Necessity And Advantages Of DG SetEnergy is needed for every system. To cater the needs of Industry, Residential, Agriculture and other purpose, State Electricity Boards Generate, transport and distribute Electrical Energy. The prime sources of energy are Coal, fossil fuel, Water, Nuclear fuel and Natural Gas.
All these Power Plants are Economic only if they are built on large capacity i.e. 200 MW and above. Also the capital cost of establishment is very high.
Due to larger demand of power than the generated, State boards can not supply power continuously. Also, the power is not available where the area or plant is under development.
To have alternate source of Power, Diesel Generating Set is the ideal solution.
It is used mainly as Standby Source and sometimes as Continuous Duty.
MAHINDRA & MAHINDRA are one of the large manufacturers of DG sets, under the name POWEROL
The range of the DG set is from 2.5 kVA to 500 kVA
Chapter 4 - Basics of Diesel Generator
Features of Mahindra Powerol ProductsMain Features of POWEROL are as below
lThe DG Set is housed in an acoustic enclosure.
lWeather proof enclosure provides protection against all environmental conditions.
lEasy for lifting- shifting.
lEasily detachable Diesel Tank, for cleaning purpose.
lEasy access for emergency stop control
lSize of control panel is adequately large to provide better cooling.
lInner volume of acoustic canopy is larger to provide more air for cooling and engine aspiration.
Po
wer
ol S
ales
Gui
de
Main components of DG set are
lDiesel Engine
lAlternator
lBase frame for Mounting
lFuel Tank
lEngine Control Panel
lAlternator Control Panel
lSilencer
lSound reducing Canopy
Diesel Engine
Engine converts heat energy into mechanical energy in rotational form. Heat is generated by burning Diesel Fuel inside the cylinder block. Engine Fly wheel is coupled to alternator and alternator is rotated.
Alternator
Alternator converts the rotational mechanical energy into Alternating Current – Voltage and Power . Rotating magnets in alternator, generate AC voltage.
Base frame for Mounting
Engine and Alternator are mounted on Steel Base frame.
Po
wer
ol S
ales
Gui
de
Fuel Tank of DG Set
Alternator
Battery
Inside of DG Set - Rear Face
DG Set Fuel Tank
Diesel Tank - Removable
Fuel Tank
lFuel tank is housed in base frame.
lFuel tank can be taken out easily from the base for the purpose of cleaning.
lNormally Diesel storage capacity of the tank is sufficient for continuous running for 8 hours.
Po
wer
ol S
ales
Gui
de
Engine Control Panel – Manual operation
lEngine is started manually, maintains constant speed, stopping of the engine is manual.
lThe engine stops immediately, in case of any abnormal condition or accident.
lThe control panel indicates the nature of fault.
Alternator Control Panel
lFunction of Alternator control panel is to develop voltage, maintain constant output voltage, within specified limits, switch ON or OFF, the power supply, switch of the supply in case of fault or accident, indicate power consumption and nature of fault.
Silencer
Is used to arrest the sound caused by Internal Burning of Fuel and generated at exhaust.
Sound reducing CanopyDuring running, Sound generated by, moving components, Fan and external components of any Diesel Engine. A silencer is used for the purpose. However even the reduced sound is harmful to human ears. Hence it is essential to restrict the audible sound surrounding the DG set upto distance of 1 meter. It is reduced by covering the entire DG set by Acoustic and mechanically strong enclosure.
Po
wer
ol S
ales
Gui
de
CPCB Norms and CircularCentral Pollution Control Board have set norms for limits of pollution due to sound and Smoke Emission. And it is compulsory to follow the norms.
The GSR says,
“Noise Limit for Generator Sets run with Diesel
1. Noise limit for diesel generator sets (upto 1000 KVA) manufactured on or after the 1st January, 2005
The maximum permissible sound pressure level for new diesel generator (DG) sets with rated capacity upto 1000 KVA, manufactured on or after the 1st January, 2005 shall be 75dB(A) at 1 meter from the enclosure surface.
The diesel generator sets should be provided with integral acoustic enclosure at the manufacturing stage itself.
POWEROL Gensets are approved as per the norms.
Sound Reducing Barrier
Inside Alternator
DG Set showing Acoustic enclosure
Po
wer
ol S
ales
Gui
de
Basics Of EngineIn 1892, Rudolf Diesel Invented the Engine run by Fossil Fuel. Further the Engine and the fuel was called by the name Diesel.
Main parts of the Engine are:
Cylinder Block, Piston, connecting rod, crank shaft, fly wheel.
A piston is placed in a cylinder and allowed to move up-down.
A small amount of air + fuel mixture is forced into the gap between over piston.
Due to very high pressure, the mixture gets ignited. The burnt gas creates very high pressure on the piston. The piston is forced down.
While piston moves down, it rotates the crank shaft.
Hence the linear motion of piston is transferred to crank shaft. Crank shaft converts the linear motion in rotation.
