Post on 18-Aug-2015
PRODUAL l 1 l CAtALOgUe
Catalogue
2013
PRODUAL l 2 l CAtALOgUe
Customer oriented expertisein measurement technologyProdual is an internationally operating pioneer of building automation measurement technology. the steady growth along with our customers during last years has enabled developing our operations according to the requirements of modern building construction. Reliable and accurate measurements facilitate the monitoring of energy efficiency, improve interior air quality and increase the comfort of occupants of the buildings.
Understanding the emerging requirements of building automation forms the foundation for our operation. We offer a wide and versatile product portfolio. Our devices have earned a reputation as reliable, easy-to-use and installation-friendly equipment, tried and tested in the decades of demanding use. We continuously invest in product development for new innovations and upgrading the basic products. Our customers are satisfied with the reachability of our representatives, and the fast and reliable deliveries. Based on the customer feedback, we constantly develop our operations, and have also strengthened our technical support, which is crucial to the customers in the field.
All the 68 Produal experts are very committed to keep on maintaining close relations with our customers – in Finland and elsewhere in europe!
this product list shows merely the foremost features of our products. We are engaged in constant development of our products and the current details and prices may be viewed on our website: www.produal.com /products.
PRODUAL Oy
Source and rights of the pictures on the cover and the introduction: Helsinki Music Centre / Arno Chapelle.
PRODUAL l 3 l CAtALOgUe
5
6
7
8
9
10
11
COntentS
air velocity transmitters ........................................7differential pressure transmitters for air .............. 8–9air flow transmitters ............................................9air flow probe ......................................................10humidity transmitters ....................................... 11–12light level transmitters ............................................13
light level sensor ...................................................14differential pressure transmitters for water .............. 15pressure transmitters for water ............................ 15CO2 transmitters .......................................... 16–17carbon monoxide transmitters ............................. 17wind speed detector .......................................... 18rain sensor ....................................................... 19
heating/cooling water sensors ..............................27hot domestic water sensors .................................28frost guard sensors .............................................29strap-on sensors ................................................30duct sensors.................................................31–33cable temperature sensors ............................. 34–35cable temperature sensor, floor ............................36
cable temperature sensor, soil installation ..............36combustion gas sensors ......................................37room temperature sensors ..............................37–39outdoor air temperature sensors ..................... 39–40industrial temperature sensors .............................40temperature transmitters ..................................... 41
I/O modules ......................................................42transducers ................................................. 42–44transformers .....................................................45occupancy sensors .............................................46pir detectors .....................................................47
timers ..............................................................48push buttons .....................................................48indicator lights ...................................................49relays ......................................................... 49–50water leakage ................................................... 51
meters .............................................................57differential pressure switches ...............................58
control valves ....................................................59thermal actuators...............................................59
Produal Oy reserves the right to change the specifications without prior notification.
12
13
14
15
16
FROST PROTECTION CONTROLLERS ................................................................................4
HIGH TEMPERATURE ALARM THERMOSTATS .....................................................................4
ELECTRONIC THERMOSTATS ..........................................................................................5
TRANSMITTERS .........................................................................................................7
ELECTRIC POwER REGULATION ................................................................................... 19
TEMPERATURE CONTROLLERS .....................................................................................20
UNIvERSAL CONTROLLERS ......................................................................................... 25
TEMPERATURE MEASUREMENT .................................................................................... 27
TRANSDUCERS AND ACCESSORIES ............................................................................... 42
wIRELESS ............................................................................................................... 53
METERS, SwITCHES, vALvES AND ACTUATORS ............................................................... 57
TERMS OF DELIvERY ............................................................................................ 60–61
SENSOR SELECTION GUIDE .................................................................................... 62–63
SENSOR CHARACTERISTICS ........................................................................................ 64
CONTROLLER SELECTION GUIDE .................................................................................. 65
INDEX ................................................................................................................... 66
2
3
4
1
PRODUAL l 4 l CAtALOgUe
Frost protection relays are protective devices for preventing heating coils from freezing in the air handling units.
Frost protection relays are protective devices for preventing heating coils from freezing in the air handling units.
High temperature alarm relay is a protective device monitoring duct temperatures in the air handling units.
supply 24 Vac/dc, 2 VA
range 0…+100 °C = 0…10 V
contact output 230 Vac, 10 A res.
alarm contact output 60 Vdc, 1 A
input /output signal 0…10 Vdc, 10 mA
housing IP20, for 35 mm DIn rail
supply 24 Vac, 2 VA
range 0…+100 °C = 0…10 V, 10 mA
contact output , AR 1 230 Vac, 10 A
alarm contact output 60 Vdc, 1 A
input / output signal 0(2)…10 V, 10 mA
housing IP20, 11-pole relay housing
supply 24 Vac/dc, 2 VA
range 0…+100 °C = 0…10 V
contact output 230 Vac, 10 A
alarm contact output 60 Vdc, 1 A
housing IP20, for 35 mm DIn rail
Type arT no.
Type arT no.
Type arT no.
JvA 24 1110110 forecasting, regulating; selectable sensor type (Pt1000, ni1000-Lg, PtC 1000/2000)
JvS 24 1110120 adjustable forecasting, regulating; selectable sensor type (Pt1000, ni1000-Lg, PtC 1000/2000)
EJv 24-PT 1110080 for Pt1000 sensor (1000 Ω / 0 °C), AR 1 relay included
Jv 24-PT 1110090 for Pt1000 sensor (1000 Ω / 0 °C), contact output 50 Vac 6 A res.
PvA 24 1110180 selectable sensor type (Pt1000, ni1000-Lg, PtC 1000/2000)
FROSt PROteCtIOn ReLAyS
FROSt PROteCtIOn ReLAyS
HIgH teMPeRAtURe ALARM ReLAyS
DIN housing
11-pole relay housing
DIN housing
1
2
PRODUAL l 5 l CAtALOgUe
LK 24-Pt is a thermostat with an external Pt1000 temperature sensor input.
LeK 24-Pt is a temperature difference thermostat with two external Pt1000 temperature sensor inputs.
supply 24 Vac/dc, 2 VA
range -30…+30 °C or 0…+100 °C
input sensor input, Pt1000 (1000 Ω / 0 °C)
output 1 change-over contact, 230 V, 5 A res.,
by using AR 1 relay, 230 Vac, 10 A
output 2 0…10 V = -30…+30 °C
or 0…10 V = 0…+100 °C
housing IP20, 11-pole relay housing
supply 24 Vac/dc, 2 VA
range -30…+100 °C
difference setting 0…10 °C
hysteresis 0,2…5 °C
inputs sensor inputs, Pt1000 (1000 Ω / 0 °C)
output change-over contact 230 V, 5 A res.,
by using AR 1 relay, 230 Vac, 10 A
housing IP20, 11-pole relay housing
LK 24-PT 1120050 electronic thermostat, range -30…+30 °C
LK 24-PT 0/100 1120051 electronic thermostat, range 0…100 °C
LEK 24-PT 1120060 temperature difference thermostat
External Pt1000 temperature sensor, e.g. TEK PT 1000.
eLeCtROnIC tHeRMOStAtS
eLeCtROnIC tHeRMOStAtS
°C
Δ °C
3
Type arT no.
