Post on 29-Jan-2021
Viega Megapress
Data sheet
INFO!Other documents (e.g. certificates) refer with the number 566 320 to this Megapress data sheet.
Contents
SYSTEM DESCRIPTION ________________ 4Intended use _________________________________ 4
Technical data ________________________________ 5
Megapress press connector ___________________ 7
Megapress S press connector _________________ 8
Megapress press-in branch connector ________ 11
MOUNTING _________________________ 12Press tools __________________________________ 12
Fire extinguisher and sprinkler systems _______ 14
Pipe overview _______________________________ 15
Examples ___________________________________22
Commissioning ______________________________26
Creation of the press connection up to 2 inches _26
Creation of the press connection 2 ½ to 4 inches _____________________________________29
Space requirement during pressing ___________32
Length expansion – Expansion equalisation joints/expansion bends ______________________36
TABLES – PIPE EQUIVALENTS _________ 38Inquiry regarding material durability __________45
SYSTEM DESCRIPTION
Intended useThe Megapress/Megapress S system is suitable for the installation of heat-ing, cooling, and industrial systems in connection with steel pipes according to (see pipe overview):
■ DIN EN 10255 ■ DIN EN 10220 / DIN EN 10216-1 ■ DIN EN 10220 / DIN EN 10217-1
Furthermore, Megapress can be used in sprinkler systems according to VdS CEA 4001 and the specifications according to the respective approval G 414021. In addition to this information, the section "Fire extinguishing systems" must be noted.
The Megapress system is not suitable ■ for use in potable water installations and other open systems – Compo-nents must be marked with symbol "Not for potable water installations"
■ for fuel gases acc. to DVGW worksheet G 260 ■ for local and district heating pipelines in the soil
Megapress connectors may only be used with components that belong to the system.The use of the system for applications other than those described must be approved by the Viega Service Center.Press connectors leak visibly when not pressed. Do a leakage test before commissioning.
Operating conditions ■ Water, closed system
■ Operating temperature Tmax ≤ 110 °C (EPDM) ■ Operating temperature Tmax ≤ 140 °C (FKM) ■ Operating pressure pmax ≤ 1.6 MPa (16 bar)
■ Compressed air, dry and oil-free ■ Operating pressure pmax ≤ 1.6 MPa (16 bar)
Fig. 1: Megapress / Megapress S product selection (⅜–2 inches)
Megapress data sheet
4
Technical dataSteel pipes – seamless and with seam heat sealing: black, galvanised, indus-trially painted or powder-coated according to
■ DIN EN 10255 ■ DIN EN 10220 / DIN EN 10216-1 ■ DIN EN 10220 / DIN EN 10217-1
For use in sprinkler systems according to VdS CEA 4001, the following pipe wall thicknesses must be observed:
inch (DN) Minimum pipe wall thick-ness (acc. to VdS CEA 4001 Table 15.02)
Maximum pipe wall thicknesses
≤ D2 (DN50) 2.6 mm 3.3 mmD2½ (DN65) 2.6 mm 4.5 mmD3 (DN80) 2.9 mm 5.0 mmD4 (DN100) 3.2 mm 5.4 mm
Tab. 1: Pipe wall thicknesses for use in sprinkler systems
Non-alloyed steel, material 1.0308, exterior with high-quality zinc-nickel coating 3–5 µm
EPDM profile sealing element, for Tmax ≤ 110°C and pmax ≤ 1.6 MPaFKM round sealing element, for Tmax ≤ 140°C and pmax ≤ 1.6 MPa
Standard size XL sizes Intermediate sizes (not VdS tested)
D⅜ (DN10) * D2½ (DN65) 38.0 mm (DN32) *D½ (DN15) * D3 (DN80) 44.5 mm (DN40) *D¾ (DN20) D4 (DN100) 57.0 mm (DN50) *D1 (DN25)D1¼ (DN32)D1½ (DN40)D2 (DN50)* not VdS tested
Tab. 2: Available dimensions
www.viega.com/en/products/Catalogue/Piping-technology/ Megapress.html
VdS – For sprinklers wet, dry, and wet /dry (except models 4211.3, 4212.2, 4213.2, 4215.4, 4215.7, 4259.1, 4259.1XL, 4259.6XL, 4312.2, 4312.7, 4359.1 and 4359.6); TÜV; shipbuilding; various country approvals
Press connectors
Sealing element
Dimensions
Z dimensions
Certification
System description | Technical data
5
Fig. 2: Megapress S XL product selection (2½–4 inches)
Areas of useReplacement for welded and threaded connectors in new installations and repairs
■ Closed heating and cooling circuits ■ Industrial units – nitrogen etc. ■ Compressed air systems ■ Fire extinguisher and sprinkler systems ■ Systems for technical gases (on request) ■ Local and district heating system as per AGFW FW 524 (with Megapress S up to 2 inches / DN50)
Features / benefits ■ Fast processing without handling of gas cylinders or thread cutting ma-chines
■ No fire hazard, no smoke emissions, damage, fire guards, cooling pha-ses
■ Zinc-nickel coating 3–5 µm – corrosion resistant, long service life ■ Special !sealing elements for rough pipe surfaces
Transition to other piping systemsThe product portfolio comprises different adapters for the transition to other systems, e.g. to Prestabo or groove systems as well as the special Megapress adapter for potable water (cold) made of silicon bronze.
Megapress data sheet
6
Megapress press connectors Megapress press connectors up to 2 inches are equipped with specifically designed EPDM profile sealing elements. Integrally moulded sealing lips with several sealing levels reliably seal pipe surfaces, even those with slightly uneven surfaces or grooves. The Megapress press connectors are labelled with a black dot.
Fig. 3: Megapress press connector up to 2 inches
Fig. 4: Megapress profile sealing ele-ment up to 2 inches
1. Profile sealing element2. Cutting ring3. Separator ring
Fig. 5: Megapress press connectors
System description | Meeapress press connectors
7
Megapress S press connectorsAll Megapress S press connectors are fitted with FKM sealing elements. In the dimensions of ⅜ to 2 inches, the press connectors include a round seal-ing element and a reinforced separator ring.The XL press connectors in the dimensions 2½, 3 and 4 inches are equipped with round sealing elements with an increased cord thickness. Given their design, the Megapress S press connectors have the same sealing properties as the Megapress press connectors and therefore do not require a profile. All Megapress S press connectors are labelled with a white dot. In addition, the imprint "FKM" refers to the installed sealing element.