Radiator
Fuel Filter
Bell Housing
Fly Wheel
Air Filter
Engine Images
Exhaust Manifold
Oil Filter
Oil Sump
Starter
Fuel Pump
Po
wer
ol S
ales
Gui
de
Engine has 5 main systems
1. Fuel Injection System: Diesel and Air are mixed in a specific ratio and pumped in each cylinder with high pressure. The fuel is ignited with high pressure compression. Fuel is first passed through a filter and then pumped in cylinders. For burning of fuel adequate air must be available.
Fuel Injection System
2. Exhaust System: The burnt hot gases are carried out through common duct. They are directed away from the DG set and should be guided through a high duct, so that it is not harmful to the persons, around it.
3. Lubrication System: The moving parts and piston rings have a great friction. Oil is circulated in engine with pump for effective lubrication. Oil is passed through filter and then pumped in system.
4. Cooling System: Engine gets heated due to burning of gases inside. It needs cooling. The engines are cooled by Air with help of Fan or they are cooled by Water radiator. The DG set must have a sufficient space around it for better cooling.
5. Governing System: Engine speed is maintained constant at 1500 RPM, with tolerance within 4%. The unit for control of speed is called Governor. Governors are Mechanical or Digital type.
Po
wer
ol S
ales
Gui
de
The various Terms used in specifications of Engine:
lHP : [IP ] Indicated Horse Power. Power Developed by the engine
in its cylinders.
lBHP : Brake Horse Power . Power available at output shaft /
flywheel. IP – Friction losses.
lRPM : Revolutions Per Minute. Speed of the engine is measured in
RPM
lTYPE :
lSFC : Specific Fuel Consumption. Fuel consumed in Litres /
BHP / Hour
lAIR COOLED : Engine is cooled by air with help of fan.
lWATER COOLED : Cooling is done with Water Radiator. Radiator is
cooled by a fan mounted on engine.
lTURBO CHARGED : A Turbo charger is connected in air inlet
system to enhance output power of engine.
Filter Units : To ensure entry of clean fuel , clean air and clean oil, they
are filtered before entry into engine.
Filter Units are need to be replaced after a specific period or after
specific running hours of engine.
Engine Oil : Lubricating Oil is to be replaced after a specific period or
after specific running hours of engine.
Po
wer
ol S
ales
Gui
de
Alternator
Principle Of Operation-Stator-Rotor-Excitation-Control
When Magnetic rotor is rotated in stator coils, A.C. voltage is generated in stator.
Rotor of alternator is coupled to Engine. Speed of the Engine is maintained
constant at 1500 RPM [Rotations Per Minute]
TerminologyVoltage : Voltage is level of Electrical pressure. e.g. 240 Volt; 440 volt;
6600 volt etc.
Current : unit of measurement is Ampere. It is flow of electric power in wire.
E.g. 5 Amp; 15 Amp; 100 amp. Etc.
Phase : e.g. Single phase; three phase. i.e. the number of windings in the
stator.
KW = Kilo- Watt = 1000 Watt = Useful Power supplied by Alternator
KVA = Kilo- Volt- Ampere = 1000 Volt x Ampere = Total Power Generated by
alternator
RPM = Rotations Per Minute = Revolutions of rotor per minute.
Power Factor = Useful Power of load ÷ Total Power Generated by
DG set
Alternator
Po
wer
ol S
ales
Gui
de
Alternators are available with output of Single phase – 240 Volt or 3
phase 415 Volt. Depending upon the load requirement, select 1 phase or
3 phase alternator. The terminal arrangement of terminal box is as shown
in fig.
Single phase alternator has 2 terminals in connection box. They are:
LINE and NEUTRAL.
Three phase alternator has 4 terminals in connection box. They are: RED – YELLOW – BLUE - NEUTRAL.
AVR
Single Phase Alternator - Terminal Box
Phase
Neutral
Po
wer
ol S
ales
Gui
de
AVR : Automatic Voltage Regulator is fixed in the connection box. The functions of AVR are:
lIt maintains constant voltage output at all the loads.
lVoltage setting can be done ±10% of rated voltage.
lOutput voltage is switched OFF, in case of overload of problem of lower speed of engine. Alternator can be saved from further damage.
Control Panel
Alternator Control Panels are of two types.
1. Standard Panel
2. AMF Panel [Automatic Mains Fail – controlled panel]
STANDARD Control Panel : It has following features
lEngine ON / OFF control - done manually.
lPower ON / OFF control – manual operation.
lIndicating meters – Voltmeter, Ammeter, Frequency Meter, Hour meter.
lIndicating lamps for DG ON / OFF, Power ON / OFF.
lProtection circuit – Power goes OFF, if there is overload.
Po
wer
ol S
ales
Gui
de
AMF Panel – FEATURES AND APLICATIONS
lAutomatic Sensing of Failure of supply of Mains Power.
lRelay for command to Start Engine.
lRelay to switch ON supply.
lSensing restoration of Mains.
lCommand to switch OFF DG Supply.
lCommand to Stop Engine.
lIndicating meters – Voltmeter, Ammeter, Frequency Meter, Hour meter.
lIndicating lamps for DG ON / OFF, Power ON / OFF.
lProtection circuit – Power goes OFF, in case of overload.
lSupply for DG and supply from Mains, can not be short circuited.
Voltage, current, frequency meter
Hour meter
Control unit
Auto/Manual/ Test switch
AMF Panel