Type arT no.
PRODUAL l 6 l CAtALOgUe
FRAnKFURt AIRPORt
HeAtHROW AIRPORt
PRODUAL l 7 l CAtALOgUe
IVL air velocity transmitters are designed for measuring flow velocity inside the duct. Provided also with a temperature output.
VK 10 is a voltage controlled relay with an adjustable hysteresis.
supply 24 Vac/dc, < 1,5 VA
range, velocity IVL 10: 0…10 m/s, IVL 02: 0…2 m/s,
IVL 20: 0…20 m/s
range, temperature 0…+50 °C
output 1 velocity = 0…10 V < 2 mA
or 4…20 mA < 600 Ω
output 2 temperature 0…+50 °C = 0…10 V < 2 mA
or 4…20 mA < 600 Ω
ambient temperature 0…+50 °C
stem 10 mm x 200 mm
housing IP54, stem or cable gland downwards
mounting with flange, adjustable probe depth
supply 24 Vac, 2 VA
range 0…10 Vdc
setting range 0…100 %
hysteresis 0,5…5,0 V
output change over contact 230 V, 5 A res.
ambient temperature 0…+50 °C
housing IP20, 11-pole relay housing
IvL 10 1130010 air velocity transmitter 0…10 m/s, adjustable probe depth 50…190 mm
IvL 10-N 1130012 with display air velocity transmitter, 0…10 m/s, adjustable probe depth 50…190 mm
IvL 02 1130030 air velocity transmitter 0…2 m/s, adjustable probe depth 50…190 mm
IvL 02-N 1130031 with display air velocity transmitter, 0…2 m/s, adjustable probe depth 50…190 mm
IvL 20 1130050 air velocity transmitter 0…20 m/s, adjustable probe depth 50…190 mm
IvL 20-N 1130051 with display air velocity transmitter, 0…20 m/s, adjustable probe depth 50…190 mm
versions with 100 mm and 400 mm stems are also available, e.g. IvL 20-400.
vK 10 1130020 voltage controlled relay
AIR VeLOCIty tRAnSMItteRS
VOLtAge COntROLLeD ReLAy
m/s, °C
0...10 v control
4
Type arT no.
Type arT no.
PRODUAL l 8 l CAtALOgUe
PeL differential pressure transmitters are designed for clean / isolation room applications. the transmitter zero point is kept accurate by using the regular automatic zeroing, eliminating the possible zero point drifting.
PeL 2500 differential pressure transmitters are designed for controlling pressures in the air handling units or detecting air volumes. Output signal can be selected either differential pressure linear or flow (volume) linear. the transmitter zero point is kept accurate by using the regular automatic zeroing, eliminating the possible zero point drifting.
supply 24 Vac/dc, 1.5 VA
range selectable at commissioning
output 0…10 Vdc < 2 mA or 4…20 mA < 900…1200 Ω
zeroing automatic; regularly eliminates the possible
zero point drifting
ambient temperature -10…+45 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
supply 24 Vac/dc, 1.5 VA
range selectable at commissioning
output 0…10 Vdc, < 2 mA
zeroing automatic; regularly eliminates the possible
zero point drifting
ambient temperature -10…+45 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
PEL 1131110 ranges 0…100, 0…200, 0…500, 0…1000, ±50, ±100, ±250 or ±500 Pa
PEL-N 1131111 with display, ranges identical with PeL
PEL 25K 1131220 ranges 0…2, 0…4, 0…7, 0…10, 0…15, 0…20 or 0…25 kPa
PEL 25K-N 1131221 with display, ranges identical with PeL 25K
PEL-AS 1131010 PeL accessory kit, includes 2 m hose and duct assemblies
PEL 2500 1131210 ranges ±100, 0…100, 0…200, 0…500, 0…1000, 0…2000 or 0…2500 Pa
PEL 2500-N 1131211 with display, ranges identical with PeL 2500
PEL-AS 1131010 PeL accessory kit, includes 2 m hose and duct assemblies
DIFFeRentIAL PReSSURe tRAnSMItteRS FOR AIR
DIFFeRentIAL PReSSURe tRAnSMItteRS FOR AIR
Pa
Pa
4
Type arT no.
Type arT no.
PRODUAL l 9 l CAtALOgUe
PeL 1000 differential pressure transmitters are designed for fan controlling and air handling unit filter monitoring.
supply 24 Vac/dc, 1 VA
range selectable at commissioning
output 0…10 V, < 3 mA
ambient temperature 0…+50 °C
zeroing manual; process connections must be removed
before zeroing
housing IP54, cable gland downwards
mounting with screws, external lugs
DIFFeRentIAL PReSSURe tRAnSMItteRS FOR AIR
Pa
PEL 1000 1131140 range 0…500 or 0…1000 Pa
PEL 1000-N 1131141 with display, ranges identical with PeL 1000
PEL-AS 1131010 PeL accessory kit, includes 2 m hose and duct assemblies
IML is designed for detecting and controlling air flow in air handling units and rooms. IML-M has RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc, 1.5 VA
range selectable at commissioning
output 1, air volume 0…10 Vdc, < 2 mA
output 2, diff. pressure or control 0…10 Vdc, < 2 mA
input, external set point 0…10 Vdc, < 2 mA
ambient temperature -10…+45 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
IML 1131600 range 0...1000, 0...2000, 0...5000 or 0...7000 Pa
IML-M 1131611 IML for Modbus
PEL-AS 1131010 PeL accessory kit, includes 2 m hose and duct assemblies
AIR FLOW tRAnSMItteRSm3/s, m3/h, l/s, Pa
4
Type arT no.
Type arT no.
PRODUAL l 10 l CAtALOgUe
PP air flow probes are designed for detecting air flow in the air handling systems. Different models with fixed Kv values are available for circular and rectangular ducts.