Fig. 6: Megapress S press connector up to 2 inches
Fig. 7: Megapress S sealing element up to 2 inches
Fig. 8: Megapress S XL press connector from 2½ inches
Fig. 9: Megapress S XL sealing element from 2½ inches
Megapress data sheet
8
Press connectors – leaking when unpressedAll Megapress/Megapress S press connectors are leaking when not pressed.The "leaking when not pressed" function is clearly marked by a black dot at the bead.
Viega guarantees that accidentally unpressed connections become visible during a leakage test:
■ with the wet leakage test in the pressure range from 0.1–0.65 MPa (1.0–6.5 bar)
■ with the dry leakage test in the pressure range from 22 hPa–0.3 MPa (22 mbar–3.0 bar)
Fig. 10: Unpressed press connection (⅜–2 inches)
Fig. 11: Unpressed press connection (2½–4 inches)
The Megapress sliding couplings have no internal limit stop. For this reason, they are used mostly for repairing defective pipeline sections or for system extensions – e.g. for installing T-pieces in narrow spaces.
Fig. 12: Megapress sliding coupling (model 4215.5)
Fig. 13: Megapress sliding coupling (model 4215.4 – not VdS tested)
Repairs and system extensions
System description | Meeapress S press connectors
9
Megapress for steel pipes with 38.0 mm, 44.5 mm and 57.0 mm external diameterThe special Megapress adapters/reducing sleeves (not VdS tested) provide a fast transition to steel pipes of intermediate sizes with 38.0 mm, 44.5 mm and 57.0 mm external diameter. These press connectors can be pressed with the existing Megapress press tools (see Tab. 4 on page 13).
Fig. 14: Megapress (model 4211.3) Fig. 15: Megapress (model 4215.7)
Special Megapress transition for potable water (cold)The Megapress adapter model 4213.2 offers a simple means of connecting galvanised steel piping (Zinc plating in acc. with DIN EN 10240) directly to the Profipress, Sanpress and Sanpress Inox systems. The model has been approved according to DVGW Worksheet W 534 and is available in the sizes ½ inch x 15 mm up to 2 inch x 54 mm.In addition to the Megapress areas of application (except fire extinguishing and sprinkler systems), the model can also be used in potable water pipe-lines (cold).For installation, the flow rule must be observed.
Fig. 16: Megapress (model 4213.2)
Megapress data sheet
10
Megapress / Megapress S press-in branch connectorThe Megapress press-in branch connectors (with EPDM or FKM sealing elements) can be used to make connections subsequently in unpressurised steel pipe installations (1½, 2, 2½, 3, 4, 5 and 6 inch).By means of the respective tool set, a hole is drilled in the steel piping, and the Megapress press-in branch connector is then pressed in. This makes it possible for example to mount a thermometer quickly and without labour-in-tensive preparations to an existing steel pipe installation. The system will be operational immediately afterwards.
Making a threaded connection in just four steps
Fig. 17: A special drilling device for guiding the drilling shaft is fastened to the steel pipe (1½ to 6 inches) by means of ring or fork spanner.
Fig. 18: The hole is drilled by means of a commercially available drilling machi-ne. The steel chips can be extracted by means of the vacuum cleaner nozzle. Af-terwards, remove the drilling device again.
Fig. 19: Press the press-in branch con-nector to the steel pipe by means of the press machine and the positioning aid. This is a fast and clean way of making the connection to the pipeline.
Fig. 20: The steel pipe connection Rp ¾ for thermometers, temperature sensors, manometers, drains or line connections is completed.
For subsequent connections in steel pipe installa-tions
Megapress press-in branch connec-tor with internal thread Rp ¾
For detailed infor-mation on the areas of application, media, and suitable press machines, refer to the Viega instructions for use 573 184.
System description | Meeapress / Meeapress S presssin ranch connector
11
MOUNTING
Press tools Megapress press connectors are pressed with special press jaws/press rings. The press rings / press jaws of the metal Viega press connector sys-tems Profipress, Sanpress, Sanpress Inox, and Prestabo cannot be used.Viega recommends using Viega press jaws, press rings and hinged adapter jaws according to Tab. 3.
Fig. 21: Megapress press tool up to 2 inches
Fig. 22: Megapress XL press tool of 2½ inches and up
Use the press tools dedicated to the system!
Megapress press tools
Megapress data sheet
12
Press machines Press jaws Press rings Set
Type 2PT 3 AH / EHPressgun 4 / 5
DN10 to DN25Model 4299.9
DN15 model 4296.1, with hinged adapter jaw Z1 model 2296.2
Press jawsDN15 to DN25Press ringsDN32 to DN50 Hinged adapter jaw Z2Model 4299.61
DN 32 to DN 50 model 4296.1, with hinged adapter jaw Z2 model 2296.2
Type 2PT 3 EHPressgun 4 / 5
–
DN 65 to DN 100 model 4296.1XL, with Pressgun Press Booster mod-el 4296.4XL
Press ring DN65 and Pressgun Pressgun Press Booster model 4296.2XLPress ringsDN80 and DN100Model 4296.5XL
PiccoPressgun Picco
DN 10 and DN 15 model 4284.9
DN15 model 4296.1, with hinged adapter jaw P1 model 2496.1
–
Tab. 3: Press tools – For Megapress press connectors
Press tools for intermediate sizes (38.0 mm, 44.5 mm and 57 mm)The Megapress press connectors for the intermediate sizes are pressed with standard Megapress press rings.
External diameter Press rings
38.0 mmDN32 (1¼ inches)Model 4296.1 with hinged adapter jaw Z2Model 2296.2
44.5 mmDN40 (1½ inches)Model 4296.1 with hinged adapter jaw Z2Model 2296.2
57.0 mmDN50 (2 inches)Model 4296.1 with hinged adapter jaw Z2Model 2296.2
Tab. 4: Press tools for intermediate sizes (38.0 mm, 44.5 mm and 57 mm)
Mountine | Press tools
13
Transport and storage / General notes on mountingTo guarantee the high quality of the Megapress system components, the following notes must be observed.
■ Do not remove the Megapress system components from the packaging until immediately before use.
■ Only use commercially available chloride-free sealants to seal the threads of the adapters to Viega press connections.
