Digital Capacitor BankControl M-62833 Phase Digital Capacitor Bank Control for Remote Capacitor Automation, Monitoring and Protection
CONTROLS
• Flexible Communication Options For Wired or Wireless Networks
•RS-232, RS 485, & Serial Fiber Optic (ST or V-Pin)
•Ethernet Over Copper RJ-45 @ 10/100 Base-T
•Ethernet Over Fiber Optic (ST or V-Pin) 100 Base-FX
•Embedded Bluetooth, Class 1 (v2.0), 128 bit encryption, up to 1/2 mile transmission (with appropriate antenna)
•Supports DNP3.0 & MODBUS® Protocols
• Time sync via DNP3.0 Set Time Command
•DNP mapping templates to match SCADA historical databases
•Sequence of Events (SOE) Recording Of Events - Stores 160 events, ms time-stamped with Graphic Logic Initiate from critical operational factors
• FULL DNP implementation – Including DNP File Transfer, multi-addressing, unsolicited response, source address validation
• TRUE Ethernet – Full 10/100Mbps auto-negotiable concurrent multi-session and multi-protocol support
•DNP+Ethernet – Send/receive DNP configuration files using DNP File Transfer Protocol
•Device Discovery using CapTalk
•DNP SCADA Heartbeat – Integrity check of communications media and/or Master. Fully programmable
•Quick (10 -15 second) Uploading of Configurations, Settings, Firmware Upgrades
•Assists in locating harmonics adversely affecting customer processes
•Helps mitigation measures to determine corrective filter design and location
•Control Cabinet – Direct Pole-Mount with Meter Socket Plug. Mount the control away from the meter socket and away from power lines and other equipment
•Oscillography Capture – Selectable 16, 32, or 64 samples per cycle. Captures sags, swells, CBEMA events and sub-synchronous transients
•Cyber Security – Authentication and Multi Level Access Codes, Smart Flash SD Card serves as Cyber Security Hard-Key with Audit Log
•Data Logging Continuous Recording – Data stored in non-volatile memory requiring no battery backup
•CBEMA Excursion Recording and Reporting
•Harmonics Detection, Recording, Protection and Suppression
•Downloading of Event Reports, Oscillography
•No need for battery to back up clock
•Smart Flash SD Card Slot
•Supports Control Cloning
–2–
M-6283 Digital Capacitor Bank Control
Standard Features • Three-phasesensing,onephaseoperation
-selectableregulation;operationbasedonindividualoraverageofthethreephases
• Fourcontrolmodesofoperation:
–ClassicAutomatic(Voltage,optional
VArControloroptionalCurrentControl)
–AutoAdaptivemode(FixedorAveraging)
–Remote
–Manual
• Twooverridemodesofoperation:
–Temperature
–Time
• TimeDelay–DefiniteandInverse
• Adjustable Maximum/Minimum VoltageLimits
• NeutralUnbalancecurrentdetection
–Bank/SwitchFailed
–BankClosed
–BankOpen
–Supports200mAinputtocontrol
• User selectable Overvoltage limit/Undervoltage limit and time delay forremotecontrolsupervision
• AdjustablewarningtimersforClose/Open/Re-close
• Adjustable Close/Open output pulseduration
• Real-Time Metering of measured andcalculatedparameters
• VTRatioCorrection,VT andCT (PhaseandNeutral)Multiplier
• OperationsCounter
• ResettableOperationsCounterwithAlarm
• HarmonicAnalysisofVoltageandCurrentSignals,uptothe31stplusTHD
• DataLogging
• Remote/Auto-LocalManualswitch
• Outputs:Close,OpenandAlarm
• 20 Character by 2 Row LCD display(LEDbacklit)
• Upto30unique15characterUserAccessCodes(Level1orLevel2)
• CBEMA monitoring to detect sags andswells and trigger data collection andalarmingfunctions
• SmartFlashSDCardSlotsupportingSDandSDHCSDcards
• SmartFlashSDCardcanbelinkedtooneor multiple controls providing a physicalsecurity"Key"whichprovidesUserAccessLevel2AccesstothecontrolwhentheSDCardisinsertedforsettingsmanipulation
• SequenceofEvents(SOE)recorder
• DeviceDiscovery
• SourceAddressValidation
• Oscillography
• FrontPanelLEDsforRemote/Auto,LocalManual,Alarm,Close,Open,OK,RSSI,Neutral Unbalance, (TX) Transmit and(RX)Receive
• ProgrammableAlarms
• Front Panel Hot Buttons provide directaccesstomenuheaders
• FrontPaneltesting:
–Int/ExtVoltageSourceswitch
–ExternalPowerinputterminals
–MeterOutterminals
• Communication Protocols DNP3.0 andMODBUS®
• Adaptive Delta Voltage sensing duringswitchoperations
• DailyOperationsCounterLimit
• CapTalk® S-6283 CommunicationsSoftware
• Capacitor Bank switch status inputs forphaseA,BandC
• Graphical display of real-time harmonicspectrum of voltage and current usingCapTalkCommunicationsSoftware
• CommunicationPorts:
–USB
–RS-232
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.
–3–
M-6283 Digital Capacitor Bank Control
Standard Features (Cont’d) • SCADA"HeartBeat"(withDNP3.0only)
• Supports Station and Feeder LevelDNP addressing in addition to individualaddressingforSmartGridapplications
• OnepushbuttonaccesstouserconfigurableWakeupscreenformanualdatarecordingwithSmartFlashSDCardsavingfeature
• Oneset(3)ofsparefusesareincluded
• CapacitorBankSwitchselection"SolenoidDriven"or"MotorDriven"forClose/OpenPulseDuration
• 200mANeutralCurrent inputforNeutralUnbalancedetection
• SCADATestMode
Optional Control Features • Automatic VAr Control Mode options
include:
–0to10VLinePostSensorinput
• Local Wireless Bluetooth® capability.Class1TypeBluetoothUSBAdapterthatsupportswirelesstransmissionupto300meters.
• EthernetPort(10/100Base-T)isavailablethrough a RJ-45 jack or Fiber Optic STConnector.This port supportsDNP overTCP/IPandUDP;MODBUSoverTCP/IP.
• 5 A Neutral Current input for NeutralUnbalancedetection
• LinePostCurrentSensorinputforNeutralUnbalancedetection(suppliesbothvoltageorcurrentunbalancedetection)
• CommunicationsPorts:
–STFiberOptic
–V-pinFiberOptic
–RS-485
• TheM-6283 can be housed in a NEMA4 Molded Lexan®, Cold Rolled Steel orStainless Steel Control cabinet. (SeeM-2980A section of this specification fordetailedinformation).
–4–
M-6283 Digital Capacitor Bank Control
CAPACITOR BANK CONTROL OPERATIONControl ParameterDependingonthecontrolmodeofoperation, thecontrolparametercanbeeithervoltage,VArsorcurrent.ForexamplethecontrolVoltageisthemeasurementusedinthecontrolalgorithmtomaketheloadvoltageregulationdecision.Thecontrolparametershallbeuserselectable.