AIR FLOW PROBel/s
PP-PK R100 1250010 air flow volume probe for a circular 100 mm duct
PP-PK R125 1250020 air flow volume probe for a circular 125 mm duct
PP-PK R160 1250030 air flow volume probe for a circular 160 mm duct
PP-PK R200 1250040 air flow volume probe for a circular 200 mm duct
PP-PK R250 1250050 air flow volume probe for a circular 250 mm duct
PP-PK R315 1250060 air flow volume probe for a circular 315 mm duct
PP-PK R355 1250065 air flow volume probe for a circular 355 mm duct
PP-PK R400 1250070 air flow volume probe for a circular 400 mm duct
PP-PK R500 1250075 air flow volume probe for a circular 500 mm duct
PP-PK R700 1250077 air flow volume probe for a circular 700 mm duct
PP-SK L200 1250080 air flow volume probe for a 200 mm rectangular duct
PP-SK L250 1250090 air flow volume probe for a 250 mm rectangular duct
PP-SK L300 1250100 air flow volume probe for a 300 mm rectangular duct
PP-SK L350 1250110 air flow volume probe for a 350 mm rectangular duct
PP-SK L400 1250120 air flow volume probe for a 400 mm rectangular duct
PP-SK L450 1250130 air flow volume probe for a 450 mm rectangular duct
PP-SK L500 1250140 air flow volume probe for a 500 mm rectangular duct
PP-SK L550 1250150 air flow volume probe for a 550 mm rectangular duct
PP-SK L600 1250160 air flow volume probe for a 600 mm rectangular duct
PP-SK L650 1250170 air flow volume probe for a 650 mm rectangular duct
PP-SK L700 1250180 air flow volume probe for a 700 mm rectangular duct
PP-SK L750 1250190 air flow volume probe for a 750 mm rectangular duct
PP-SK L800 1250200 air flow volume probe for a 800 mm rectangular duct
PP-SK L850 1250210 air flow volume probe for a 850 mm rectangular duct
PP-SK L900 1250220 air flow volume probe for a 900 mm rectangular duct
PP-SK L950 1250230 air flow volume probe for a 950 mm rectangular duct
PP-SK L1000 1250240 air flow volume probe for a 1000 mm rectangular duct
PP-SK L1050 1250250 air flow volume probe for a 1050 mm rectangular duct
PP-SK L1100 1250260 air flow volume probe for a 1100 mm rectangular duct
PP-SK L1150 1250270 air flow volume probe for a 1150 mm rectangular duct
PP-SK L1200 1250280 air flow volume probe for a 1200 mm rectangular duct
Other lengths also available on request.
4 Type arT no.
PRODUAL l 11 l CAtALOgUe
KLH and KLH-M room humidity transmitters are designed for detecting indoor relative humidity and temperature.
KLH 420 is a 2-wire humidity transmitter designed for detecting indoor relative humidity.
KLK 100 duct humidity transmitters are designed for detecting relative humidity and temperature inside ventilation ducts.
supply 24 Vac/dc, 1 VA
range 1 0…100 % rH
range 2 0…+50 °C
output 1, % rH 0…10 V = 0…100 % rH, 2 mA
output 2, °C 0…10 V = 0…+50 °C, 2 mA
housing IP20, ABS plastic
mounting with screws on wall or on a junction box (hole distance 60 mm)
operating voltage 12…35 Vdc
range 0…100 % rH
output, 2-wire transmitter 4…20 mA < 500 Ω (24 Vdc)
housing IP20, ABS plastic
mounting with screws on wall or on a junction box
(hole distance 60 mm)
supply 24 Vac/dc, < 1 VA
humidity range 0…100 % rH
temperature range -50…+50 °C
output 1, % rH 0…10 V < 2 mA /
4…20 mA < 600 Ω = 0…100 % rH
output 2, °C 0…10 V < 2 mA /
4…20 mA < 600 Ω = -50…+50 °C
ambient temperature -50…+50 °C
housing IP54, sensor or cable gland downwards
mounting with flange, adjustable probe depth < 150 mm
KLH 100 1132210 room humidity transmitter
KLH 100-N 1132211 room transmitter with display (humidity and/or temperature display)
KLH-M 1132600 room humidity transmitter for Modbus RtU gateway
KLH-M-N 1132601 room transmitter with display for Modbus RtU gateway (humidity and/or temperature display)
KLH 420 1132280 room humidity transmitter
KLH 420-N 1132281 room transmitter with humidity display
KLK 100 1132240 duct humidity transmitter
KLK 100-N 1132241 duct humidity transmitter with display
HUMIDIty tRAnSMItteRS
HUMIDIty tRAnSMItteRS
HUMIDIty tRAnSMItteRS
room % rH, °C
room % rH
duct % rH, °C
4
Type arT no.
Type arT no.
Type arT no.
PRODUAL l 12 l CAtALOgUe
KLHJ 100 transmitters are designed for detecting relative humidity and temperature. the probe cable length is 2 m.
KLU 100 humidity and temperature transmitters are designed for outdoor applications.
supply 24 Vac/dc, < 1 VA
range 1 0…100 % rH
range 2 -50…+50 °C
output 1, % rH 0…10 V < 2 mA /
4…20 mA < 600 Ω = 0…100 % rH
output 2, °C 0…10 V < 1 mA /
4…20 mA < 600 Ω = -50…+50 °C
ambient temperature -50…+50 °C
sensor cable 2 m
housing IP54, cable gland downwards, (sensor IP50)
mounting transmitter with screws (external lugs), sensor
with flange, adjustable probe depth < 150 mm
supply 24 Vac/dc, < 1 VA
range 1 0…100 % rH
range 2 -50…+50 °C
output 1, % rH 0…10 V < 2 mA /
4…20 mA < 600 Ω = 0…100 % rH
output 2, °C 0…10 V < 1 mA /
4…20 mA < 600 Ω = -50…+50 °C
ambient temperature -50…+50 °C
housing IP54, sensor downwards
mounting with screws, external lugs
KLHJ 100 1132260 humidity and temperature transmitter
KLHJ 100-N 1132261 humidity and temperature transmitter with display
KLU 100 1132250 outdoor humidity transmitter
KLU 100-N 1132251 outdoor humidity transmitter with display
HUMIDIty tRAnSMItteRS
HUMIDIty tRAnSMItteRS
room/duct % rH, °C
outdoor % rH, °C
4
Type arT no.
Type arT no.
PRODUAL l 13 l CAtALOgUe
Condensation switch KA 10 is designed for detecting water condensation in cooling systems, for example in cooling beams. With the condensation switch it is possible to control the cooling water supply when the water starts to condensate on the pipe. the KA 10-eXt model has an external condensation sensor.
supply 24 Vac/dc
outputs condensation information 0...10 Vdc
relay output 24 Vac/dc, 2 A
cable gland M16
ambient temperature 0...50 °C
housing IP54, cable gland downwards
COnDenSAtIOn SWItCH0...10 v output, relay output
KA 10 1187030 condensation switch
KA 10-EXT 1187031 condensation switch with external sensor, cable length 2 m
LUX 24 is designed for detecting room light level.
LUX 34 is designed for detecting outdoor light level and temperature. Measured values can be used for controlling lighting and heating.
supply 24 Vac, 1 VA
range 0…2000 lux
output 0…10 V < 5 mA or 4…20 mA < 500 Ω
ambient temperature 0…+50 °C
housing IP20
mounting by screws on wall or on junction box
supply 24 Vac/dc, < 0,1 VA
range, light level selectable at commissioning
range, temperature -50…+50 °C
output 1, light level 0…10 V, < 1 mA
output 2, temperature 0…10 V, < 1 mA = -50...+50 °C
ambient temperature -40…+40 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
LUX 24 1133320 light level transmitter
LUX 34 1133310 light level transmitter, selectable range 0...1000 lux or 0...10000 lux
LUX 34-100 1133311 light level transmitter, selectable range 0...100 lux or 0...500 lux
LIgHt LeVeL tRAnSMItteRS
LIgHt LeVeL tRAnSMItteRS
room lux
outdoor lux, °C
4
Type arT no.
Type arT no.
Type arT no.