■ When mounting components or pipeline sections with combined thread and press connections, always make the thread connection first.
■ Always comply with the applicable accident prevention regulations (e.g. wear personal protective equipment).
Fire extinguisher and sprinkler systemsFor fire extinguishers and sprinkler systems, the following requirements must be observed:
■ VdS CEA 4001 ■ Requirements and advisory notes in the respective VdS approval ■ Country-specific requirements and regulations (e.g. DIN 14462) ■ Tab. 5
Only black, galvanised or powder-coated steel pipes in acc. with the condi-tions of the VdS approval G 414021 are permitted in VdS conform sprinkler systems acc. to CEA 4001. For application in sprinkler systems according to VdS CEA 4001, the pipe wall thicknesses according to Table 5 must be observed. The distances and layout (bracket distances) for steel pipes acc. to VdS CEA 4001 Section 15.2 apply.
This section does not apply for the Megapress press-in branch connec-tors and the models excepted on page 5
Permitted pressure ≤ DN 65 1.6 MPa; DN 80 1.25 MPa; DN 100 1.0 MPaNominal widths DN20 to DN100 (exception: 38,0 mm, 44.5 mm and 57.0 mm)Pipe wall thicknesses
inch (DN)Minimum pipe wall thick-ness (acc. to VdS CEA 4001 Table 15.02)
Maximum pipe wall thick-nesses
≤ D2 (DN50) 2.6 mm 3.3 mmD2½ (DN65) 2.6 mm 4.5 mmD3 (DN80) 2.9 mm 5.0 mmD4 (DN100) 3.2 mm 5.4 mm
Area of use (pipeline network)
Sprinkler wet systems: pipeline network downstream of the alarm valve stationSprinkler dry systems: pipeline network downstream of the alarm valve station
Fixing intervals In compliance with the regulations in VdS CEA 4001 section 15.2Firefighting water additive
Generally not permitted; exceptions only with the manufacturer's permission and prior agreement of the VdS
Tab. 5: Permitted pressure, nominal width and conditions of use on the basis of Table A.1 acc. to VdS 2100-26-2: 2012-04
Megapress data sheet
14
All of the fire hazard classes in acc. with VdS CEA 4001 are covered by Megapress:
■ Fire hazard class LH (light hazard) ■ Fire hazard class OH 1–4 (ordinary hazard) ■ Fire hazard class HHP 1–4 (extra hazard, production risks) ■ Fire hazard class HHS 1–4 (extra hazard, storage risks)
Pipe overview Megapress can be used to connect different steel pipes – such as black, galvanised, industrially painted, or coated pipes – in sizes ⅜ to 4 inches.
DIN EN 10255Standard DIN EN 10255 differentiates between heavy pipe series H and me-dium pipe series M, and between pipe type L, L1 and L2. The different pipe series and pipe types comprise seamless pipes (S) and pipes welded along the longitudinal seam (W).
Steel pipes for Megapress / Megapress S press connectors
DIN EN 10255 – Threaded pipe quality – Heavy series H and Medium series M
Thread size
[Inch]
Nominal width
[DN]
Nominal external diameter[mm]
External diameter incl. coating
Pipe wall thicknessHeavy series H[mm]
Medium series M[mm]
min. [mm]
max.[mm]
⅜ 10 17,2 16,7 17,5 2,9 2,3½ 15 21,3 21,0 21,8 3,2 2,6¾ 20 26,9 26,5 27,3 3,2 2,61 25 33,7 33,3 34,2 4,0 3,21¼ 32 42,4 42,0 42,9 4,0 3,21½ 40 48,3 47,9 48,8 4,0 3,22 50 60,3 59,7 60,8 4,5 3,62½ 65 76,1 75,3 76,6 4,5 3,63 80 88,9 88,0 89,5 5,0 4,04 100 114,3 113,1 115,0 5,4 4,5
Tab. 6: DIN EN 10255 – Threaded pipe quality – Heavy series H and Medium series M
Mountine | Pipe overview
15
DIN EN 10255 – Threaded pipe quality – pipe type L
Thread size
[Inch]
Nominal width
[DN]
Nominal external diameter[mm]
External diameter incl. coating
Pipe wall thickness
[mm]min.[mm]
max.[mm]
⅜ 10 17,2 16,7 17,4 2,0½ 15 21,3 21,0 21,7 2,3¾ 20 26,9 26,4 27,1 2,31 25 33,7 33,2 34,0 2,91¼ 32 42,4 41,9 42,7 2,91½ 40 48,3 47,8 48,6 2,92 50 60,3 59,6 60,7 3,22½ 65 76,1 75,2 76,0 3,23 80 88,9 87,9 88,7 3,24 100 114,3 113,0 113,9 3,6
Tab. 7: DIN EN 10255 – Threaded pipe quality – pipe type L
DIN EN 10255 – Threaded pipe quality – pipe type L1
Thread size
[Inch]
Nominal width
[DN]
Nominal exter-nal diameter
[mm]
External diameter incl. coating
Pipe wall thickness
[mm]min.[mm]
max.[mm]
⅜ 10 17,2 16,7 17,4 2,0½ 15 21,3 21,0 21,7 2,3¾ 20 26,9 26,4 27,1 2,31 25 33,7 33,2 34,0 2,91¼ 32 42,4 41,9 42,7 2,91½ 40 48,3 47,8 48,6 2,92 50 60,3 59,6 60,7 3,22½ 65 76,1 75,2 76,3 3,23 80 88,9 87,9 89,4 3,64 100 114,3 113,0 114,9 4,0
Tab. 8: DIN EN 10255 – Threaded pipe quality – pipe type L1
Megapress data sheet
16
DIN EN 10255 – Threaded pipe quality – pipe type L2
Thread size
[Inch]
Nominal width
[DN]
Nominal external diameter[mm]
External diameter incl. coating
Pipe wall thickness
[mm]min.[mm]
max.[mm]
⅜ 10 17,2 16,7 17,1 1,8½ 15 21,3 21,0 21,4 2,0¾ 20 26,9 26,4 26,9 2,31 25 33,7 33,2 33,8 2,61¼ 32 42,4 41,9 42,5 2,61½ 40 48,3 47,8 48,4 2,92 50 60,3 59,6 60,2 2,92½ 65 76,1 75,2 76,0 3,23 80 88,9 87,9 88,7 3,24 100 114,3 113,0 113,9 3,6
Tab. 9: DIN EN 10255 – Threaded pipe quality – pipe type L2
Steel pipes for Megapress press-in branch connector Rp ¾
Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 – Heavy series H and Medium series M
Press-in branch connectorArt. no.