Thethreeuserselectableuseroptionsshallbe:
• SinglePhaseSelection
• ThreePhaseAverage/Total
• Maximum/MinimumofThreePhase–(Future)
Single Phase SelectionThisoptionwillallowtheusertochoosewhichphaseA,BorCisusedasthecontrollingparameter.Oncethisisselected,thecontrolwillusethatphasevalueinClassicvoltagecontrolmodeorAutoAdaptivemodetomakedecisiononhowtoregulatetheloadvoltage.TheoptionisvalidforallthreemethodsofcontrolnamelyVoltage,VArsandCurrent.
Three Phase Average/TotalThisoptionwillaveragethevalueofallthreephasequantitiesandthisaveragewillbeusedtomakethecontroldecision.TheoptionisvalidforallthreemethodsofcontrolVoltage,VArsandCurrent.ItisimportanttonotethatwheninthecontrolisusingVArControl,theaveragingisreplacedbythetotalsumoftheVArsofallthreephases.
InadditionwhentheoptionisselectedtheCTMultiplier isassumedtobeequal.InControlModeLimitsthemaximumandminimumofthe3phasesisusedtoevaluatewhetherthevoltageisviolatingtheuserassignedlimits.
Control Modes of OperationThecontrolincludestwostandardmodesofAutomaticVoltageControl(ClassicVoltageControlandAutoAdaptiveVoltageControl),OptionalVAr ControlmodeandCurrent Controlmodeareavailable.
Classic Voltage Control Mode:The controlwillmake itsOpenandClose switching decisions basedonmeasuredLineVoltageconditionsandTimeand/orTemperatureoverrideswhenapplied.Voltageexcursionsbeyondthesetvalueforgreaterdurationthanthetimedelaywillresultinappropriatecontroloperation.
– Control Open Voltage:Adjustablefrom95.0to140.0Vin0.1Vincrements
– Control Close Voltage: Adjustablefrom95.0to140.0Vin0.1Vincrements
– Close and Open Time Delays:DefiniteorInverse;adjustablefrom0secondsto600seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.
– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.
– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.
NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.
–5–
M-6283 Digital Capacitor Bank Control
Auto Adaptive Voltage Control Mode:Thisfeaturecontainstwocontrolmethods,FixedorAverage.TheFixedmethodprovidesaBandcentersettingthecontrolcomparestomeasurevoltagetoopenorclosetheCapacitorbank.TheAveragemethodusesanEffectiveBandcenterbasedonalongtermaverageoftheinputvoltagetocomparetomeasurevoltagetoopenorclosethecapacitorbank.BothmethodsemployaninversetimerandBandwidthtooptimizebankoperationandeliminateunnecessaryswitching.Also,Timeand/orTemperatureoverridescanbeapplied.
– Fixed-Band Center:Adjustablefrom100.0to135.0Vin0.1increments
– Bandwidth (Multiple of Delta V): Adjustablefrom1.0to2.0in0.1increments
– Close and Open Time Delays: Inverse only; adjustable from60 to 3600 seconds, in 1 secondincrements.Timerresetisfixedasintegrating.
– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.
– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.
NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.
Automatic VAr Control Mode Option*:ThecontrolwillmakeitsOpenandCloseswitchingdecisionsbasedonmeasuredlineVArconditionsandTimeand/orTemperatureoverrideswhenapplied.VArexcursionsbeyondthesetvalueforgreaterdurationthanthetimedelaywillresultinappropriatecontroloperation.Thecontrolcanbeorderedwitheithera5ACTorLinePostCurrentSensorinputstoprovidephasecurrentmeasurementtothecontrol.
– Control Open VArs:–100%to100%ofsingle-phasecapacitorBanksizein1%increments
– Control Close VArs: 0%to100%ofsingle-phasecapacitorBanksizein1%increments
– Close and Open Time Delays:Definite or Inverse; adjustable from0 seconds to 600 seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.
– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.
– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.
NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.
*OnlyavailablewithVArandCurrentControlModeoption.
–6–
M-6283 Digital Capacitor Bank Control
Automatic Current Control Mode Option*:ThecontrolwillmakeitsswitchingdecisionsbasedonmeasuredLineCurrentconditionsandTimeand/orTemperatureoverrideswhenapplied.Currentexcursionsbeyondthesetvalueforgreaterdurationthatthetimedelaywillresultinappropriatecontroloperation.Thecontrolcanbeorderedwitheither5ACTorLinePostSensorinputstoprovidephasecurrentmeasurementtothecontrol.
– Control Open Current:Adjustablefrom10to600Amps
– Control Close Current: Adjustablefrom10to600Amps
– Close and Open Time Delays:Definite or Inverse; adjustable from0 seconds to 600 seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.
– Time Override:IntheAutoControlModeaTimeOverridecanbeappliedtocapacitorbankOpenandCloseoperations.TheTimeOverridefeatureconsidersStartDate,StartTime,Duration,RecurrencePatternandaRangeOfOccurrencestoimplementtheoverride.
– Temperature Override: In the Auto Control Mode a Temperature Override can be applied tocapacitorbankOpenandCloseoperations.TheTemperatureOverride featureconsiderssensedambienttemperatureandimplementsoverrideaction(Open,CloseorNone)foreitheraboveorbelowtemperaturesetpointconditions.
NOTE: TimeandTemperatureOverridescanbeoverriddenbyControlModeLimits.
Remote Control Mode: Inthismode,thecontrolreceivescommandsthroughcommunicationsforClosingorOpeningoftheCapacitorBank.
Remote Control Mode Limits: These limitscanbedisabledorenabled. If controloperationwill resultinvoltageoutsideof these limitsoperationwillbeblockedandnotificationwillbesent to thesender. Ifmeasuredvoltageisoutsideoftheselimits,thecontrolwillinitiate anoperationinthedirectiontoreturnvoltagewithinlimits.
– Overvoltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements
– Undervoltage Limit: Adjustablefrom95.0to140.0Vin0.1Vincrements
– Voltage Limits Timer:DefiniteorInverse;adjustablefrom0secondsto600seconds,in1secondincrements.Timerresetcanbeselectedasinstantaneousorintegrating.
*OnlyavailablewithVArandCurrentControlModeoption.
–7–
M-6283 Digital Capacitor Bank Control
Control Mode Limits:Ifcontroloperationwillresultinvoltageoutsideoftheselimits,operationwillbeblocked.Ifmeasuredvoltageisoutsideoftheselimits,thecontrolwillinitiate anoperationinthedirectiontoreturnvoltagewithinlimitsafterthesettimedelay.Onlytheblock andnottheinitiate operationisimplementedinremotemanualmodeduetopersonnelsafetyconsiderations.Thesecontrolmodelimitscanbe;"DisableAll","EnableinAuto","EnableinRemote","EnableinManual".Anycombinationof"EnableinAuto","EnableinRemote"and"EnableinManual"canbeselected.Theselimitswillapplyregardlessofthecontrolmodeofoperationselectedprovidingvoltageoverridefunctionalityinalloperationalmodes.
– Maximum Voltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements
– Minimum Voltage Limit:Adjustablefrom95.0to140.0Vin0.1Vincrements
– Definite Time:Adjustablefrom0to60secondsin1secondincrements
Local Manual Mode:InthismodethecontrolwilldisableAutomaticandRemoteControlmodes.Inthismode,thecontrolwillrespondtothefrontpanelCLOSE/OPENswitchposition.