PRODUAL l 14 l CAtALOgUe
LUX 11 is designed for detecting outdoor light level and temperature. temperature sensor can be either an ntC 10 or ntC 20 thermistor.
range, illumination level 0...800 lux = 30...3 kΩ
range, temperature -50...+50 °C
sensor, illumination level photo resistive cell
sensor, temperature ntC 10 or ntC 20
housing IP54, cable gland downwards
mounting with screws, external lugs
LUX 11 + NTC 10 1133350 illumination and temperature sensor (ntC 10)
LUX 11 + NTC 20 1133351 illumination and temperature sensor (ntC 20)
LIgHt LeVeL SenSORoutdoor lux, °C
MMSP1 is designed for detecting sun light intensity.
supply 5...30 Vdc, 30 mW
range 0...1500 W/m2
accuracy ±5 % (annual mean)
outputs 0...10 Vdc*, 0...3.125 Vdc, 0...150 mVdc or 4...20 mA
housing IP65
* the supply voltage must be at least 12 V
MMSP1 1133360 sun light intensity transmitter
LIgHt IntenSIty tRAnSMItteRoutdoor w/m2
4
Type arT no.
Type arT no.
PRODUAL l 15 l CAtALOgUe
VPeL differential pressure transmitter is designed for detecting water/glycol pressures in heating and cooling systems.
VPL pressure transmitter (3-wire) is designed for detecting fluid pressures in heating and cooling systems.
supply 24 Vac/dc, 1 VA
ranges see type
output 0…10 V, < 5 mA or 4...20 mA < 500 Ω
ambient temperature -20…+70 °C
process connections 8 mm compression fittings for copper pipes
housing IP54
mounting with screws, external lugs, position allowed
only process connectors downwards
zeroing manually by using the push button
supply 24 Vac/dc, 1 VA
range selectable
output 1 0…10 V < 2 mA
output 2 4…20 mA < 800 Ω
ambient humidity non-condensing
ambient temperature 0…+60 °C
housing IP54, cable gland or process connection
downwards
mounting R ½”, wetting parts stainless steel
allowed media fresh water, air, glycol & water, oils
allowed media temperature 0…+85 °C
vPEL 1.0/2.5 1134060 range selectable 0…1.0 or 0…2.5 bar
vPEL 1.0/2.5-N 1134061 with display
vPEL 4.0/6.0 1134070 range selectable 0…4.0 or 0…6.0 bar
vPEL 4.0/6.0-N 1134071 with display
DIFFeRentIAL PReSSURe tRAnSMItteRS FOR WAteR
PReSSURe tRAnSMItteRS FOR WAteR
bar
bar
vPL 16 1134050 pressure transmitter, range selectable 0…2.5, 0…6, 0…10 or 0…16 bar
vPL 16-N 1134051 pressure transmitter with display
vPL 60 1134030 pressure transmitter, range selectable 0…16, 0…25, 0…40 or 0…60 bar
vPL 60-N 1134031 pressure transmitter with display
4
Type arT no.
Type arT no.
PRODUAL l 16 l CAtALOgUe
HDH transmitters are designed for detecting CO2 and temperature in dry room spaces. RH models have also the relative humidity measurement. the CO2 sensor zero point is calibrated regularly by using the ABCLogic™ function.
HDK transmitters are designed for detecting CO2 inside the ventilation ducts. the CO2 sensor zero point is calibrated regularly by using the ABCLogic™ function.
supply 24 Vac/dc, 2,5 VA
range, CO2 0…2000 ppm
range, temperature 0…+50 °C
accuracy, CO2 ±40 ppm +3 % of value
accuracy, temperature ±0,5 °C
outputs 0…10 V, < 2 mA
ambient temperature 0…+50 °C
housing IP20, ABS plastic
mounting with screws on wall or on junction box
supply 24 Vac/dc, 2,5 VA
range CO2 0…2000 ppm
range temperature 0…+50 °C
accuracy ±40 ppm +3 % of value
output 0…10 V, < 2 mA
ambient temperature 0…+50 °C
housing IP54, cable gland downwards
duct mounting in a Ø 10 mm hole, fixing by a flange and screws,
external lugs
HDH 1135040 room transmitter, CO2 and temperature measurement
HDH-N 1135041 room transmitter with display
HDH-C 1135042 controller and calibration tool for HDH
HDH-RH 1135044 room transmitter, CO2, temperature and humidity measurement
HDH-RH-N 1135045 room transmitter with display
HDH-AL3 1135048 option for HDH, 3 leds indicating different CO2 concentrations
HDH-M 1135100 Modbus room transmitter, CO2 and temperature measurement
HDH-M-N 1135101 Modbus room transmitter with display
HDH-M-RH 1135102 Modbus room transmitter, CO2, temperature and humidity measurement
HDH-M-RH-N 1135103 Modbus room transmitter with display
HDHFL 1191150 room transmitter with wireless communication, CO2 and temperature measurement
HDHFL-N 1191151 room transmitter with wireless communication and with display
HDHFL-RH 1191160 room transmitter with wireless communication, CO2, temperature and humidity measurement
HDHFL-RH-N 1191161 room transmitter with wireless communication and with display
HDK 1135050 duct transmitter
HDK-N 1135051 duct transmitter with display
HDK-C 1135052 controller and calibration tool for HDK and HDU
CO2 tRAnSMItteRS
CO2 tRAnSMItteRS
room ppm CO2, °C, % rH
duct ppm CO2, °C
4
Type arT no.
Type arT no.
PRODUAL l 17 l CAtALOgUe
HDU transmitters are designed for detecting CO2 concentration in underground parking garages and parking halls. the CO2 sensor zero point is calibrated regularly by using the ABCLogic™ function.
HML transmitters are designed for detecting carbon monoxide concentration in underground parking garages and parking halls. the measuring is based on electro-chemical cell. the transmitter measuring range is 0…100 or 0…300 ppm.
supply 24 Vac/dc, 2,5 VA
range, CO2 0…2000 ppm
range, temperature -50…+50 °C
accuracy ±40 ppm +3 % of value
outputs 0…10 V, < 2 mA
ambient temperature -30…+50 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
supply 24 Vac/dc, 3 VA
range 0…100 ppm or 0…300 ppm CO
accuracy 10 ppm/±10 ppm or 15 % of measured value
output 0…10 V or 4…20 mA
ambient temperature -30…+40 °C
housing IP54, cable gland downwards
mounting with screws, external lugs
Type arT no.
HDU 1135090 CO2 transmitter for cold spaces
HDU-N 1135091 CO2 transmitter with display
HDK-C 1135052 controller and calibration tool for HDK and HDU
CO2 tRAnSMItteRS
CARBOn MOnOXIDe tRAnSMItteRS
outdoor ppm CO2, °C
outdoor ppm CO
HML 1135520 CO transmitter
HML-N 1135521 CO transmitter with display
HMv 1135510 exchange kit for HML
HML-C 1135522 calibration tool for HML
HM-vS 1135523 flow controller for HML
HM-KK 1135524 reference gas for HML
4
Type arT no.