For pipe dimensions
[Inch]
Nominal external diameter [mm]
External diameter Pipe wall thicknessmin.
[mm]
max.
[mm]
Heavy series H [mm]
Medium series M [mm]
731 168 1½ 48,3 47,9 48,8 4,0 3,2731 175 2 60,3 59,7 60,8 4,5 3,6731 182 2½ 76,1 75,3 76,6 4,5 3,6731 199 3 88,9 88,0 89,5 5,0 4,0731 205 4 114,3 113,1 115,0 5,4 4,5731 212 5 139,7 138,5 140,8 5,4 5,0731 229 6 165,1 163,9 166,5 5,4 5,0
Tab. 10: Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 – Heavy
series H and Medium series M
Mountine | Pipe overview
17
Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 – pipe type L
Press-in branch connectorArt. no.
For pipe dimensions
[Inch]
Nominal external diameter[mm]
External diameter Pipe wall thick-ness
[mm]
min.
[mm]
max.
[mm]731 168 1½ 48,3 47,8 48,6 2,9731 175 2 60,3 59,6 60,7 3,2731 182 2½ 76,1 75,2 76,0 3,2731 199 3 88,9 87,9 88,7 3,2731 205 4 114,3 113,0 113,9 3,6731 212 5 139,7 138,5 140,8 4,5731 229 6 165,1 163,9 166,5 4,5
Tab. 11: Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 – pipe type L
Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 pipe type L1
Press-in branch connectorArt. no.
For pipe dimensions
[Inch]
Nominal exter-nal diameter
[mm]
External diameter Pipe wall thickness
[mm]
min.
[mm]
max.
[mm]731 168 1½ 48,3 47,8 48,6 2,9731 175 2 60,3 59,6 60,7 3,2731 182 2½ 76,1 75,2 76,3 3,2731 199 3 88,9 87,9 89,4 3,6731 205 4 114,3 113,0 114,9 4,0
Tab. 12: Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 pipe type L1
Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 pipe type L2
Press-in branch connectorArt. no.
For pipe dimensions
[Inch]
Nominal exter-nal diameter
[mm]
External diameter Pipe wall thickness
[mm]
min.
[mm]
max.
[mm]731 168 1½ 48,3 47,8 48,4 2,9731 175 2 60,3 59,6 60,2 2,9731 182 2½ 76,1 75,2 76,0 3,2731 199 3 88,9 87,9 88,7 3,2731 205 4 114,3 113,0 113,9 3,6
Tab. 13: Press-in branch connector for steel pipe – threaded pipe quality DIN EN 10255 pipe type L2
Megapress data sheet
18
DIN EN 10220 / DIN EN 10216-1 and DIN EN 10220 / DIN EN 10217-1 DIN EN 10220 differentiates between pipe series 1, 2 and 3.The standard recommends using installation pipes of pipe series 1 as pipe series 2 and 3 are either not or not always available in practice.Pipe series 1 comprises seamless pipes (S) and pipes welded along the longitudinal seam (W).
Steel pipes for Megapress / Megapress S press connectors
DIN EN 10220 / DIN EN 10216-1, DIN EN 10220 / DIN EN 10217-1 Boiler pipe quality – pipe series 1, 2, and 3
Thread size
[Inch]
Nominal width
[DN]
Nominal exter-nal diameter
[mm]
External diameter incl. coating
Pipe wall thick-ness
[mm]min.[mm]
max.[mm]
⅜ 10 17,2 16,7 17,7 from 1.4 to 4.5½ 15 21,3 21,0 21,8 from 1.4 to 5.0¾ 20 26,9 26,5 27,3 from 1.4 to 8.01 25 33,7 33,3 34,2 from 1.4 to 8.8- 32 38,0 37,5 38,5 from 1.4 to 10.01¼ 32 42,4 42,0 42,9 from 1.4 to 10.0- 40 44,5 44,0 45,0 from 1.4 to 12.51½ 40 48,3 47,9 48,8 from 1.4 to 12.5- 50 57,0 56,4 57,6 from 1.4 to 14.22 50 60,3 59,7 60,9 from 1.4 to 16.02½ 65 76,1 75,3 76,9 from 1.4 to 20.03 80 88,9 88,0 89,8 from 1.4 to 25.04 100 114,3 113,2 115,4 from 1.4 to 32.0
Tab. 14: DIN EN 10220 / DIN EN 10216-1, DIN EN 10220 / DIN EN 10217-1 Boiler pipe quality – pipe series 1, 2, and 3
Mountine | Pipe overview
19
Steel pipes for Megapress press-in branch connector Rp ¾
DIN EN 10220 / DIN EN 10216-1, DIN EN 10220 / DIN EN 10217-1 Boiler pipe quality – pipe series 1
Press-in branch connectorArt. no.
For pipe dimen-sions[Inch]
Nominal external diameter[mm]
External diameter Pipe wall thick-ness
min.[mm]
max.[mm]
min.[mm]
max.[mm]
731 168 1½ 48,3 47,9 48,8 2,3 4,0731 175 2 60,3 59,7 60,9 2,3 4,5731 182 2½ 76,1 75,3 76,9 2,6 4,5731 199 3 88,9 88,0 89,8 2,6 5,0731 205 4 114,3 113,2 115,4 2,6 5,4731 212 5 139,7 138,5 140,8 2,9 5,4731 229 6 168,3 166,6 170,0 2,9 5,4
Tab. 15: DIN EN 10220 / DIN EN 10216-1, DIN EN 10220 / DIN EN 10217-1 Boiler pipe quality – pipe series 1
Cut to lengthUnder consideration of the pipe coating, the steel pipes can be cut with the following tools:
■ pipe cutter ■ fine-toothed saw ■ chopsaw – low cutting speed ■ angle-grinder
After cutting, deburr the inside and outside of the pipes.
Preparing the pipe ends for the press connectionThe Megapress system is suitable for use with black, galvanised, industrially painted, or powder-coated steel pipes.As a precondition for making technically faultless press connections, the pipes must be free of damage and deformations and the pipe ends must be sufficiently smooth and clean, as well as free of loose dirt and rust particles.