Bank Operational Delays:
– Close Warning Delay:Adjustablefrom0to90secondsin1secondincrements(Enable/Disable)
– Open Warning Delay:Adjustablefrom0to90secondsin1secondincrements(Enable/Disable)
– Re-Close Delay:Adjustablefrom300to600secondsin1secondincrements
– Close/Open Pulse Duration:
SolenoidDrivenSwitchType–Adjustablefrom50to100msin1msincrements
MotorDrivenSwitchType–Adjustablefrom5to15secondsin1secondincrements
NOTE: TheCloseandOpenWarningDelays"Auto"and"Remote"canbeenabledordisabled.However,"Manual"isalwaysenabled.
–8–
M-6283 Digital Capacitor Bank Control
Neutral Unbalance Current/Voltage DetectionCurrentandVoltagemeasuredbytheNeutralBalanceCurrentDetectionfeatureisusedtodetectbankorswitchfailuresaswellasbankOpenorClosestatus.NeutralUnbalanceCurrent/Voltageismeasuredusingoneofthefollowing:
– 200 mA CT Input:Thisoptionisofferedbydefaultintheunit.
– 5 A CT Input:Thisoptionmustbespecifiedwhenordered.
– 10 V Line Post Current Sensor: ThisoptionmustbespecifiedwhenorderedandshouldbechosenifeitheraVoltageorCurrentLinePostSensorwillbeused.
Neutral Unbalance Current Levels: Bank/Switch Failed Level 1 (can be enabled or disabled)
– Bank/Switch Failed:Adjustablefrom1.0to200.0Ain0.1Aincrementsor0.00to300.00Vin0.01increments.
Bank/Switch Failed Level 2 (can be enabled or disabled)
– Bank/Switch Failed Level 2:Adjustablefrom1.0to200.0Ain0.1Aincrementsor0.00to300.00Vin0.01increments.
– Time Delay:Adjustablefrom10to300secondsin1secondincrements
– Prior Operation:
Action Taken: RetryOperation,ReverseOperationandBlock,ResetBlock
Number of Attempts:1to9
Block Reset Time Delay: Adjustablefrom1to72hoursin1hourincrements
– No Prior Operation: (canbeenabledordisabled)
Open and Lockout Time Delay: Adjustablefrom1to4320minutesin1minuteincrements
Reset Lockout: Canbeenabledordisabled
Lockout Reset Time Delay: Adjustablefrom1to72hoursin1hourincrements
Bank Status (canbeenabledordisabled) – Bank Status Closed:Adjustablefrom0.10to10.00Ain0.01Aincrementsor0.00to30.00Vin0.01
increments.IfNeutralCurrentisgreaterthanthissetting,thebankisconfirmedtobeclosed.
– Bank Status Open:Adjustablefrom0.10to10.00Ain0.01Aincrementsor0.00to30.00Vin0.01increments..IfNeutralCurrentislessthanthissetting,thebankisconfirmedtobeopen.
– Bank Status Time Delay:Adjustablefrom10to300secondsin1secondincrementsforboth(CloseandOpen)
– Action Taken:Ifbankstatusindicatesanunsuccessfuloperation,thecontrolcanbeprogrammedtotakenoactionorretrytheoperation.
Bank Switch Status FeedbackSwitchauxiliarypositioncontactscanbeconnectedtothecontroltoconfirmindividualphaseswitchpositions.IndividualphaseswitchpositionindicatorscanbeobservedontheMeteringandStatusDialogScreen(Figure1).
BankSwitchStatusdetectioncanbedisabledorenabled.
–9–
M-6283 Digital Capacitor Bank Control
Additional SettingsVT/CT Setup: – Voltage Multiplier:Adjustablefrom0.1to3260.0in0.1increments
– VT Correction:Adjustablefrom-15.0Vto+15.0Vin0.1Vincrements
– Phase Current Multiplier*:Adjustablefrom1.0to200in.01increments
– NeutralCurrentMultiplier:
5ANeutralCTandLinePostSensor–Adjustablefrom1.0to150in0.1increments
200mANeutralCT–Adjustablefrom1.0to3260in0.1increments
Counters: – Resettable Counter: A software counter that increments by one count per Close or
Openoperation.Resettableto0.
– Operation Counter Preset: A software counter which increments by one count per Close orOpenoperation.Presettablefrom0to999,999.
– Resettable Counter Alarm Limit: Alimit thatalerts theusereitherbycommunicationsand/oraprogrammablealarm.Itissettablefrom0to999,999.
– Daily Operation Counter Limit: A limit that will block any further Close/Open operation until12:00AMandalertstheusereitherbycommunicationsand/oraprogrammablealarm.Itissettablefrom2to99.
–10–
M-6283 Digital Capacitor Bank Control
*OnlyavailablewithVArandCurrentControlModeoption.
MonitoringHarmonic Analysis:Providesthetotalharmonicdistortionandtheharmoniccontentofthevoltageandcurrentuptothe31stharmonic.
Alarms:Thealarmrelayisuser-programmablewithanon-latchingoutputcontactthatclosesononeormoreofthefollowingconditions:
•MaximumVoltageLimit •MinimumVoltageLimit •RemoteOvervoltageLimit
•RemoteUndervoltageLimit •Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1
•ResettableCounterLimit •DailyOperationCounterLimit •VoltageHarmonics
•CurrentHarmonics* •RemoteManual •SelfTest
•DeltaVoltageAlarm
Sequence of Events: A built-in Sequence of Events (SOE)Recorder has the capability to record up to160events.ItallowstriggereventstobeAND’edandOR’edforPickupandDropout.TriggerEventsinclude:
•CloseCommand •OpenCommand •MaximumVoltageLimit
•MinimumVoltageLimit •RemoteOvervoltageLimit •RemoteUndervoltageLimit
•Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1 •SCADAHeartBeat(withDNP3.0only)
•VoltageHarmonics •CurrentHarmonics* •CBEMA1Through4
•DeltaVoltageAlarm •PhaseOvercurrent* •PowerFactor
ParametersthatarecapturedwitheachSequenceofEventsRecordinclude:
•Voltage(PhaseA,B,C) •RMSVoltage(PhaseA,B,C)•DeltaVoltage(PhaseA,B,C)
•PrimaryVoltage(PhaseA,B,C)•Frequency •NeutralCurrent
•OperationCounter •ResetOperationCounter •Current(PhaseA,B,C)
Oscillography:Abuilt-inOscillographRecordercontinuouslyrecordsvoltageandcurrentwaveformdatainabuffermemory.Thismemorycanbeconfiguredfrom1to16partitions.Whentriggered,asnapshotofwaveformdatafrom235to2000cyclesiscaptured.Thedatacapturedcanbespecifiedfrom5%to95%post-triggerevent.Theremainderofthepercentageispre-triggerdata(samplespercycleisselectableas16,32or64samples/cycle).TriggerEventsinclude:
•CloseCommand •OpenCommand •MaximumVoltageLimit
•MinimumVoltageLimit •RemoteOvervoltageLimit •RemoteUndervoltageLimit
•Bank/SwitchFailed-Level2 •Bank/SwitchFailed-Level1 •SCADAHeartBeat(withDNP3.0only)
•VoltageHarmonics •CurrentHarmonics* •CBEMA1Through4
•DeltaVoltageAlarm •PhaseOvercurrent*
Data Logging:Abuilt-inDataLoggingRecorderthatcontinuallyrecordsdatainnon-volatilememory.Dataloggingwillcontinueindefinitelyaslongasthedataintervalissettoanon-zerovalue.Datatoberetrieved:
•Voltage •PrimaryVoltage •DeltaVoltage
•AutoAdaptive •PrimaryNeutralCurrent •Frequency
•OperationCounter •ResettableCounter •CapacitorBankStatus
•Temperature •PrimaryPhaseCurrent* •PowerFactor*
•PrimaryWatts* •PrimaryVArs* •PrimaryVA*
–11–
M-6283 Digital Capacitor Bank Control
MeteringFigure1providesanexampleoftheMeteringparametersthatareavailablefromthecontrol.