PRODUAL l 18 l CAtALOgUe
tUnA 20 is designed for measuring wind speed and outside air temperature.
supply 24 Vac/dc, < 1,5 VA
range, velocity 0...20 m/s
range, temperature -50…+50 °C
outputs 0...10 V, < 2mA
4...20 mA, < 600 Ω
ambient temperature -50…+50 °C
housing IP54 (transmitter)
mounting wall mounting with screws
TUNA 20 1136010 wind speed detector
WInD SPeeD DeteCtOR m/s, °C
UV7 ultrasonic wind sensor is designed for measuring wind speed and direction in HVAC applications. the sensor is robust and stable.
supply 24 Vdc/ac
range, wind direction 0...359°
range, wind speed 0.1...15 m/s or 0.1...30 m/s
accuracy, wind direction ±1°
accuracy, wind speed ±0.1 m/s
outputs 3 x 0...10 Vdc
RS232 nMeA0183®
ambient temperature -10...+55 °C
housing IP67
Uv7 1136030 wind sensor
Uv7-B 1136031 wind sensor bracket for Ø50 mm mast
Uv7-vv 1136032 transmitter module for wind sensor
WInD SenSOR m/s, °
VS 3000 wind sensor is designed for measuring wind speed and direction in HVAC applications.
supply 24 Vac/dc
range, wind direction 0...360 <°
range, wind speed 0...35 m/s
output 0...10 Vdc
ambient temperature -35...+70 °C
housing IP65
vS 3000 1136040 wind speed and direction sensor
vH 1000 1136050 wind speed sensor
vR 1000 1136060 wind direction sensor
WInD SenSOR m/s, °
4
Type arT no.
Type arT no.
Type arT no.
PRODUAL l 19 l CAtALOgUe
SA 10 is designed for detecting and monitoring rain in HVAC applications.
supply 24 Vac/dc, < 5 VA
range weak rain approx. 1 V, 0,5 mm/h
normal rain approx. 2…3 V
heavy rain approx. 3…10 V
outputs 0…10 V, < 2 mA
relay nO 60 Vdc, 0,1 A
ambient temperature range -40…+50 °C
housing IP54
mounting by a band to a mast (Ø 25…60 mm) or by
screws on the wall (hole distance 68 mm)
SA 10 1136020 rain sensor
RAIn SenSOR
BAK 64 binary step controller is designed for controlling electric heating power. It can be used with all systems with 0…10 V outputs. Relays like AR 1 or Ry 1 are needed for contact outputs. Power steps must be in binary sequence e.g. 1, 2, 4, 8, 16, 32 kW.
supply 24 Vac, 3 VA
input 0…10 Vdc or 10…0 Vdc, selectable
outputs 1-6 < 40 Vdc 100 mA, valid for AR 1 and Ry 1 relays
delay between steps adjustable, 0,7…60 s
housing IP20, 11-pole relay housing
eLeCtRIC POWeR RegULAtIOn
BAK 64 1140010 binary step controller
AR 1 1183010 relay, normally open (no) contact 230 Vac, 10 A
RY 1 1183020 relay, change-over contact 230 Vac, 10 A
4
Type arT no.
Type arT no.
5
PRODUAL l 20 l CAtALOgUe
StS 4 converts 0…10 V signal to one time proportional and up to 3 contact outputs. each step must be identical in power.
HLS 16 is a 1-stage controller for room temperature control. Both heating and cooling are controlled by using the same valve. the function of the valve can be changed by using external (summer/winter) switch connected to the Z1 terminal.
StS 1 controls time proportionally electric power of heaters in cycles of 20 s.
supply 24 Vac, 1 VA
input 0…10 Vdc < 1 mA
output 1 for solid state relay 15 Vdc < 50 mA, time proportional
outputs 2-4 40 Vdc < 100 mA, valid for AR 1 and Ry 1 relays
number of steps selectable, 1-4 pcs
housing IP20, 11-pole relay housing
supply 24 Vac, 1 VA
input 0…10 Vdc < 1 mA
output 230 Vac < 4 A, time proportional (cycle 20 s)
housing IP20, for 35 mm DIn rail
dimensions 22 x 77 x 51 mm
eLeCtRIC POWeR RegULAtIOn
teMPeRAtURe COntROLLeRS
eLeCtRIC POWeR RegULAtIOn
room °C
STS 1 1140040 time proportional power controller
STS 4 1140020 electric power controller
PR 50/440 1140030 solid state relay 230…400 Vac, < 25 A, input 8…32 Vdc
PR 10/440 1140060 solid state relay 230…400 Vac, < 10 A, input 3…32 Vdc
PRMK 1140070 solid state relay control signal converter, Vac -> Vdc
AR 1 1183010 relay, normally open (no) contact 230 Vac, 10 A
RY 1 1183020 relay, change-over contact 230 Vac, 10 A
PJR 4 1140050 solid state relay, input 24 Vac/dc, output 230 Vac < 4 A, IP20, for 35 mm DIn rail
HLS 16 1150160 controller for floor heating/cooling
HLS 16-N 1150161 with display
supply 24 Vac, 2 VA
set point +18…+24 °C, ±3°C
accuracy ±0,5 °C
outputs A1 (nC) and A2 (nO) 24 Vac, 1 A for thermal actuator
ambient temperature 0…+50 °C
housing IP20, ABS plastic
mounting with screws on wall or on a junction box
(hole distance 60 mm)
StS 4 PR 50/440 Ry 1
5
Type arT no.
Type arT no.
Type arT no.
6
PRODUAL l 21 l CAtALOgUe
HLS 21 is a 2-stage controller for room temperature control. the controller has one thermal (PWM) actuator stage for both heating and cooling.
HLS 33 is a room temperature controller with 2 or 3 stages. One stage is for heating and up to two stages for cooling. the controllers can be used with 0…10 V, 3-point or thermal (PWM) actuators.
supply 24 Vac, 2 VA
set point +18…+24 °C, ±3 °C
output A1, cooling 24 Vac < 1 A thermal actuator
output A2, heating 24 Vac < 1 A thermal actuator
ambient temperature 0…+50 °C
housing IP20, ABS plastic
mounting with screws on wall or on a junction box
(hole distance 60 mm)
supply 24 Vac, 2 VA
set point +18…+24 °C, ±3 °C
output y1, cooling 0…10 V / 10…0 V < 2 mA
output y2, heating 0…10 V / 10…0 V < 2 mA
output A1, cooling 24 Vac < 1 A, 3-point or thermal actuator
output A2, heating 24 Vac < 1 A, 3-point or thermal actuator
ambient temperature 0…+50 °C
housing IP20, ABS plastic
mounting with screws on wall or on a junction box
(hole distance 60 mm)
HLS 21 1150100 controller with internal temperature sensor
HLS 21-N 1150101 with display
HLS 21-EXT 1150102 controller for an external ntC10 temperature sensor
HLS 21-N-EXT 1150103 controller for an external ntC10 temperature sensor and display
teMPeRAtURe COntROLLeRS
teMPeRAtURe COntROLLeRS
room °C
room °C
HLS 33 1150090 controller with internal temperature sensor
HLS 33-N 1150091 with display
HLS 33-EXT 1150092 controller for an external ntC10 temperature sensor
HLS 33-N-EXT 1150093 for an external ntC10 temperature sensor with display
TH 5 1183090 driver for thermal actuators
External NTC 10 temperature sensor, e.g. TEKHA NTC 10.