Cutting steel pipes to length
Requirement of smooth, clean, and non-deformed pipe surfaces
Megapress data sheet
20
Requirements in pipe ends ■ Correctly cut to length ■ Inside and outside of pipe wall free of burrs ■ Cross section round, without deformations, e.g. caused by vices ■ The minimum distance to welding seams and bending points must be 3 x D – however at least 100 mm
■ For the installation of Megapress press connectors, the maximum exter-nal diameter of the installation pipe (incl. coating) according to Tab. 6 to Tab. 9 and Tab. 14 must not be exceeded.
■ For the installation of Megapress press connectors, the minimum exter-nal diameter of the installation pipe must not fall below the value speci-fied in Tab. 6 to Tab. 9 and Tab. 14.
Requirements in pipe surfaces ■ Smooth and even – without damage from vices or thread cutters or similar ■ If the pipe has an industrially applied coating, the coating must not be damaged when cutting the pipe (e.g. pipe cutter). Damaged or scratched coating must be previously removed in the area of the insertion depth.
■ Free of grease and oil ■ Free of loose dirt and rust particles and unevenly (manually) applied coats ■ For the Megapress press-in branch connector, the thickness of the coat on the installation pipe must not exceed 300 µm for industrially painted pipes.
NOTE!Do not press on embossed pipe markings.
Mountine | Pipe overview
21
ExamplesAs long as they are free from dirt, smooth, firm, even and undamaged, the following pipe surfaces are suitable for the production of press connections without further treatment:1. Black pipes2. Galvanised pipes3. Industrially painted / powder-coated pipes
Fig. 23: Black, uncoated Fig. 24: Galvanised
Fig. 25: Powder-coated
Megapress data sheet
22
Before making the press connections, pipe surfaces must be treated around the press connections (Fig. 26 and Fig. 27) if they exhibit the following char-acteristics:
■ Unevenly applied layers of paint (Fig. 26) ■ Excessive coat thickness on the pipe (mounting without force not possi-ble any more), max. external diameter according to Tab. 6 to Tab. 9 and Tab. 14 exceeded
■ Bumps, damage, grooves, corrosion or loose adhesions (Fig. 27)
Fig. 26: Uneven, painted Fig. 27: Corroded
■ Do not press on embossed pipe markings (Fig. 28)
Fig. 28: Embossed
Mountine | Examples
23
The following are examples of suitable tools for the work: ■ Wire brush (Fig. 29) ■ Cleaning fleece/sanding paper (Fig. 30) ■ Angle grinder with serrated washer (Fig. 31)
Fig. 29: Wire brush treatment Fig. 30: Cleaning fleece/sanding paper treatment
Fig. 31: Angle grinder treatment Fig. 32: Treated pipe surface
After the treatment, the quality of the pipe surface should be as shown in Fig. 32.The external diameter of the installation pipe must not fall below the minimum value specified in Tab. 6 to Tab. 9 and in Tab. 14.
Megapress data sheet
24
Corrosion protection/coatIn systems where complete corrosion protection is required (e.g. cooling sys-tems), parts of the processed pipe surface that are uncovered after pressing must subsequently have suitable corrosion protection applied.
Pipe fastenerThe general rules of fixing technology apply, e.g.
■ No further pipelines must be attached to existing pipeline installations. ■ Use of pipe hooks is not permitted. ■ Consider the thermal expansion – plan for fixed and gliding points.
Ø external
[mm]
Nominal width fixing interval [m]
[DN] [Inch]Acc. to manufac-turer's information
acc. to VdS CEA 4001
17,2 10 ⅜ 2,25-
21,3 15 ½ 2,7526,9 20 ¾ 3,00
4,00
33,7 25 1 3,5042,4 32 1 ¼ 3,7548,3 40 1 ½ 4,2560,3 50 2 4,7576,1 65 2 ½ 5,5088,9 80 3 6,00114,3 100 4 6,00
Tab. 16: Fixing table
Protection against external corrosion/insulationA high-quality zinc-nickel coating protects the press connectors optimally against corrosion – e.g. when condensation water forms in cooling systems.The pipes must be equipped with suitable corrosion protection; observe the manufacturer's information.Pipes and press connectors must be insulated according to the generally recognised rules of engineering.Use halogen-free insulation.
Mountine | Examples
25
CommissioningA pressure test must be carried out before commissioning the system, the results thereof must be documented.Procedure:
■ Completely fill the system with the test medium, such as inert gases / filtered potable water. If the system is not put into operation immedia-tely after the pressure test, carry out a pressure test with oil-free com-pressed air/inert gases.
■ Perform the pressure test according to the generally recognised rules of engineering – in sprinkler systems note VdS CEA 4001, section 17.
■ Document the results of the pressure test in a log. ■ Have an authorized expert sign the log and provide it to the customer.
Creation of the press connection up to 2 inches
Fig. 33: Cut the steel pipe properly and at a right angle using a pipe cutter, angle grinder or fine-toothed hacksaw. Do not use a flame cutter.
Fig. 34: Proceed with caution when clamping the pipe – avoid deformation of the pipe end.
Megapress data sheet
26
Fig. 35: Use a deburrer to deburr the inside and outside of the pipe – up to DN40 use model 2292.2, for DN50 use model 2292.4 XL
Fig. 36: With the help of a wire brush, sanding paper or an angle grinder with a fan washer, remove loose dirt and rust particles from the pressing area.
Fig. 37: Ensure the proper seat of sealing element, separator ring and cutting ring.
Fig. 38: Measure the insertion depth and mark it on the pipe.
Mountine | Creation of the press connection up to 2 inches
27
Fig. 39: Push the press connector onto the pipe as far as it will go. Do not tilt the press connector.
Fig. 40: Place the Megapress press jaw (≤ DN 25) around the press connector. Ensure that it is properly fitted. Carry out the pressing until the press jaw is completely closed.
Fig. 41: Place the Megapress press ring around the press connector. Ensure that it is properly fitted. Carry out the pres-sing using the hinged adapter jaw until the press ring is completely closed.
Fig. 42: Remove the control label to mark the press connector as "pressed". Following installation, check that the insertion depth is correct.