NOTE: PowerFactorandPrimary;PhaseCurrent,Watts,VArsandVAareonlyavailablewhentheVArControlModeoptionispresent.
Figure 1 Metering and Status Dialog Screen
InputsSwitch Power Input:Nominal120VAC,60Hz(50Hzoptional);operatesproperlyfrom95to140VAC.Ifsetat60Hz,theoperatingsystemfrequencyisfrom55to65Hz;ifsetat50Hz,theoperatingsystemfrequencyisfrom45to55Hz.Theburdenimposedontheinputis8VAorless.Theunitwillwithstandtwicethenominalvoltageforonesecondandfourtimesthenominalvoltageinputforonecycle.
V1, V2, and V3 Monitor Voltage Inputs:0–10VACLinePostVoltageSensorinput,optional0to150VACVTinput.Theseinputsaresuitableforusewithhighimpedancevoltagedividers.Inputimpedanceisapproximately1MΩ.Theinputswillwithstandtwicethemaximumvoltageratingforonesecondandfourtimesthevoltagethevoltagemaximumvoltageratingforonecycle.
Phase Current Input:0–10VACLinePostCurrentSensorinput.Externalcurrenttovoltageconversionisrequiredif5ACTistobeused.Appropriatemultiplierisutilizedtocalculatetheprimaryphasecurrent.LinePostCurrentSensoroptionalsoincludesaphaseshiftcompensationsetting.
Neutral Unbalance Current Input:0–10VACLinePostCurrentSensor,200mA,or5Ainputwillalsobesupported.Appropriatemultiplierisutilizedtocalculatetheprimaryneutralunbalancecurrent.
–12–
M-6283 Digital Capacitor Bank Control
OutputsClose Output:Capableofswitching10Afor30secor45Afor25ms.
Open Output:Capableofswitching10Afor30secor45Afor25ms.
User-Programmable Alarm Output:OneForm"C"contactcapableofswitching6Aat125VACor0.2Aat125Vdc.
Digital InputsThree12VdcInputsforswitchstatusandoneinternallywettedintrusiondetectioninput.
Front Panel ControlsMenu-drivenaccesstoallfunctionsbywayofsixpushbuttonsandatwo-linealphanumericdisplay.Thereareupto30programmableUserAccessCodes(Level1orLevel2)availabletoprovidevariouslevelsofaccesstothecontrolfunctions.
TheCapacitorBankcontroloffersa2-lineby20characterLCDdisplay(LEDbacklit)forenhancedviewingindirectsunlight.
CLOSE/OPENswitchallowslocalmanualCloseandOpencommandstobeinitiated.
REMOTE/AUTO - LOCAL MANUALswitchallowsAutomaticoperationofthecontrolorManualoperationfromthefrontpanelbyusingtheCLOSE/OPENtoggleswitch.
VOLTAGE SOURCEswitchdisconnectsallpowerfromtheunitwhenselectedtotheOFFposition.TheEXT positionallowsthecontroltobepoweredfromthefrontpaneltestjacks.
EXTERNAL POWERbindingpostsallowapplicationofa120VRMSnominalvoltagetotheunitfortesting.
METER OUTbindingpostsallowreadingoftheinputvoltage.
Smart Flash SD Card SlotAllowstheusertoperformthefollowingfunctions:
•LoadSetpoints •SaveSetpoints •SaveDataLog •SaveSequenceofEvents
•SaveOscillographRecords •CloneSave •CloneLoad •LoadDNPConfig
•SaveDNPConfig •FirmwareUpdate •SaveMeteringData •SaveWakeScreenData
•SDCardUserAccess(PhysicalSecurityKey) •QuickCapture
LED IndicatorsFront panel LED indicators show the following control conditions: REMOTE/AUTO, LOCAL/MANUAL, ALARM, NEUTRAL UNBALANCE, CLOSE, OPEN,CPU OK,RSSIandTX (Transmit)andRX(Receive).
–13–
M-6283 Digital Capacitor Bank Control
CommunicationsThecommunicationportsprovideaccesstoallfeatures,includingmetering,softwareupdates,andprogrammingofallfunctions.ThisisaccomplishedusingaconnectionfromanyWindowsTM-compatiblecomputerrunningtheCapTalk®S-6283CommunicationsSoftwareorSCADAcommunicationssoftware.
Protocols:ThestandardprotocolsincludedintheM-6283areDNP3.0andMODBUS®.TheUSBportusesMODBUS for localcommunications.TheoptionalEthernetPortsupportsDNP3.0andMODBUSprotocolssimultaneously.DNPMasterSourceAddressAuthenticationissupportedallowingmultipleSCADAMasterstocoexistonthesamecommunicationsnetwork.
Communications Via Direct Connection:CapTalksupportsdirectcommunication(MODBUSprotocol)withtheM-6283usingtheapplicableconnector(USBcable)forthecomputer.Additionally,thestandardRS-232communicationsportaswellasthe2-wireRS-485andSerialFiber(STorVpin)optionalcommunicationsportscanbeusedtocommunicateviaCapTalk.
Optional Ethernet Port:TheoptionalEthernetPortprovidesanRJ-45(10/100Base-T)ora(100Base-Fx)FiberOpticinterfaceforethernetcommunicationtotheM-6283.Theprotocolssupportedare:MODBUSoverTCP,DNP3.0overTCPandDNP3.0overUDP.Theportsupportsuptoeightconcurrentconnections.ThemaximumnumberofallowedDNPconnectionsisfiveforeachprotocol(5forUDP,5forTCP).ThemaximumnumberofMODBUSconnectionsiseight.EthernetPortsettingscanbeconfiguredmanuallyorviaDHCPprotocol.MODBUSprotocol"PortNumber"andDNPProtocol"PortNumber"canbechangedmanuallyfromdefaultvalues.DNPMasterSourceAddressAuthenticationissupportedallowingmultipleSCADAMasterstocoexistonthesamecommunicationsnetwork.Thisoptioncanbefieldinstalled.
Optional Bluetooth:TheoptionalBluetooth® (V2.0+EDRClass 1Type) provideswireless access to theM-6283.WithBluetooththeuserisabletoconfigurethecontrol,readstatusandmeteringvaluesaswellaschangesetpoints.Thisoptioncanbefieldinstalled.TherearefourmodesofoperationfortheBluetooth:
Mode 0 –Thedeviceisdiscoverableandconnectabletoanyclientstation.
Mode 1 –(Future)Thedeviceisnon-discoverablebutitisconnectabletoanyclientstationwhoknowsthecontrolBluetoothdeviceaddressindicatedunder“Control BT Device”intheHMI.
Mode 1 –HasbeenaddedtomeetCIPrequirement.(CIP-0007-4SystemSecurityManagement)(R2.3)
Communications Using Networking:TheaddressingcapabilityoftheM-6283allowsnetworkingofmultipleM-6283’s.Eachcapacitorbankcontrolcanbeassignedanaddress,FeederAddressorSubstationAddressrangingfrom1to65519.Selectedcommandsmaybebroadcasttoallcontrolsonthenetwork.Figures3,4and5illustratetypicalnetworkconfigurations.Addresses1-247canbeassignedtoMODBUSand1-65519forDNP3.0.
ApplicationUsingCapTalkCommunicationsSoftware,theoperatorhasreal-time,remoteaccesstoallfunctionsoftheM-6283. The protocols implement half-duplex, two-way communications. This allows all functions, whichwouldotherwiserequirethepresenceofanoperatoratthecontrol,tobeperformedremotely.Communicationcapabilitiesinclude:
• Interrogationandmodificationofsetpoints
• Broadcastofcommands
• Recognitionofalarmconditions,suchasvoltageextremes
• Unsolicitedexceptionreporting
• MulticastcapabilityusingUDP
Unit IdentifierA2-rowby20-characteralphanumericsequence,setbytheuser,canbeusedforunitidentification.
–14–
M-6283 Digital Capacitor Bank Control
COM 1, RS-485, RS-232, (2Wire),or Fiber Optic (ST or Vpin) Cable
USB Cable
Switched Capacitor Bank
PrinterComputer Running CapTalk® S-6283
Communications Software
BeckwithDigital
CapacitorControl
Figure 2 Direct Connection
–15–
M-6283 Digital Capacitor Bank Control
Computer Running CapTalk® S-6283Communications Software
ST Multi-mode or Vpin 62/125 or 200 Micron Optical Fiber
Connect to computer
Straight DB25Connection to ComputerRS-232 COM Port
Dymec Model No. 5843DTE = OnRepeat = Off
TX
RX
Figure 3 Fiber Optic Connection Loop
A
B
Model No. 485 LP9TBB & B ElectronicsRS-232/RS-485
120
Computer Running CapTalk® S-6283Communications Software
Connect to computer
Straight DB9 Connectionto Computer RS-232COM Port
Figure 4 RS‑485 Network Connection
–16–
M-6283 Digital Capacitor Bank Control
NetworkCAT 5 Twisted Pair RJ-45orFiber Optic ThroughST Connectors
Network Server
Computer Running CapTalk® S-6283Communications Software
Hub
Figure 5 Optional Ethernet Network Connection
RS232 Link RS232 Link
Cellular Tower
RS232 Link
Cellular Modem with TCP/IP or UDP capabilities usingstandards-based EDGE, GPRS, or CDMA technologies
Figure 6 Cellular Modem Network
–17–
M-6283 Digital Capacitor Bank Control
EnvironmentalTemperature:Controloperatesfrom–40°Cto+85°C.
NOTE: TheLCDdisplay’svisibletemperaturerangeis–20°Cto+70°C.
IEC60068-2-1Cold,–40°CIEC60068-2-2DryHeat,+80°CIEC60068-2-78DampHeat,+40°C@95%RHIEC60068-2-30DampHeatCondensingcycle25°C,+55°C@95%RH
Transient Protection
High VoltageAllinputandoutputterminalswillwithstand2000Vacrmstochassisorinstrumentgroundforoneminutewithaleakagecurrentnottoexceed25mA,forallterminalstoground.Inputandoutputcircuitsareelectricallyisolatedfromeachother,fromothercircuitsandfromground.
Surge Withstand CapabilityIEEEC37.90.1-2002 2,500VpkOscillatory 4,000VpkFastTransientBurst
IEEEC37.90.1-1989 2,500VpkOscillatory 5,000VpkFastTransient
Radiated ImmunityIEC60255-22-3 10V/M
Fast Transient/Burst ImmunityIEC60255-22-4 (4kV,5kHz)
Electrostatic DischargeIEC60255-22-2 (8kV)Pointcontactdischarge (15kV)Airdischarge
IEEEC37.90.3 (8Kv)Pointcontactdischarge (15Kv)Airdischarge
Voltage Withstand
Dielectric WithstandIEC60255-5 2,000Vacfor1minuteappliedtoeachindependentcircuittoearth 2,000Vacfor1minuteappliedbetweeneachindependentcircuit
–18–
M-6283 Digital Capacitor Bank Control
Impulse VoltageIEC60255-5 5,000Vpk,+/-polarityappliedtoeachindependentcircuittoearth 5,000Vpk,+/-polarityappliedbetweeneachindependentcircuit 1.2µsby50µs,500ohmsimpedance,threesurgesat1every5seconds
Insulation ResistanceIEC60255-5 >100Megaohms
Surge ImmunityIEC60255-22-5 4,000Vpk,+/-polarityapplied,1.2µsby50µs,2ohms/12ohmsimpedance,fivesurges1every5seconds
Voltage Interruptions ImmunityIEC60255-11
Mechanical EnvironmentIEC60255-21-1 VibrationResponseClass1 0.5g VibrationEnduranceClass11g
IEC60255-21-2 ShockResponseClass1 5g ShockWithstandClass1 15g BumpEnduranceClass1 10g
PhysicalM-6283Size:9.18"widex15"highx3.22"deep(23.32cmx12.5cmx7.95cm)
Approximate Weight:6lbs,5oz(2.92kg)
Approximate Shipping Weight:10lbs,5oz(4.56kg)est.
Patent & WarrantyTheCapacitorControliscoveredbypendingU.S.Patents.
TheCapacitorControliscoveredbyatenyearwarrantyfromdateofshipment.
