Dry & Wet Riser Systems

Post on 21-Apr-2017

291 views 21 download

Transcript of Dry & Wet Riser Systems

DRY & WET DRY & WET

RISER RISER

SYSTEMSSYSTEMS

Who to decide on the nos. of wet riser main/Dry riser system to be installed ?

• Architect

Where to locate the wet/dry riser ?

• To be decided by Architect

Design Criteria

Numbers of rising mains depend on :

• Each rising main serves not more than 930m2 of floor area

• Cover a distance of 38m from a landing valve

The riser and landing valves shall be housed in:

• A protected area or lobby or shaft

Where to locate the breeching inlet

Design Criteria

Breeching inlet shall be less than 18m from the fire engine hard standing

Conspicuous position and accessible to the fireman

TYPE OF THE SYSTEMTYPE OF THE SYSTEM

LANDING LANDING VALVEVALVE

Dry Riser SystemDry Riser System

BREECHING INLETBREECHING INLET

AIR AIR RELEASEDVALVERELEASEDVALVE

Requirement of dry riser installation

• For residential building height more than 45m but less than 60m, or with basement or commercial building

• Ø100mm dry riser main pipe is for building height from 10m to 45m

• Ø150mm dry riser main pipe is for building height from 45m to 60m

Requirement of dry riser installation

•2- way breeching inlet for Ø100mm rising main

•4- way breeching inlet for Ø 150mm rising main

Breeching Inlet

Air Release valve

Hand Wheel

Landing Valve

Anti-Thief Device

FSSB SUBMISSION IS NOT REQUIRED FSSB SUBMISSION IS NOT REQUIRED

LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION

Submission

ConventionalConventional

PUMP FEED

GRAVITY FEED

TRANSFER PUMP

WET RISER PUMPS

JOCKEY PUMP

FROM PUB SUPPLY

4 WAY BREECHING INLET

LANDING VALVE

Old designOld design

• Non conventional - phase out

FROM PUB SUPPLY

AIR RELEASE VALVE

LANDING VALVE

DOMESTIC FEED

Tanks

WET RISER PUMP

4 WAY BREECHING INLET WET RISER TANK

Down Comer System Down Comer System

DOMESTIC

21 ST STOREY

25TH STOREY

BREECHING INLET

Ø100mm GI PIPE

1ST STOREY

Between 60m to 70 m

WET RISER

Phase out for New Building (17 Sep’01)

Transfer Water Tank Design

• One rising main = 11.5 m3 (15min) @ 27 l/s

• Two rising main = 23 m3 (15min) @ 38 l/s

Roof top wet riser tank layoutRoof top wet riser tank layout

DIA 3.621m 1m

2m

3m length for pump set

1mRing tanks

3-Rings Tank

3 nos. = 49 m3

5 nos. =75 m3

ACOUSTIC SOUND INSULATION

3

1

12m

7m

4-Rings Tank

2 nos. = 49 m3

3 nos. =75 m3

Wet riser tank capacity

• One rising main capacity = 49 m3 for half hours + 1.1 m3 fire hose reel

• Two rising main capacity=74 m3 for half hours +1.1 m3 fire hose reel

Building Above 120mBuilding Above 120m

FROM PUB SUPPLY

1ST STOREY

Mid-Storey

Roof Storey

WET RISER PUMPHOSEREEL PUMPTRANSFER PUMP

Down feed

Down feed

Transfer tanks

Power required

• PUB supply• Generator - supply to 4 blocks per generator

FSSB SUBMISSION IS REQUIRED FSSB SUBMISSION IS REQUIRED

LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION

Submission

50TH STOREY HEIGHT BUILDING50TH STOREY HEIGHT BUILDING

WET RISER AND HOSEREEL SERVICE WET RISER AND HOSEREEL SERVICE DUCTDUCT

TESTING AND TESTING AND

COMMISSIONING OF WET COMMISSIONING OF WET

RISERRISER

WET RISER REQUIREMENTSWET RISER REQUIREMENTS

RESIDENTIAL COMMERCIAL & ANY MIXED BUILDING FLOW RATE 27L/S FOR FIRST 38L/S FOR THE FIRST RISING MAIN RISING MAIN 19L/S FOR EACH ADDITIONAL 13.5L/S FOR EACH RISING MAIN ADDITIONAL RISING MAIN MAXIMUM SUPPLY RATE OF 190L/S MAXIMUM SUPPLY RATE OF 135 L/S

RUNNING PRESSURE 3.5BAR TO 5.5 BAR 3.5 BAR TO 5.5 BAR

STATIC PRESSURE 8 BAR 8 BAR

PLAN VIEW FOR WET RISER AND PLAN VIEW FOR WET RISER AND HOSE REELHOSE REEL

Check Valve

Gate Valve

Drain Cock

Check Valve

Rubber Expansion Joint

Gate Valve c/w

limit switch

Pilot Valve

Motorize Valve

Pressure Relief Valve

Bypass system

Flow Meter

Motorize Valve

Gate Valve

Down feed

Pilot Valve

Check Valve

Flow Switch

Down feed Pipe

Duty Pump

Standby Pump

Fire Pump

Jockey Pump

Level Indicator

Landing ValveStrap Lock

Air Release

valve

Drain Cock

Limit Switch

Butterfly valve

Check Valve

Piping

Pressure Switches

Pressure Gauge

Limit Switch Indicator Panel

Alarm Bell

Fire Extinguisher

Wet Riser Control Panel