6
Type arT no.
Type arT no.
PRODUAL l 22 l CAtALOgUe
HLS 34 is a room temperature controller with RS-485 connection for Modbus RtU communication. the set point and fan speed can be adjusted by using the display and push buttons. Commissioning can be made by using push buttons or by using HLS 34-SeR configuration tool. e.g. occupancy or CO2 sensor can be connected to the controller.
HLS 35 is a controller for floor heating and cooling. HLS 35 is especially suitable for floor heating and cooling applications when there is a possibility to change the supply water from heating to cooling in the summer time. the controller has RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc < 1 VA
nOte: Only the 0…10 V outputs and Modbus work
when using DC supply voltage.
set point adjusting by push buttons or by modbus communication
output y1, cooling 0…10 V / 10…0 V < 2 mA
output y2, heating 0…10 V / 10…0 V < 2 mA
output A1, cooling 24 Vac < 1 A, 3-point or thermal actuator
output A2, heating 24 Vac < 1 A, 3-point or thermal actuator
ambient temperature 0…+50 °C
housing IP20
mounting with screws on wall or on a junction box
(hole distance 60 mm)
teMPeRAtURe COntROLLeRS
teMPeRAtURe COntROLLeRS
room °C
floor °C
HLS 34 1150110 room temperature controller with Modbus, contains display, 4 buttons
HLS 34-2B 1150112 like HLS 34, buttons: + and -
HLS 34-3B 1150113 like HLS 34, buttons: +, - and day extension
HLS 34 -SER 1150111 configuration tool for HLS 34
TH 5 1183090 driver for thermal actuators
FCRY 3 1183070 fan coil relay
External NTC 10 temperature sensor, e.g. TEKHA NTC 10.
supply 24 Vac/dc, < 1 VA
nOte: Only the 0…10 V output and
Modbus work when using DC supply voltage.
input, return water 1 x ntC 10 temperature
input, summer/winter 1 x digital input
output, control valve 1 x 0…10 Vdc
output, heating/cooling 24 Vac, < 1 A, 3-point or thermal actuator
ambient temperature 0…+50 °C
housing IP20
mounting with screws on wall or on a junction box
(hole distance 60 mm)
HLS 35 1150130 room temperature controller for floor heating (modbus), contains display
TEL NTC 10 1175280 floor sensor with 3 m cable
6Type arT no.
Type arT no.
PRODUAL l 23 l CAtALOgUe
HLS44 is a multifunctional controller designed especially for individual room temperature and zone control applications. Controller has a galvanically isolated RS-485 connection for Modbus RtU communication.
HLS44-V is a multifunctional controller designed especially for individual room temperature and light control applications. Controller has a galvanically isolated RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc, < 1 VA
nOte: Only the 0…10 V outputs and Modbus work
when using DC supply voltage.
set point adjusting by push buttons or by modbus communication
output y1, VAV 0...10 V < 2 mA
output y2, fan 0...10 V < 2 mA
output y3, cooling 0…10 V / 10...0 V < 2 mA
output y4, heating 0…10 V / 10...0 V < 2 mA
output A1, cooling 24 Vac < 1 A, thermal actuator
output A2, heating 24 Vac < 1 A, thermal actuator
ambient temperature 0…+50 °C
mounting with screws on wall or on a junction box
housing IP20
supply 24 Vac/dc, < 1 VA
nOte: Only the 0…10 V outputs and Modbus work
when using DC supply voltage.
set point adjusting by push buttons or by modbus communication
output y1, VAV 0...10 V < 2 mA
output y2, fan 0...10 V < 2 mA
output A1, cooling 24 Vac < 1 A, thermal actuator
output A2, heating 24 Vac < 1 A, thermal actuator
output B1, on/off damper 24 Vac < 0,5 A
output B2, light control 24 Vac < 0,5 A
ambient temperature 0…+50 °C
mounting with screws on wall or on a junction box
housing IP20
HLS 44 1150250 room temperature controller with Modbus communication
FCRY 3 1183070 fan coil relay
HLS 44-SER 1150251 configuration tool for HLS 44
HLS 44-v 1150260 room temperature controller for fan coil VAV and lights, Modbus communication
FCRY 3 1183070 fan coil relay
RYvA 16 1183060 relay for fluorescent lamps 230 V, 16 A
HLS 44-SER 1150251 configuration tool for HLS 44
teMPeRAtURe COntROLLeRS
teMPeRAtURe COntROLLeRS
room °C
room °C
6Type arT no.
Type arT no.
PRODUAL l 24 l CAtALOgUe
PDS 2 is a temperature controller for air handling unit, hot domestic water and heating applications. the controller supports Pt1000 temperature sensors. the thermal actuators can be either 0...10 V controlled or 3-point controlled. Configuration, settings and monitoring can be made by using display and push buttons. the controller has RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc < 2 VA
inputs 3 x Pt1000 or 2 x Pt1000 + 1 x potentiometer
1 x 0…10 V / digital
outputs 3 or 4 x 0…10 Vdc, 2 mA
4 x 24 Vac 1 A triac
housing IP20, for 35 mm DIn rail
dimensions 53 x 90 x 58 mm
teMPeRAtURe COntROLLeRS°C
PDS 2 1150120 controller
TEAT PT 1000 1174070 immersion water sensor
AT 80 1170010 pocket
TEHR PT 1000 1174190 room sensor IP20
TEK PT 1000 1174040 duct sensor IP54
TENA PT 1000 1174050 domestic water sensor
TEP PT 1000 1174080 pipe strap-on sensor
TEU PT 1000 1174090 outdoor sensor IP54
TEHR PT 1000-P/PDS 2 1174231 room sensor + set point for PDS 2, IP20
HLS 45 is a versatile room controller for individual room temperature and VAV control applications. HLS 45 is excellent for both 2-pipe FCU and floor heating and cooling applications.the controller has a galvanically isolated RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc, < 1 VA
nOte: Only the 0…10 V outputs and Modbus work
when using DC supply voltage.
set point adjusting by push buttons or by modbus communication
outputs 0...10 V < 2 mA for VAV
0...10 V < 2 mA for fan
0…10 V < 2 mA for heating/cooling valve control
2 x 24 Vac < 1 A for thermal actuators or 3-point actuator
ambient temperature 0…+50 °C
mounting with screws on wall or on a junction box
housing IP20, ABS plastic
HLS 45 1150270 room temperature controller with Modbus communication
FCRY 3 1183070 fan coil relay
HLS 45-SER 1150271 configuration tool for HLS 45
teMPeRAtURe COntROLLeRSroom °C
6 Type arT no.
Type arT no.
PRODUAL l 25 l CAtALOgUe
HS 2.2 is a universal controller designed for HVAC applications. It can be used for controlling e.g. pressure, differential pressure, temperature or illumination level. Display is possible to scale according to the measurement.
