at 1400mm AFFNormal 2
Colour Tunable
Room Name
Storage, Equipment
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
quantity
Quad 6 provide recep. on 1 m centers mounted at 1400mm AFFNormal 2
Colour Tunable
Room Name
Medication Room
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
SECURITY SYSTEM:
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
1 Counter Gooseneck Lever Blade
PLUMBING:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Housekeeping Room
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
1 Floor Standard Lever Blade
PLUMBING:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 3 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Hand Hygiene
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
0
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Plastic LaminatePatient Wardrobe:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
2 duplex at HW & 1 duplex above bed non-nursing side
Normal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall) 1
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
1
1
1
Security Camera
SECURITY SYSTEM:
Colour Tunable
Room Name
Washroom, Patient
STC Rating/NIC
INTERIOR FINISHES:
Washable
Waterproof Cover.
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other: Locate 1 EPCA between toilet and sink, 1 adjacent to shower
ELECTRICAL REQUIREMENTS
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 2
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Plastic LaminatePatient Wardrobe:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
2 duplex at HW & 1 duplex above bed non-nursing side
Normal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall) 1
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
1
1
1
Security Camera
Colour Tunable
Room Name
INTERIOR FINISHES:
Washable
Waterproof Cover.
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other: Locate 1 EPCA between toilet and sink, 1 adjacent to shower
ELECTRICAL REQUIREMENTS
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 2
quantity
Security Camera
Room Name
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Plastic LaminatePatient Wardrobe:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: I
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
2 duplex at headwall & 1 duplex above bed non-nursing side
Normal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall) 1
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
1
1
1
Security Camera
SECURITY SYSTEM:
Colour Tunable
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: I
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Washable
Waterproof Cover.
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other: Locate 1 EPCA between toilet and sink, 1 adjacent to shower
ELECTRICAL REQUIREMENTS
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 2
quantity
Security Camera
Room Name
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Plastic LaminatePatient Wardrobe:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: I
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
2 duplex at HW & 1 duplex above bed non-nursing side
Normal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall) 1
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
1
1
1
Security Camera
SECURITY SYSTEM:
Colour Tunable
Room Name
Washroom, Patient
STC Rating/NIC
INTERIOR FINISHES:
Washable
Waterproof Cover.
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other: Locate 1 EPCA between toilet and sink, 1 adjacent to shower
ELECTRICAL REQUIREMENTS
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 2
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: I
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Alcove, Observation
STC Rating/NICSub-Department
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall) 0
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Room Name
Nourishment Alcove
STC Rating/NIC
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
quantity mounting type faucet type control typePLUMBING:
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
STC Rating/NICSub-Department
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Alcove, Seating
STC Rating/NICSub-Department
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Medical Vacuum
(Quantity) Other:
ELECTRICAL REQUIREMENTS
15A/20A, 120V Housekeeping 2 Locate HK outlets at 1400mm AFFNormal 1
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Washroom, Patient/Visitor
STC Rating/NIC
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
Security Camera
Room Name
Washroom, Staff
STC Rating/NIC
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 0
quantity
Security Camera
Room Name
Staff Room
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
1 Counter Gooseneck Lever Blade
PLUMBING:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Locker Area
STC Rating/NIC
INTERIOR FINISHES:
Paint
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
quantity mounting type faucet type control typePLUMBING:
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Washroom, Staff
STC Rating/NIC
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 0
quantity
Security Camera
Room Name
Project Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Room Name
Project Name
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: II
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
Conditional 1
Delayed Vital
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Washroom, Patient/Visitor
STC Rating/NIC
Project Name
INTERIOR FINISHES:
Washable
Non-Skid
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
ELECTRICAL REQUIREMENTS
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
Colour Tunable
Room Name
Washable
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
SECURITY SYSTEM:
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
provide master zone lighting controller. Provide specialty lighting - LED under cabinet & cove lighting
LIGHTING:
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
quantity
quantity feature 1 feature 2 feature 3 feature 4
Security Camera
SECURITY SYSTEM:
Colour Tunable
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Colour Tunable
Room Name
Workstation, Learners
STC Rating/NIC
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
Workstation, Touchdown
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
Security Camera
Room Name
Photocopy Room
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: BMS Monitor and ControlRoom Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio 1
quantity
Security Camera
Colour Tunable
Room Name
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks:Room Temp Control with Local Adjustment and Readout
Room Relative Humidity with Local Readout
Room Pressure Monitor with Local Readout
VENTILATION: Relative Pressure Equal Positive Negative Other:
Exhaust Required: Yes No Remarks:Dedicated Exhaust
HVAC: Type: III
Other Fixtures: Urinal:
Nursing Side Non-Nursing Side Nursing Side Non-Nursing Side
Oxygen
General Power
Remote Power Shut-Off
Workstation Task Light
Bedside Staff Light
Zone Controller
lighting remarks
Headwall Outlets 2PM/3A (per headwall)
Legend; A – Active/Allocated Data Port or Data Jack I – Inactive/Unallocated Data Port or Data Jack C – Coax NC – Nurse Call PM- Patient Monitoring Outlet
Intercom Station
VST: VoIP Staff Terminal/Station
EPCA Emergency Pull Cord station with Audio
quantity
Security Camera
Room Name
STC Rating/NIC
INTERIOR FINISHES:
Vandal resistant tamper proof pipe and valve cover
Vandal resistant tamper proof and access panels
Security-type ventilating grille
Tamper Proof and Anti ligature Breakaway Smoke Detector Cover
Electrical Cover Plate Extra Heavy Duty with Tamper Proof Screws
Upper Cabinets microwave shelfdoors
Sidelight
Patient Wardrobe:
Mail Slots:
MECHANICAL REQUIREMENTS
ROOM CONTROLS: Room Control Remarks: