Post on 05-Jul-2018
2 | Css/M
safety and reliability Our focus, our solution
Technical Data
Transformer
Design standard As60076
Type and style Hermetically sealed
Rated kVA up to 2000kVA
Insulation medium (Oil only) mineral or BiOteMp ® (environmentally friendly)
Cooling type ONAN
Winding material (HV/LV) Al/Al or Cu/Cu
Pressure relief devices optional
Winding Temperature Indicator optional
Oil Temperature Indicator optional
Oil level sight gauges included
Maximum medium voltage up to 36kV
Maximum low voltage up to 1000V
Maximum transformer power rating up to 2000kVA
Service conditions
Design ambient temperature 40°C or 50°C
Design altitude less than 1000m above sea level
Maximum wind speed region (rated as per AS/NZS 1170.2:2011)
region D
CSS enclosure/plinth
Technical Specifications ieC62271-202
CSS Style/Format Mercury (Rectangular)
Short Circuit current of internal earthing network
20kA/1sec
Internal Arc Classification Note: Authorised Personnel and General Public
iAC A 20KA/1sec
Enclosure Rated Class K 10
Enclosure Material Galvabond or stainless steel
Enclosure Material Thickness 2.9mm / 1.5mm
Base Frame Material and Finishing steel - hot dip galvanised
Bund Capacity 100% or 110%
Surface Protection/Paint powder coat
Colour - external and internal Orange as standard / optional colours on request
IP rating
MV Switchgear compartment ip54
LV Switchgear compartment ip54
Transformer compartment ip23D
High voltage switchgear (ring main unit - RMU)
Technical Specifications ieC62271-200
ABB RMU Type safeRing safe plus
Rated Voltage 12kV / 24kV / 36kV
Power Frequency Withstand Voltage 28kV / 50kV / 70kV
Lighting Impulse Withstand Voltage95kV / 125kV / 170kV
Nominal Current "C" module (Load switch)
630A
Nominal Current "F" module (Switch-Fuse)
630A max rating for bushings / 200A
Nominal Current "V" module (Vacuum Circuit Breaker)
200A 200A / 630A
Short Time Current 3s "C" module (Load switch)(@12kV/24kV)
21kA / 16kA / 16kA
21kA / 21kA / 16kA
Short Time Current 3s "F" module (Switch-Fuse)(@12kV/24kV)
N/A
Short Time Current 3s "V" module (Vacuum Circuit Breaker)
16kA/16kA 21kA/21kA
Typical ConfigurationsDeF, DeV, CCF
CCV, CCVV
different combinations
up to 4 modules
Local/Remote + Motor Operation optional
CB Trip/Fuse Blown Status optional
Protection relay
ABB type ReJ603-selfpoweredReF615 or other ABB Relion series
Low voltage switchgear
Technical Specifications As3439-1
Form Segregation form 1A to 4B
Short Time Rating 50kA / 80kA
Enclosure access front or double access
Internal power connection flexible insulated cable
Main Isolator or Circuit Breaker up to 3200A ACB
Power Meter optional
Light & Power Distribution Board up to 36 circuits
Feeders different arrangement up to 9x160A MCCB
Automatic transfer switch optional
SCada/RTU/Smart grid capability
Remote control and monitoring optional
Separate compartment for SCADA/Comms equipment
optional
While care has been taken to ensure that the information contained in this document is correct, no responsibility can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at any time in the light of technical or other developments. technical specifications are valid under normal operating conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for indirect or consequential damages. technical data and design is subject to change and should be confirmed prior to ordering.
Css/M | 3
Dimensions
CSS/10M CSS/20M
height 2800 3400
width 1600 2400
length 4400 7000
maximum weight (kg) 5000 14000
information is approximate and subject to change without notice.All dimensions are in mm. Drawings are not to scale.
the Css concept is for applications where energy transformation is required. the solution is a type tested enclosure where all switchgear, distribution transformer, communications and auxiliary equipment are installed and factory tested to reduce cost and installation time on site.
CSS/10M (single front) side view CSS/20M (double front) side view
CSS/10M (single front) plan view CSS/20M (double front) plan view
© 2
013
AB
B.
All
right
s re
serv
ed.
1VG
A 6
7107
5 re
v A
- C
SS
- C
SS
-M A
3 fly
er
CSS/M Request for quotation form
Name
Company
Project
Phone + 6 1
Mobile + 6 1
Email @
Address
Address line 2
State Postcode
ABB reference number
Date of enquiry D D / M M / Y Y Y Y
CSS technical requirements
Ambient temperature °C
Wind speed km/h
Enclosure colour Default: Orange
Internal arc classification, IAC A 20kA, 1s tick if required
Oil bund
Internal lighting to MV & LV space
Remote control/SCADA
Transformer technical requirements (OIL TYPE ONLY)Power (kVA) Primary (kV) Secondary (V) Accessories
315 34.5 430 Oil temperature
500 22 690 Winding temp.
750 11 1000 Pressure relief
1000 6.6
1250 3.3
1500
2000
MV Switchgear technical details
RMU type:
SafeRing SafePlus
Configuration (up to 4 modules)
DeF DeV CCV CCF CCVV
De = Direct connection to bus + earth switch C = Load switch + earth switchV = Vacuum circuit breaker + earth switchF = Fuse feeder + earth switch
Electrical operation (tick if required)
Specify auxiliary voltage:
LV Switchgear technical details
Incomer:
Circuit breaker Isolator only ATS
630A, 3P 1250A, 3P 2000A, 3P 3200A, 3P
800A, 3P 1500A, 3P 2500A, 3P
Outgoing CBs:
63A, 4P 160A, 3P 400A, 3P 800A, 3P
100A, 3P 250A, 3P 630A, 3P 1250A, 3P
Other, specify:
Electrical operation + aux. contacts
MDI Specify aux. voltage:
Power meter L&P DB+GPO
Please fill in the form below and email to: contact.centre@au.abb.com
For further enquiries, different configurations and assistance, contact ABB Australia: 1800 222 435.
Scan the QR code to visit the product page.
Expected date of PO D D / M M / Y Y Y Y
Expected date of delivery D D / M M / Y Y Y Y
Delivery postcode
abbaustralia.com.au