BluetoothistheRegisteredTrademarkofBluetoothSIG,Inc.CapTalkistheRegisteredTrademarkofBeckwithElectricCo.,Inc.MODBUSistheRegisteredTrademarkofGould,Inc.Lexan®istheRegisteredTrademarkofGeneralElectricCo.NEMAistheRegisteredTrademarkofNationalElectricalManufacturersAssociationTroposistheRegisteredTrademarkofTroposNetworks,Inc,SpeedNetistheRegisteredTrademarkofS&CElectricCompanyUListheRegisteredTrademarkofUnderwritersLaboratories,Inc.WindowsistheRegisteredTrademarkofMicrosoftCorporationWindows2000istheRegisteredTrademarkofMicrosoftCorporation
WindowsVistaistheRegisteredTrademarkofMicrosoftCorporationWindowsXPistheRegisteredTrademarkofMicrosoftCorporation
–19–
M-6283 Digital Capacitor Bank Control
NEMA® 4X, Lexan® Meter Socket Mount Cabinet
Integrated DoorHinge With StainlessSteel Hinge Pin
External Grounding Stud
Cabinet Door AccomodatesOptional Power Supplies andCommunication Devices
Radio AntennaMounting Hole
Stainless SteelLocking Clasps
Accept up to 3/8"Hasp Locks
4, 5 or 6 BladeMeter Socket(4 Standard)
Factory CustomWiring Available
Radio AntennaMounting Hole
NEMA® 4X, Lexan® Pole Mount Cabinet
Adjustable Direct PoleMounting Bracket
Integrated DoorHinge With Stainless
Steel Hinge Pin
External Grounding Stud
Standard 5' Control Cable(Optional cable lengths in fivefoot increments up to 50 feet)
Adjustable Direct PoleMounting Bracket
Stainless Steel LockingClasps Accept up to 3/8"Hasp Locks
4, 5 or 6 BladeMeter Socket Plug
(4 Standard)Factory CustomWiring Available
Cabinet Door AccomodatesOptional Power Supplies andCommunication Devices
Radio AntennaMounting Hole
Radio AntennaMounting Hole
Figure 7 M‑6283 Digital Capacitor Control NEMA 4X Lexan Cabinet, Multiple Common Connector, Meter Socket Plug, and Meter Socket Mount
–20–
M-6283 Digital Capacitor Bank Control
15.00[12.5]
Smart Flash SD Card
S O UR C EV O LTAG E
INT
E X T
O F F
USB
RXTX
9.18[23.32]
0.65[0.17]
1.10[2.8]
1.0[2.54]
9.77[24.82]
1.0[2.54]
3.22[8.18]
0.88[2.24]
OK
OPEN ALARM
EXTERNALPOWER
METEROUT
REMOTE/ AUTO
LOCAL/ MANUAL
CLOSE REMOTE/
AUTO
LOCAL/ MANUAL
CLOSE
OPEN
NEUTRALUNBALANCE
RSSI
COM
!
Made in U.S.A.
M-6283 Three PhaseDigital Capacitor Bank Control
HTIWKCEB
CIRTCELE.CNI.OC
EXITWAKE
ENTUTIL
SETP
COMMMNTR
CNFG
Figure 8 M‑6283 Control Outline Dimensions
–21–
M-6283 Digital Capacitor Bank Control
Neutral Current Input (POL)
Capacitor Bank Close Output
Neutral
1
2
3
4
5
6
7
8
9
10
11
12
TB2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
TB1
16
1
2
3
J3RS-485 A (+)
RS-485 B (-)
RS-485 Shield
Capacitor Bank Open Output
Neutral Current Input (RTN)
Not Used
Power Input
V2
Switch Status "C" Input
Switch Status "B" Input
Switch Status "A" Input
+12 V dc Wetting Supply
Alarm Output (NO)
Alarm Output Common
Alarm Output (NC)
Factory installed Jumper that isrequired for Close/Open output
200 mA, 5 A CT, or Line PostCurrent Sensor
Optional M-2980ACabinet Door Intrusion
Detection SwitchOpen when cabinet door is openClosed when cabinet door is closed
- 12 V dc Backup Power
+ 12 V dc Backup Power
V3
V1
I3
I2
I1
Black (GND)
Red (+5 V)
White (Vo)Optional External
Temperature SensorTS
Figure 9 M‑6283 External Connections
–22–
M-6283 Digital Capacitor Bank Control
TB2
1
TB1 1 162 3 4 5 6 7 8 9 10 11 12 13 14 15
!
CLO
SE
OP
EN
NEU
TRA
L
PO
L
RTN
NEUTRALCURRENT
23456789
101112
I1I2
PO
WE
R
ALARMOUTPUT COM
NO
NC
SWITCH POWER12A 250V 3AB
TEST3A 250V 3AG
VOLTAGE0.5A 250V 3AG
TB2-1
TB2-2
TB2
Jumper TB2-1 to TB2-2
RS485OPTICFIBER
SH B ARXTX
TB1-5,6,9 140V 10ATB1-1,2,4,7 12V 0.100A
V3
V2 V1
I3
50 Hz 60 HzSENSING VOLTAGE V1
0.2A CONT.0.4A 2 HR.4.0A 1 SEC.
SENSING VOLTAGE V2
SENSING VOLTAGE V3
SENSING CURRENT I1
SENSING CURRENT I2
SENSING CURRENT I3
NONE
NONE
NONE
200 mA TB1-14, 15NEUTRAL CURRENT5.0A CONT.10.0A 2 HR.50.0A 1 SEC
5A CT TB1-14, 15
10V LINE POST TB1-11
10V LINE POST TB1-10
10V LINE POST TB1-3
10V LINE POST TB2-5
10V LINE POST TB2-4
10V LINE POST TB1-16
10V LINE POST TB1-14,15
10.0V 0.1 mVA
120V TB1-11
120V TB1-10
120V TB1-3
120V 15 mVA
TB2-6,7,8 120V 6ATB2-11,12 10-16V 5W
SW
STA
T C
SW
STA
T B
SW
STA
T A
WE
TTIN
G S
UP
.
{ +-
BUPWR
BECKWITH ELECTRIC CO., INC.6190-118th Avenue North - Largo Florida 33773-3724 U.S.A.