Megapress data sheet
28
Creation of the press connection 2 ½ to 4 inches
Fig. 43: Cut the steel pipe properly and at a right angle using a pipe cutter, angle grinder or fine-toothed hacksaw. Do not use a flame cutter.
Fig. 44: Proceed with caution when clamping the pipe – avoid deformation of the pipe end.
Fig. 45: Properly deburr the inside and outside of the pipe.
Fig. 46: With the help of a wire brush, sanding paper or an angle grinder with a fan washer, remove loose dirt and rust particles from the pressing area.
Mountine | Creation of the press connection 2 ½ to 4 inches
29
Fig. 47: Ensure the proper seat of sealing element, separator ring and cutting ring.
Fig. 48: Measure the insertion depth in the press connector and mark it on the pipe.
Fig. 49: Push the press connector onto the pipe as far as it will go. Do not tilt the press connector.
Fig. 50: Place the Pressgun Press Booster in the press machine and lock in place using the retaining bolt.
Megapress data sheet
30
Fig. 51: Place the Megapress XL press ring around the press connector. Obser-ve the proper fit of the press ring. Trigger pressing twice! If necessary, carry out a reset stroke.
Fig. 52: Remove the control label to mark the press connector as "pressed". Following installation, check that the insertion depth is correct.
Insertion depthsMeasure the required insertion depths at the press connection. The following insertion depths must be observed:
Dimension Minimum insertion depth[mm][Inch] [mm]
⅜ 17,2 24½ 21,3 27¾ 26,9 291 33,7 34- 38,0 421¼ 42,4 46- 44,5 481½ 48,3 48- 57,0 482 60,3 502½ 76,1 463 88,9 594 114,3 80
Tab. 17: Megapress insertion depths
Mountine | Creation of the press connection 2 ½ to 4 inches
31
Space requirement when pressingFor technically fault-free pressing, some space is required for placing the press machine. See the following tables for information on the minimum space required in different installation situations.
Size a b
⅜ 30 70
½ 30 70
¾ 35 80
1 45 95
Tab. 18: Pressing between pipes – press jaws up to DN 25
Size a b c
⅜ 35 50 80
½ 35 50 80
¾ 40 55 90
1 50 65 105
Tab. 19: Pressing between pipe and wall – press jaws up to DN 25
Size Minimum space required amin [mm]
⅜
50
½
¾
1
Tab. 20: Distance to wall – press jaws up to DN 25
Press jaws
Megapress data sheet
32
Size Minimum space required amin [mm]
⅜
5
½
¾
1
Tab. 21: Minimum distance between the pressings – press jaws up to DN25
Size a b
½ 60 75
¾ 65 85
1¼ 95 125
1½105
135
2 140
2½ 115 150
3 120 170
4 135 210
Tab. 22: Pressing with press rings between pipes – press rings DN 15 – DN 100
Press rings
Mountine | Space requirement when pressine
33
Size a b c
½ 60 75
80
¾ 65 85
1¼ 95 125
1½105
135
2 140
2½ 115 150 100
3 120 170 120
4 135 210 140
Tab. 23: Pressing with press rings between pipes – press rings DN 15 – DN 100
Size Minimum space required amin [mm]
½
20
¾
1¼
1½
2
2½
3
4
Tab. 24: Distance to wall – press rings DN 15 – DN 100
Megapress data sheet
34
Size Minimum space required amin [mm]
½
15
¾
1¼
1½
2
2½
3
4
Tab. 25: Minimum distance between the pressings – press rings DN15–DN100
Mountine | Space requirement when pressine
35
Length expansion – Expansion equalisa-tion joints/expansion bends
0 10 20 30 40 50 60 70 80 90 100
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Läng
enau
sdeh
nung
--->
∆l [
mm
]
Roh
rläng
e ---
> l 0
[m]
Temperaturdifferenz ---> ∆ϑ [K]
30
25
20
15
1098765432
Fig. 53: Length expansion steel pipes
Fig. 54: Z-shaped expansion bend Fig. 55: T-shaped expansion bend
Determine the length expansion:
Read the length expansion on the x-axis from the value of the tempe-rature difference vertically upwards to the pipe length, then read the linear expansion on the left on the y-axis
Z-shaped expan-sion bend and T-shaped expansion bend LBZ
Megapress data sheet
36
Fig. 56: U-shaped expansion bend
Deh
nung
sauf
nahm
e ---
> ∆
l [m
m]
Rohrschenkellänge ---> LBZ [m]
0,5 1,0 1,5 2,0
25
20
15
10
5
3/8
1/2
3/4 1
1 1/
41
1/2
2
1,0 1,2 1,4 1,6 1,8 2,0 2,2 2,4 2,6 2,8 3,0
40
30
20
10
2 1/
2
3 4
Deh
nung
sauf
nahm
e ---
> ∆
l [m
m]
Rohrschenkellänge ---> LBZ [m]
Fig. 57: Z-shaped and T-shaped expan-sion bends for Megapress / Megapress S ⅜–2 inches
Fig. 58: Z-shaped and T-shaped expan-sion bends for Megapress S XL 2½–4 inches
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4
50
45
40
35
30
25
20
15
10
5
0
3/8
1/2
3/4 1
1 1/
41
1/2
2
Deh
nung
sauf
nahm
e ---
> ∆
l [m
m]
Rohrschenkellänge ---> LBU [m]
0 0,5 1,0 1,5 2,0 2,5 3,0
100
50
10
2 1/
23 4
Deh
nung
sauf
nahm
e ---
> ∆
l [m
m]
Rohrschenkellänge ---> LBU [m]
Fig. 59: U-shaped expansion bend for Megapress / Megapress S ⅜–2 inches
Fig. 60: U-shaped expansion bend for Megapress S XL 2½–4 inches
U-shaped expan-sion bend with ex-pansion bend LBU
Z-shaped and T-shaped expansion bends
U-shaped expan-sion bend
3737
Mountine
TABLES – PIPE EQUIVALENTSFor planning and installing sprinkler systems, the equivalent pipe length (leq) is significant. In sprin-kler systems according to VdS CEA 4001, dimensions of ¾ inch and up must be used.