UnIVeRSAL COntROLLeRS °C, % rH, Pa, bar, CO, CO2, m/s, lux
supply 24 Vac/dc, < 1VA
nOte: Only the 0…10 V outputs work when using
DC supply voltage.
inputs 1 x 0…10 V, 10 kΩ
1 x DI, potential free
outputs 1 x 0…10 Vdc, 2 mA
1 x 0/10 Vdc
1 x 24 Vac, < 1 A, for thermal or 3-point actuators
housing IP20, ABS plastic
mounting with screws on wall or on a junction box
(hole distance 60 mm)
HS 2.2 1150240 universal controller, room housing
PDS 2.2 universal controller can be used for controlling e.g. pressure, humidity or temperature. the controller supports 0…10 V controlled, 3-point controlled or thermal actuators. Configuration, settings and monitoring can be made by using display and push buttons. the controller has RS-485 connection for Modbus RtU communication.
supply 24 Vac/dc, < 2 VA
inputs 0…10 V measurement
0…10 V external set point setting
outputs 1 x 0…10 Vdc, 2 mA
2 x 24 Vac, < 1 A, for thermal or 3-point actuators
1 x 10 Vdc, 2 mA, for 4,7...220 kΩ potentiometer
housing IP20, for 35 mm DIn rail
dimensions 53 x 90 x 58 mm
PDS 2.2 1150150 universal controller
UnIVeRSAL COntROLLeRS °C, % rH, Pa, bar, CO, CO2, m/s, lux
7
Type arT no.
Type arT no.
PRODUAL l 26 l CAtALOgUe
PRODUAL l 27 l CAtALOgUe
teAt immersion water temperature sensors are designed for detecting heating and cooling water temperatures. Sensor is always installed to a pocket.
mounting R ½” (Produal pocket)
range -50…+120 °C
time constant 5 s
housing IP54, stem or cable gland downwards
cable gland M16
pressure rating Pn16 (Produal pocket)
materials PBt, PC, PA, acid proof steel
mounting depth 80 mm
several other mounting depths also available
for example 300 mm (e.g. teAt Pt 1000-300)
HeAtIng/COOLIng WAteR SenSORS
°C
TEAT PT 100 1173070 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEAT PT 1000 1174070 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEAT NTC 1.8 117e070 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEAT NTC 2.2 1172070 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEAT NTC 10 1175070 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEAT NTC 10-KB 117B070 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEAT NTC 10-AN 117H070 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEAT NTC 10-C 117M070 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEAT NTC 20 1176070 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEAT NI 1000-LG 1178070 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEAT NI 1000 117C070 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEAT KP 10 117J070 LM335Z, 10 mV/K, 2,98 V / 25 °C
TEAT LL 1177070 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEAT LU 1179070 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
poCKeTS
AT 80 1170010 pocket, stainless steel (AISI 303), Ø 8 mm x 90 mm
ATM 80 1170030 pocket, brass (Ms 362), Ø 8mm x 90mm
ATH 80 1170020 pocket, acid proof steel (AISI 316L), Ø 8 mm x 90 mm
ATS 80 1170025 pocket, acid proof steel (AISI 316ti), sea water resistant, Ø 8 mm x 90 mm
ATH 300 1170021 pocket, acid proof steel (AISI 316L), Ø 8 mm x 310 mm
Type arT no.
8
PRODUAL l 28 l CAtALOgUe
tenA sensors are designed for detecting hot domestic water temperatures with fast response.
mounting R ½”
range -50…+120 °C
time constant 2,5 s
housing IP54, stem or cable gland downwards
cable gland M16
pressure rating Pn16
materials PBt, PC, PA, stainless steel
mounting depth 80 mm
50 mm (e.g. tenA ntC 10-50)
210 mm (e.g. tenA ntC 10-210)
HOt DOMeStIC WAteR SenSORS°C
TENA PT 100 1173050 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TENA PT 100-50 1173051 like sensor above, stem length 50 mm
TENA PT 1000 1174050 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TENA PT 1000-50 1174051 like sensor above, stem length 50 mm
TENA NTC 1.8 117e050 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TENA NTC 1.8-50 117e051 like sensor above, stem length 50 mm
TENA NTC 2.2 1172050 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TENA NTC 2.2-50 1172051 like sensor above, stem length 50 mm
TENA NTC 10 1175050 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TENA NTC 10-50 1175051 like sensor above, stem length 50 mm
TENA NTC 10-KB 117B050 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TENA NTC 10-KB-50 117B051 like sensor above, stem length 50 mm
TENA NTC 10-AN 117H050 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TENA NTC 10-AN-50 117H051 like sensor above, stem length 50 mm
TENA NTC 10-C 117M050 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TENA NTC 10-C-50 117M051 like sensor above, stem length 50 mm
TENA NTC 20 1176050 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TENA NTC 20-50 1176051 like sensor above, stem length 50 mm
TENA NI 1000-LG 1178050 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TENA NI 1000-LG-50 1178051 like sensor above, stem length 50 mm
TENA NI 1000 117C050 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TENA NI 1000-50 117C051 like sensor above, stem length 50 mm
TENA LL 1177050 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5°C
TENA LL-50 1177051 like sensor above, stem length 50 mm
TENA LU 1179050 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5°C
TENA LU-50 1179051 like sensor above, stem length 50 mm
TE-N 1170130 display option for LL and LU transmitters
8
Type arT no.
PRODUAL l 29 l CAtALOgUe
8
teV sensors are designed for frost protection and for applications with fast response.
mounting R ¼”
range -50…+120 °C
time constant 2,5 s
cable 2 m LIyy 2 x 0,14
materials acid proof steel
pipe connector brass
pressure rating Pn16
mounting depth < 200 mm (also available < 400 mm)
FROSt gUARD SenSORS°C
Type arT no.
TEv PT 100 1173020 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEv PT 1000 1174020 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEv NTC 1.8 117e020 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEv NTC 2.2 1172020 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEv NTC 10 1175020 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEv NTC 10-KB 117B020 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEv NTC 10-AN 117H020 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEv NTC 10-C 117M020 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEv NTC 20 1176020 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEv NI 1000-LG 1178020 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEv NI 1000 117C020 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEv LL 1177020 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEv LU 1179020 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
teKV sensors are designed for frost protection and for applications with fast response.
mounting R ¼”
range -50…+120 °C
time constant 2,5 s
housing IP54, stem or cable gland downwards
cable gland M16
materials PBt, PC, PA, acid proof steel
pipe connector brass
mounting depth < 200 mm (also available < 400 mm)
FROSt gUARD SenSORS°C
Type arT no.
TEKv PT 100 1173120 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKv PT 1000 1174120 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKv NTC 1.8 117e120 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKv NTC 2.2 1172120 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKv NTC 10 1175120 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKv NTC 10-KB 117B120 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEKv NTC 10-AN 117H120 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKv NTC 10-C 117M120 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKv NTC 20 1176120 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKv NI 1000-LG 1178120 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKv NI 1000 117C120 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKv LL 1177120 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKv LU 1179120 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
PRODUAL l 30 l CAtALOgUe
teP sensors are designed for pipe strap-on installations in heating and cooling applications.
mounting by a band on the pipe (diam.< 90 mm)
range -50…+120 °C
time constant approx. 5 s
housing IP54, stem or cable gland downwards
cable gland M16
materials PBt, PC, PA, zink casting
StRAP-On SenSORS°C
Type arT no.