PHONE (727)544-2326 - FAX (727)546-0121www.beckwithelectric.com
Model: M-6283A XXXXXXXXXSoftware: ____________Ser. No. XXXXXXXXXXXXXX
Figure 10 M‑6283 Rear View
–23–
M-6283 Digital Capacitor Bank Control
M-2980A Capacitor Control Cabinet
ConstructionMoldedLexan®
• BodiesanddoorsfabricatedfrommoldedLexan
• EPDM/Neopreneclosedcellspongegasket
• Externaladjustablemountingbracket
• Integrateddoorhingewithstainlesssteelhingepin
• Enclosuredooraccommodatesoptionalpowersuppliesandcommunicationsdevices
• ExternalGroundingstudprovided
ColdRolledSteel/StainlessSteel(304)B7B346
• Bodiesanddoorsfabricatedfrom14/16gaugesteel
• Continuouslyweldedseamsgroundsmooth
• Closedcellneoprenegasket
• Externalmountingbracket
• Stainlesssteeldoorhinge
• Enclosureaccommodatesoptionalpowersuppliesandcommunicationsdevices
• ExternalGroundingstudprovided
Cabinet to Capacitor Bank Interface Type • MeterSocketMount(NotavailableforColdRolledSteelandStainlessSteelCabinets)
–Integrated4,5or6Blade(4BladeStandard)MeterSocketPlug
–StandardMeterSocketPlugwiringisavailableinfactory4,5and6Bladeconfiguration(4S,5Sand63)(Figure11)
–OptionalcustomfactoryMeterSocketPlugwiringconfigurationsavailable(Figure11)
• DirectPole-MountwithcabledMeterSocketPlug
–4,5,or6Blade(4Bladestandard)MeterSocketPlugwithstandardfivefootcontrolcable
–StandardMeterSocketPlugwiringisavailableinfactory4,5and6Bladeconfiguration(4S,5Sand63)(Figure11)
–Optionalcablelengthsavailableinfivefootincrementsupto50feet
–OptionalcustomfactoryMeterSocketPlugwiringconfigurationsavailable(Figure11)
–24–
M-6283 Digital Capacitor Bank Control
• DirectPole-MountwithCannonConnector,Integrated
–5-PinCannonConnector(5EStandard)(Figure13),CannonBulkheadShell18-11P
–8-PinCannonConnector(8AStandard)(Figure14)CannonBulkheadShell20-7P
–14-PinCannonConnector(LStandard)(Figure15)CannonBulkheadShell22-19P
–Optional8and14-Pinwiringconfigurationsavailable(Figures5and6)
• DirectPole-MountwithCannonConnector,Cabled
–5-PinCannonConnectorShell18-11P(5EStandard)(Figure13)
–8-PinCannonConnector(8AStandard)(Figure14)CannonBulkheadShell20-7P
–14-PinCannonConnector(LStandard)Figure15)CannonBulkheadShell22-19P
–Optional8and14-Pinwiringconfigurationsavailable(Figures5and6)
–Optionalcablelengthsavailableinfivefootincrementsupto50feet
• DirectPole-Mountwithcableonly,noconnector
4 Blade Selection
Config
4S
1 2 3 4
41
42
43
5 Blade Selection
1 2 3 4 5Config
5S
6 Blade Selection
Config 1 2 3 4 5 6
Meter Socket Wiring
63
67
Line Neutral OPEN CLOSE
Neutral Line OPEN CLOSE
Neutral Line CLOSE OPEN
Line Neutral CLOSE OPEN
Line Neutral OPEN CLOSE NC POL
CLOSE
CLOSE
OPEN
OPEN
Neutral
Neutral
Line
Line
NC POL
NC NC
NC RTN
1 2
3 4
1 2
3 45
1 2
5 63
4
4 Jaw Base
5 Jaw Base
6 Jaw Base
View as shown, is peering into female Meter Socket NC = Not Connected
69 CLOSEOPENNeutralLine NC NC
Figure 11 Meter Socket Wiring Configurations
M-2980A Capacitor Control Cabinet (Cont’d)
–25–
M-6283 Digital Capacitor Bank Control
PIN
A B C
NC POL NC RTN Ground
3-Pin Cannon Connector/Control Wiring
TB1-14 TB1-15 Enclosure Ground Stud
LC POL LC RTN Ground
TB2-5 TB2-4 Enclosure Ground Stud
Config
Neutral Current50:0.2 CT
Control
Line Current LinePost Sensor
Control
A B CConfig
Wire color codingdoes not apply tocontrol terminal blockwiring.
*
Wire color coding doesnot apply to controlterminal block wiring.
*
3-Pin Socket(Cabinet Side)
B-White*(LC RTN)
C-Green* orBare Wire
A-BLACK*(LC POL)
3-Pin Plug(Cabinet Side)
B-Red*(NC RTN)
C-Shield
A-BLACK*(NC POL)
LC POL - Line Current PolarityLC RTN - Load Current Return
NC POL - Neutral Current PolarityNC RTN - Neutral Current Return
Figure 12 3-Pin Cannon Plug Configurations
M-2980A Capacitor Control Cabinet (Cont’d)
–26–
M-6283 Digital Capacitor Bank Control
PIN
A B C D EConfig
5E Line Neutral CLOSE OPEN NC
5-Pin Cannon Plug/Control Wiring
TB1-9 TB1-8 TB1-5 TB1-6Control NC
5-Pin PlugC-CLOSE
D-OPEN
B-NEUTRAL
A-LINE
E-NC POL NC POL - Neutral Current Polarity
A B C D EConfig
5N Line Neutral CLOSE OPEN NC POL
TB1-9 TB1-8 TB1-5 TB1-6Control TB1-14
NC = Not Connected
Figure 13 5‑Pin Cannon Plug/Control Wiring
PIN
A B C D EConfig
8-Pin Cannon Plug/Control Wiring
8A LINE NEUTRAL CLOSE
TB1-11 TB1-8 TB1-5Control
F G
A Status
TB1-7
OPEN
TB1-6
B Status
TB1-2
H
C Status
TB1-1
Status RTN
TB1-4
A B C D EConfig
8B V1 V2 V3
TB1-11 TB1-10 TB1-3Control
F G
OPEN
TB1-6
CLOSE
TB1-5
NEUTRAL
TB1-8
H
NC NC
8 PIN PLUG
(D) Open
(C) Close
(B) Neutral
(A) Line
A Status (E)
B Status (F)
C Status (G)
Status RTN (H)
NC = Not Connected
Figure 14 8‑Pin Cannon Plug/Control Wiring
M-2980A Capacitor Control Cabinet (Cont’d)
–27–
M-6283 Digital Capacitor Bank Control
PIN
A B C D E
14-Pin Cannon Plug/Control Wiring
F G
NeutralTB1-8
NeutralTB1-8
NC POLTB1-14
V1 POLTB1-11
V3 POLTB1-3
NC RTNTB1-15
V2 POLTB1-10
H J K L M N P
V1, 2, 3 RTNTB1-8
I1 RTNTB1-8
I2 POLTB2-4
I3 RTNTB1-8
I2 RTNTB1-8
I3 POLTB1-16
I1 POLTB2-5
(A) Neutral(B) Neutral(C) NC POL
(F) V2 POL
(E) V1 POL
(D) NC RTNV1, 2, 3 RTN (H)
I3 POL (N)
(M) I2 RTN
V3 POL (G)
I3 TRN (P)
I1 POL (J)I1 RTN (K)
I2 POL (L)
14-Pin Plug
1
Figure 15 14-Pin Cannon Plug Configurations
–28–
M-6283 Digital Capacitor Bank Control
M-2980A Capacitor Control Cabinet (Cont’d)
Optional Equipment/Accessories
• Polemountbracket
• 3PhaseSensorInputOptionsInclude:
–CannonConnector,CabinetSide14-Pin,MateswithSensorInterfaceCable
–Lindsey9-587/35/R-22102,Rev.000,14PinCannontothree4PinCannonconvertercable.ConnectsB-1400toLindsey9650/E1104Sensor.
–CannonConnector-14-PinStraightPlug,FemaleThreadedCollar.AllowswiringofusercabletoconnectorwhichmateswithB-1400.IncludesMainLineConnector,CableClamp,and RubberBushing.
–SensorInterfaceCable,Includes14PinCannonconnectorononeendandun-terminatedon theother.MateswithB-1400.
–Lindsey9650/E1104Rev.000,15kVMulticoreSensor.
–Lindsey9614A/35/R-22742Rev.NS,Connectorwithcableassembly.
–30FootCableforLindseyLinePostSensor(unterminatedononeend).
–1/2"HEYCOLiquidTightCordgrip
• NeutralCurrentSensorOptionsInclude:
–50:0.2CTNeutralCurrentSensorterminatedwith3-PinCannonConnector(shellsize16)usingcustomer specified(10,20,35,or45foot)lengthofshieldedtwistedpaircable.IncludesCabinetSide Connections.
–50:0.2CTNeutralCurrentSensorwithcustomerspecified(10,20,35,or45foot)lengthof shieldedtwistedpaircable.