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4216
¾ 694 524 19 0,61 0,3761 694 531 20 0,64 0,5361¼ 694 548 16 0,51 0,623
1½ 694 555 14 0,45 0,657
2 694 562 15 0,48 0,943
4216XL
2½ 751 616 15 0,47 1,29
3 751 623 15 0,46 1,61
4 751 630 14 0,44 2,03
4216.1
¾ 694 647 18 0,58 0,356
1 694 654 18 0,58 0,4831¼ 694 661 14 0,45 0,5451½ 694 678 13 0,42 0,6102 694 685 13 0,42 0,818
4216.1XL
2½ 751 678 15 0,47 1,29
3 751 685 15 0,46 1,61
4 751 692 14 0,44 2,03
4226
¾ 694 586 16 0,51 0,317
1 694 593 17 0,54 0,456
1¼ 694 609 12 0,38 0,467
1½ 694 616 10 0,32 0,469
2 694 623 11 0,35 0,692
4226XL
2½ 751 647 12 0,38 1,04
3 751 654 12 0,37 1,31
4 751 661 11 0,36 1,65
3838
Megapress data sheet
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4226.1
¾ 694 708 16 0,51 0,317
1 694 715 16 0,51 0,429
1¼ 694 722 12 0,38 0,467
1½ 694 739 10 0,32 0,469
2 694 746 11 0,35 0,692
4226.1XL
2½ 751 708 12 0,38 1,04
3 751 715 12 0,37 1,31
4 751 722 11 0,36 1,65
4215
¾ 694 760 10 0,32 0,198
1 694 777 9 0,29 0,241
1¼ 694 784 8 0,26 0,311
1½ 694 791 7 0,22 0,329
2 694 807 7 0,22 0,440
4215XL
2½ 751 739 10 0,3 0,83
3 751 746 9 0,29 1,03
4 751 753 9 0,28 1,29
4215.5
¾ 694 821 10 0,32 0,198
1 694 838 9 0,29 0,241
1¼ 694 845 8 0,26 0,311
1½ 694 852 7 0,22 0,329
2 694 869 7 0,22 0,440
4215.5XL
2½ 751 760 10 0,3 0,83
3 751 777 9 0,29 1,03
4 751 784 9 0,28 1,29
4215.1
1 x ¾ 695 415 10 0,32 0,198
1¼ x ¾ 695 439 11 0,35 0,218
1¼ x 1 695 446 11 0,35 0,295
1½ x ¾ 695 460 11 0,35 0,218
1½ x 1 695 477 11 0,35 0,295
1½ x 1¼ 695 484 8 0,26 0,311
2 x ¾ 695 507 11 0,35 0,218
2 x 1 695 514 11 0,35 0,295
2 x 1¼ 695 521 9 0,29 0,350
2 x 1½ 695 538 8 0,26 0,376
3939
Ta les – Pipe equivalents
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4215.1XL
2½ x 2 752 156 9 0,3 0,59
3 x 2 752 163 9 0,3 0,59
3 x 2½ 752 170 9 0,27 0,74
4 x 2 752 187 10 0,3 0,60
4 x 2½ 752 194 8 0,27 0,72
4 x 3 752 200 8 0,26 0,91
4211
¾ x ¾ 695 286 19 0,61 0,376
1 x 1 695 293 15 0,48 0,402
1¼ x 1¼ 695 309 14 0,45 0,545
1½ x 1½ 695 316 10 0,32 0,469
2 x 2 695 323 9 0,29 0,566
4211XL
2½ x 2½ 751 555 11 0,35 0,96
3 x 3 751 562 11 0,34 1,17
4 x 4 751 579 10 0,31 1,44
4212
¾ x ¾ 695 347 19 0,61 0,376
1 x 1 695 354 15 0,48 0,402
1¼ x 1¼ 695 361 14 0,45 0,545
1½ x 1½ 695 378 10 0,32 0,469
2 x 2 695 385 9 0,29 0,566
4212XL
2½ x 2½ 751 586 11 0,35 0,96
3 x 3 751 593 11 0,34 1,17
4 x 4 751 609 10 0,31 1,44
4259
1¼ 694 876 8 0,26 0,311
1½ 694 883 7 0,22 0,329
2 694 890 7 0,22 0,440
4259XL
2½ 751 869 10 0,3 0,83
3 751 876 9 0,29 1,03
4 751 883 9 0,28 1,29
4040
Megapress data sheet
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4218
¾ 694 975 12 0,38 0,238
1 699 024 13 0,42 0,349
1¼ 694 999 10 0,32 0,389
1½ 695 002 9 0,29 0,423
2 695 019 9 0,29 0,566
1 x ¾ x 1 695 040 13 0,42 0,349
1¼ x ¾ x 1¼ 695 057 10 0,32 0,389
1¼ x 1 x 1¼ 695 095 10 0,32 0,389
1½ x ¾ x 1½ 695 071 9 0,29 0,423
1½ x 1 x 1½ 695 101 9 0,29 0,423
1½ x 1¼ x 1½ 695 088 9 0,29 0,423
2 x ¾ x 2 695 125 9 0,29 0,566
2 x 1 x 2 695 132 9 0,29 0,566
2 x 1¼ x 2 695 149 9 0,29 0,566
2 x 1½ x 2 695 156 9 0,29 0,566
4218XL
2½ 751 524 10,6 0,34 0,92
3 751 548 10,3 0,33 1,14
4 751 531 9,9 0,32 1,46
2½ x 1 x 2½ 751 944 10,6 0,34 0,92
2½ x 1¼ x 2½ 751 968 10,6 0,34 0,92
2½ x 1½ x 2½ 751 975 10,6 0,34 0,92
2½ x 2 x 2½ 751 982 10,6 0,34 0,92
3 x 1 x 3 751 999 10,3 0,33 1,14
3 x 1¼ x 3 752 002 10,3 0,33 1,14
3 x 1½ x 3 752 019 10,3 0,33 1,14
3 x 2 x 3 752 026 10,3 0,33 1,14
3 x 2½ x 3 752 033 10,3 0,33 1,14
4 x 1 x 4 752 040 9,9 0,32 1,46
4 x 1¼ x 4 752 057 9,9 0,32 1,46
4 x 1½ x 4 752 064 9,9 0,32 1,46
4 x 2 x 4 752 071 9,9 0,32 1,46
4 x 2½ x 4 752 088 9,9 0,32 1,46
4 x 3 x 4 752 095 9,9 0,32 1,46
4141
Ta les – Pipe equivalents
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4218
¾ 694 975 30 0,96 0,594
1 699 024 33 1,06 0,885
1¼ 694 999 29 0,93 1,128
1½ 695 002 26 0,83 1,221
