Copper tubing and other devices for Solar Plumbing!

Post on 12-Mar-2016

216 views 0 download

Tags:

description

it is a test file!

Transcript of Copper tubing and other devices for Solar Plumbing!

COPPER

Background

The first known use of copper pipe was in ancient Egypt to convey water to the Pharaoh’s royal bath. When the pipe was uncovered by archeologists almost 5000 years later, it was still usable!

Copper Types Drawn referred to as “hard”

Annealed referred to as “soft”

both are available in a wide range of diameters and wall thicknesses

Reasons to Use Copper

• Versatility

• Variety of applications

• Wide range of sizes

• Problem-free performance

• Long lasting and maintenance free

• Corrosion resistance

• High thermal conductivity

Why Use Copper for Solar?

•  It has the best thermal conductivity of all engineering metals

•  It is highly resistant to corrosion

•  It is easy to fabricate and to join by soldering or brazing

•  It has been used both for plumbing and for roofs since metals were first used in these applications

Technical Info.

NOTE: *Based on maximum allowable stress in tension (psi) for the indicated temperatures (°F), **When brazing or welding is used to join drawn tube, the corresponding annealed rating must be used

(Table continues on next page)

TABLE 4. Pressure-Temperature Ratings of Soldered and Brazed Joints Continued!

NOTE: For extremely low working temperatures in the 0°F to minus 200°F range, it is recommended that a joint material melting at or above 1100°F be employed.(1) Standard water tube sizes per ASTM B 88.(2) Ratings up to 8 inches in size are those given in ASME B16.22 Wrought Copper and Copper Alloy Solder Joint Pressure Fittings and ASME B16.18 Cast Copper and Copper Alloy Solder Joint Fittings. Rating for 10- to 12-inch sizes are those given in ASME B16.18 Cast Copper and Copper Alloy Solder Joint Pressure Fittings.(3) Using ASME B16.29 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings — DWV, and ASME B16.23 Cast Copper Alloy Solder Joint Drainage Fittings — DWV.(4) Alloy designations are per ASTM B 32.(5) The Safe Drinking Water Act Amendment of 1986 prohibits the use in potable water systems of any solder having a lead content in excess of 0.2%.(6) These joining materials are defined as brazing alloys by American Welding Society."

1. The figures shown are averages of three certified tests performed on each type and size of water tube. In each case, wall thickness was at or near the minimum prescribed for each tube type. No burst pressure in any test deviated from the average by more than 5 percent."2. These burst pressures can be used for ACR tube of equivalent actual O.D. and wall thickness."

TABLE 5. Actual Burst Pressures,1 Types K, L, and M Copper Water Tube, psi at Room Temperature

NOTES:!1. Fluid velocities in excess of 5-8 feet per second are not recommended."2. Friction loss values shown are for the flow rates that do not exceed a velocity of 8 feet per second."3. Highlighted and italicized friction loss values indicate flow rates that are between 5 feet and 8 feet per second."

NOTES:!4. Table 6 is based on the Hazen-Williams formula:"

Hydrostatic Pressure, psi!

FIGURE 2. Collapse Pressure of Copper Tube, Types K, L and M!

Nominal or Standard size, inches

FIGURE 2. Collapse Pressure of Copper Tube, Types K, L and M Continued!

Hydrostatic Pressure, psi!

Calculating Expansion & Contraction of Copper •  Calculation is based on the average coefficient of

the expansion of copper

•  0.0000094 inch per degree F, between 70°F and 212°F.

•  For example, the expansion of each 100 feet of length of any size tube heated from room temperature (70°F) to 170°F (a 100°F rise) is 1.128 inches.

•  100°F x 100 ft x 12 in./ft. x 0.0000094 in./in./°F =1.128 in.

Common Fittings Adapters, Elbows, & Couplings

Selected Fittings

Selected Fittings

Selected Fittings

Selected Fittings

Copper & Soldering

To Reduce Problems- avoid the following

• Lack of reaming of the tube ends. • Burrs left on the inside of the tube can cause

interruption of flow • Water at high velocity. • An undersized pipe or an oversized pumps may

cause high water velocity. • Protrusions into the flow stream. • caused by lumps of solder/brazing material,

improperly fabricated tees, etc.

To Reduce Problems- Continued

• Excessive water temperature. •  Heating above 140ºF can accelerate the process

of erosion-corrosion. • Excess of dissolved gases, vapors or suspended

solids in the water. • Can damage the metal surface causing erosion-

corrosion at high velocities.

Erosion-corrosion is not specific to copper. When it does occur, it is readily identifiable by pitting inside of the tubes.