–CannonConnector,Cabinetside3-Pin
–CannonConnector-3-PinStraightPlug,FemaleThreadedCollar.AllowswiringofcustomercabletoconnectorwhichmateswithB-1311-1.IncludesMainLineConnector,CableClamp,andRubberBushing.
–1/2"HEYCOLiquidTightCordgrip
• AntennaCable&Bulkhead(ForInstallationwithAntennasMountingDirecttoCabinet)optionsinclude:
–TNCmaletoNfemaleweatherproofbulkheadandantennacableforlidmount(12")
–TNCmaletoNfemaleweatherproofbulkheadandantennacableforcabinetmount(36")
–SMAmaletoNfemaleweatherproofbulkheadandantennacableforlidmount(12")
–SMAmaletoNfemaleweatherproofbulkheadandantennacableforcabinetmount(36")
–Double-DHolefor"N"ConnectionsinLocation1,2,3,or4ofCabinettoaccommodateAntennaExit.
–29–
M-6283 Digital Capacitor Bank Control
M-2980A Capacitor Control Cabinet (Cont’d)
Optional Equipment/Accessories (Cont.’d)
• LightningProtection(Forinstallationswithexternalantennas)optionsinclude:
– DSXL PolyPhaser Lightning Arrestor 700MHz - 2.7GHz N Female protected side, N FemaleBulkheadantennaside
–AL-LSXMPolyphaserLightningArrestor2GHz to6GHzNFemaleprotectedside,NFemaleBulkheadantennaside
–SMAmaletoNmaleantennacabletoconnectlightningprotectiontoaradioforcabinetmount(36")
–TNCmaletoNmaleantennacabletoconnectlightningprotectiontoaradioforcabinetmount(36")
–NmaletoNmaleantennacabletoconnectLightningProtectiontoaRadioforcabinetmount(36")
• Antennas:
– Laird FG9023, 902 MHz to 928 MHz, 3 dBi gain, fiberglass Omni-Directional antenna,NFemaleconnector
–FM2,antennaPoleMountBracketforLairdfiberglassantennas
– Laird TRAB9023NP, 902 MHz to 928 MHz, 3 dBi gain, Omni-Directional Phantom antenna,NFemalebulkheadconnector
–LairdTRAB806/1703P,Multi-Band(806MHzto2.5GHz),3dBiGain,Omni-DirectionalPhantomAntenna,NFemaleBulkheadConnector.InstalledinHoleLocation2ofCabinet
– TNC male to N male antenna cable to connect antennas with an integrated bulkhead to aradioforcabinetmount(36")
–NmaletoNmaleantennacabletoconnectLightningProtectiontoaRadio.Forcabinetmount(36")
• RadioOptionsInclude:
2 Way VHF (154 MHz) radio
–Radius
2 Way (130 MHz - 3.7 GHz) radio modems:
–SilverSpringsNetworksSSNebridgeandsbridge
–MDSINET900AP
–MDSINETII
–MDSSD9
–MDSX710
–MDSSD4
–MDS9810
–MDSTransNET
–MDSMercury3650and900
–MDSentraNET900and2400
–CellNetSeriesIII
–S&CSpeedNet™
–30–
M-6283 Digital Capacitor Bank Control
M-2980A Capacitor Control Cabinet (Cont’d)
Optional Equipment/Accessories (Cont.’d)
Digital Cellular Modems:
–SixnetBTseriesMobilityPro/industrialProGateways
–MultitechMultimodemseriesroutersandmodems
–AirLinkRavenII,X,XE,XT
–TelemetricsDNPRTMII
–ZyWAN3G/GPRS/GSM
Wireless Routers:
–TroposMeshRouter7320
• Radioreadyoptionsinclude:
–UniversalRadioBracket
–UniversalRadioBracketwith12VdcpowerSupply
–UniversalRadioBracketwith24VdcpowerSupply
–UniversalRadioBracketwithcustomersuppliedpowersupplyinstalled
• RadioInstallation:
–CustomersuppliedradiomountedandInstalledtoM-2980A
• RS-232RadioCommCable-30"length,MaletoMale,straightthrough.GoesfromM-6283ControltoRadio'sDB9Port.
• RS-232RadioCommCable-33"length,MaletoFemale,nullmodem.GoesfromM-6283ControltoRadio'sDB9Port.
• EthernetRadioCommCable-24"length.ConnectsM-6283Controltoradio’sRJ45Port.
• UniversalPowerCableprovidesfused120VACtopoweraradiopowersupply(Includedonallradiobrackets)
• DB9toDB25-RS-232CableConverter
• 1/2"HEYCOLiquidTightCordgriptosecurecablecomingintocabinet.
• UniversalRadio/ModemBracket(ForfieldmountinginthedooroftheM-6283)
• 12VdcPowerSupplyforradio
• 25footNmaletoNmaleLMR-400antennaextensioncable.
• Externaltemperaturesensor
• CannonConnector-5-PinStraightPlug,Femalethreadedcollar.AllowswiringofcustomercabletoconnectorwhichmateswithIntegrated5-PinCannonConnectorforInterface.IncludesMainLineConnector,CableClamp,andRubberBushing.
• CannonConnector-8-PinStraightPlug,Femalethreadedcollar.AllowswiringofcustomercabletoconnectorwhichmateswithIntegrated8-PinCannonConnectorforInterface.IncludesMainLineConnector,CableClamp,andRubberBushing.
• CannonInterfaceCable-5Pincannonconnectorwithspecifiedlengthofcablewithunterminatedend.
• IntrusionDetectionMicroswitch-TheM-2980Acabinetdoorintrusiondetectionmicroswitch(Figure9)status(Close/OpenCondition)ismonitoredbytheM-6283.IfanOpenConditionisdetected,aDNPbinary inputpoint for intrusiondetectionwillbesetandwillgenerateaDNPevent.TheintrusiondetectionwillalsobemonitoredusingMODBUSregister1791@bit3.
–31–
M-6283 Digital Capacitor Bank Control
PhysicalMolded Lexan® Cabinet
Size:18.38"highx12.43"widex7.81"deep(46.7cmx31.6cmx19.84cm)
Approximate Weight:10lbs,8oz(4.76kg)
Approximate Shipping Weight:12lbs(5.44kg)
Approximate Weight with M-6280A Digital Capacitor Bank Control:18lbs(8.17kg)
Approximate Shipping Weight with M-6280A:21lbs,8oz(9.75kg)
Cold Rolled Steel/Stainless Steel (304)B7B346
Size:21.3"highx11.12"widex7.71"deep(54.1cmx28.25cmx19.58cm)
Approximate Weight:15lbs,8oz(7.03kg)
Approximate Shipping Weight:23lbs(10.4kg)
Approximate Weight with M-6280A Digital Capacitor Bank Control:22lbs,8oz(10.21kg)
Approximate Shipping Weight with M-6280A:35lbs(15.88kg)
WarrantyTheM-2980AWeatherproofCapacitorControlCabinetiscoveredbyafiveyearwarrantyfromdateofshipment.Thirdpartymountedoptionswillcarrytheirrespectivemanufacturer’swarranty,passedalongthroughBeckwithElectric.
Specification subject to change without notice.
800-6283-SP-01 03/13©2008BeckwithElectricCo.AllRightsReserved.PrintedinU.S.A.(09.24.02)