2 695 019 29 0,93 1,824
1 x ¾ x 1 695 040 23 0,74 0,455
1¼ x ¾ x 1¼ 695 057 18 0,58 0,356
1¼ x 1 x 1¼ 695 095 22 0,70 0,590
1½ x ¾ x 1½ 695 071 16 0,51 0,317
1½ x 1 x 1½ 695 101 18 0,58 0,483
1½ x 1¼ x 1½ 695 088 21 0,67 0,817
2 x ¾ x 2 695 125 14 0,45 0,277
2 x 1 x 2 695 132 15 0,48 0,402
2 x 1¼ x 2 695 149 15 0,48 0,584
2 x 1½ x 2 695 156 17 0,54 0,798
4218XL
2½ 751 524 31 0,99 2,70
3 751 548 30,5 0,97 3,39
4 751 531 29,9 0,96 4,40
2½ x 1 x 2½ 751 944 13,1 0,42 0,35
2½ x 1¼ x 2½ 751 968 13 0,41 0,51
2½ x 1½ x 2½ 751 975 13,7 0,44 0,64
2½ x 2 x 2½ 751 982 17 0,54 1,07
3 x 1 x 3 751 999 11,9 0,38 0,32
3 x 1¼ x 3 752 002 11,9 0,38 0,46
3 x 1½ x 3 752 019 12,3 0,39 0,58
3 x 2 x 3 752 026 14,5 0,46 0,91
3 x 2½ x 3 752 033 21,3 0,68 1,85
4 x 1 x 4 752 040 11,8 0,38 0,32
4 x 1¼ x 4 752 057 11,3 0,36 0,44
4 x 1½ x 4 752 064 11 0,35 0,52
4 x 2 x 4 752 071 11,6 0,37 0,73
4 x 2½ x 4 752 088 13,8 0,44 1,20
4 x 3 x 4 752 095 16,8 0,54 1,87
4242
Megapress data sheet
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4217.2
¾ x ½ 695 170 12 0,38 0,238
1 x ½ 695 187 13 0,42 0,349
1 x ¾ 695 194 13 0,42 0,349
1¼ x ½ 695 200 10 0,32 0,389
1½ x ½ 695 217 9 0,29 0,423
1½ x ¾ 695 224 9 0,29 0,423
1½ x 1 695 231 9 0,29 0,423
2 x ½ 695 248 9 0,29 0,566
2 x ¾ 695 255 9 0,29 0,566
2 x 1 695 262 9 0,29 0,566
4217.2XL
2½ x ¾ x 2½ 752 101 10,6 0,34 0,92
3 x ¾ x 3 752 118 10,3 0,33 1,14
4 x ¾ x 4 752 125 9,9 0,32 1,46
4217.2
¾ x ½ 695 170 20 0,64 0,265
1 x ½ 695 187 16 0,51 0,212
1 x ¾ 695 194 17 0,54 0,337
1¼ x ½ 695 200 15 0,48 0,199
1½ x ½ 695 217 14 0,45 0,186
1½ x ¾ 695 224 12 0,38 0,238
1½ x 1 695 231 16 0,51 0,429
2 x ½ 695 248 13 0,42 0,172
2 x ¾ 695 255 11 0,35 0,218
2 x 1 695 262 14 0,45 0,375
4217.2XL
2½ x ¾ x 2½ 752 101 10,6 0,34 0,21
3 x ¾ x 3 752 118 10,5 0,34 0,21
4 x ¾ x 4 752 125 10,6 0,34 0,21
4213
¾ x 22 718 794 12,8 0,41 0,25
1 x 28 718 800 12,1 0,39 0,32
1¼ x 35 718 817 11,0 0,35 0,43
1½ x 42 718 824 10,2 0,33 0,48
2 x 54 718 831 10,0 0,32 0,63
4343
Ta les – Pipe equivalents
Model Dimension Art. no. Δp(hPa)
Zeta leq(m)
Symbol
4213.1
1 x 1 718 343 11,8 0,38 0,32
1¼ x 1¼ 718 756 10,5 0,33 0,38
1½ x 1½ 718 763 9,8 0,31 0,46
2 x 2 718 770 9,8 0,31 0,62
4263
¾ x 1 718 855 15,0 0,48 0,30
1 x 1½ 718 879 12,9 0,41 0,35
1 x 1¼ 718 848 13,4 0,43 0,36
1¼ x 1½ 718 862 12,8 0,41 0,50
1¼ x 2 725 860 12,0 0,38 0,47
1½ x 1½ 747 824 20,1 0,64 0,94
2 x 2 474 831 19,1 0,61 1,20
4265
¾ x ¾ 718 909 17,4 0,56 0,34
1 x 1 718 893 24,0 0,77 0,64
1¼ x 1¼ 718 916 14,0 0,45 0,54
1½ x 1½ 747 800 13,3 0,43 0,62
2 x 2 747 817 12,1 0,39 0,76
4444
Megapress data sheet
Inquiry regarding material durabilityInquiry regarding material durabilityTechnical ConsultingPhone +49 (0) 2722 61-1100Fax +49 (0) 2722 61-1101technical.support@viega.com
Customer Building project
Customer no.
Customer/company* Customer/company*
Contact persons* Contact persons
Street* Street
Postal code/town* Postal code/town
Country* Country
Phone* Phone
Email* Email
Potential*
Information about the installation system
Planned system*
Dimension* < DN 50 > DN50 < 2" > 2"
Information about the medium
Supplier/manufacturer*
Trade name/designation*
Application/function*
Concentration of the medium*
Other components
Duration of the condition
max. temp.*
min. temp.*
max. pressure*
min. pressure*
max. pH value
min. pH value
Information about the systemFunction of the complete system
Installation site* Indoor OutdoorType of installation* open closedStagnation* yes noAmbient conditions* Interior spaces Country air City air Sea air
Industrial air Otherdesired service life* < 1 year 1–5 years 5–10 years > 10 years
Free text field
*) Mandatory fieldsINT · 2018-05 · V1 · VPN180058
4646
Megapress data sheet
47
Viega Technology GmbH & Co. KGViega Platz 157439 AttendornGermany
Phone +49 (0) 2722 61-0
viega.com
738 990 · 2020-08 · V20 · VPN200362