TEP PT 100 1173080 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEP PT 1000 1174080 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEP NTC 1.8 117e080 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEP NTC 2.2 1172080 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEP NTC 10 1175080 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEP NTC 10-KB 117B080 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEP NTC 10-AN 117H080 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEP NTC 10-C 117M080 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEP NTC 20 1176080 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEP NI 1000-LG 1178080 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEP NI 1000 117C080 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEP KP 10 117J080 LM335Z, 10 mV/K, 2,98 V / 25 °C
TEP LL 1177080 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEP LU 1179080 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
8
tePK sensors are designed for pipe strap-on installations in heating and cooling applications.
mounting by a band on the pipe (Ø10...100 mm)
range -20…+80 °C
time constant about 5 s
material zinc casting
cable 2 m (LIyy 2 x 0,14) PVC cable
StRAP-On SenSORS°C
Type arT no.
TEPK PT 100 1173240 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEPK PT 1000 1174240 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEPK NTC 1.8 117e240 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEPK NTC 2.2 1172240 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEPK NTC 10 1175240 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEPK NTC 10-KB 117B240 5025 kΩ / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEPK NTC 10-AN 117H240 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEPK NTC 10-C 117M240 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEPK NTC 20 1176240 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEPK NI 1000-LG 1178240 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEPK NI 1000 117C240 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEPK LL 1177240 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEPK LU 1179240 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
PRODUAL l 31 l CAtALOgUe
8
teK sensors are designed for detecting temperatures inside ventilation ducts.
mounting with flange, adjustable < 200 mm
range -50…+70 °C
housing IP54, stem or cable downwards
cable gland M16
materials PBt, PC, PA, stainless steel
DUCt SenSORS°C
TEK PT 100 1173040 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEK PT 1000 1174040 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEK NTC 1.8 117e040 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEK NTC 2.2 1172040 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEK NTC 10 1175040 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEK NTC 10-KB 117B040 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEK NTC 10-AN 117H040 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEK NTC 10-C 117M040 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEK NTC 20 1176040 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEK NI 1000-LG 1178040 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEK NI 1000 117C040 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEK KP 10 117J040 LM335Z, 10 mV/K, 2,98 V / 25 °C
TEK LL 1177040 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEK LU 1179040 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
Type arT no.
teKHA sensors are designed for detecting temperatures inside small ventilation ducts.
mounting with flange, adjustable < 100 mm
range -50…+70 °C
stem Ø6 mm x 100 mm, acid proof steel
cable 2 m (LIyy 2 x 0,14) PVC cable
other lengths to order
DUCt SenSORS°C
Type arT no.
TEKHA PT 100 1173290 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKHA PT 1000 1174290 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKHA NTC 1.8 117e290 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKHA NTC 2.2 1172290 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKHA NTC 10 1175290 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKHA NTC 10-AN 117H290 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKHA NTC 10-C 117M290 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKHA NTC 20 1176290 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKHA NI 1000-LG 1178290 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKHA NI 1000 117C290 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKHA KP 10 117J290 LM335Z, 10 mV/K, 2,98 V / 25 °C
PRODUAL l 32 l CAtALOgUe
teKA sensors are designed for detecting temperatures inside large ducts. Sensor’s mechanical construction ensures accurate average temperature measurement.
mounting with flange and springs
range -50…+70 °C
length 3 m
housing IP54, stem or cable downwards
cable gland M16
materials PBt, PC, PA, stainless steel
DUCt SenSORS°C
Type arT no.
TEKA PT 100 1173130 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKA PT 1000 1174130 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKA NTC 1.8 117e130 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKA NTC 2.2 1172130 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKA NTC 10 1175130 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKA NTC 10-KB 117B130 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEKA NTC 10-AN 117H130 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKA NTC 10-C 117M130 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKA NTC 20 1176130 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKA NI 1000-LG 1178130 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKA NI 1000 117C130 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKA LL 1177130 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKA LU 1179130 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
8
PRODUAL l 33 l CAtALOgUe
8
teKA-500 sensors are designed for detecting temperatures inside ventilation ducts. Sensor detects the average temperature with 4 sensor elements.
mounting with flange
range -50…+70 °C
stem length 500 mm
housing IP54, stem or cable downwards
cable gland M16
materials PBt, PC, PA, stainless steel
DUCt SenSORS°C
Type arT no.
TEKA PT 100-500 1173170 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKA PT 1000-500 1174170 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKA NTC 1.8-500 117e170 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKA NTC 2.2-500 1172170 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKA NTC 10-500 1175170 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKA NTC 10-KB-500 117B170 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEKA NTC 10-AN-500 117H170 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKA NTC 10-C-500 117M170 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKA NTC 20-500 1176170 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKA NI 1000-LG-500 1178170 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKA NI 1000-500 117C170 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKA LL-500 1177170 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKA LU-500 1179170 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TE-N 1170130 display option for LL and LU transmitters
PRODUAL l 34 l CAtALOgUe
teKy4 temperature sensors are designed for detecting temperatures in automatic HVAC systems. the rolled stainless steel sleeve provides good protection against water and dust.
range -30…+80 °C
cable Ø 3.2 mm x 2.3 m, PVC
other lengths also available
sleeve Ø 4 mm x 30 mm, stainless steel
protection class IP67
CABLe teMPeRAtURe SenSORS°C
Type arT no.
TEKY4 PT 100 1173330 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKY4 PT 1000 1174330 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKY4 NTC 1.8 117e330 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKY4 NTC 2.2 1172330 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKY4 NTC 10 1175330 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKY4 NTC 10-KB 117B330 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEKY4 NTC 10-AN 117H330 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKY4 NTC 10-C 117M330 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKY4 NTC 20 1176330 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKY4 NI 1000-LG 1178330 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKY4 NI 1000 117C330 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKY4 LL 1177330 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKY4 LU 1179330 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C8
PRODUAL l 35 l CAtALOgUe
teKy6 and teKy6S temperature sensors are designed for detecting temperatures in automatic HVAC systems. the rolled stainless steel sleeve provides good protection against water and dust.
teKy6: range -30…+80 °C
cable Ø 5 mm x *2.3 m, PVC
teKy6S: range -50…+150 °C
cable Ø 5 mm x *2.3 m, silicone
sleeve Ø 6 mm x 45 mm, stainless steel
protection class IP67
* other lengths also available
CABLe teMPeRAtURe SenSORS°C
Type arT no.
TEKY6 PT 100 1173320 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKY6 PT 1000 1174320 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKY6 NTC 1.8 117e320 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEKY6 NTC 2.2 1172320 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEKY6 NTC 10 1175320 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKY6 NTC 10-KB 117B320 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEKY6 NTC 10-AN 117H320 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEKY6 NTC 10-C 117M320 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEKY6 NTC 20 1176320 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEKY6 NI 1000-LG 1178320 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKY6 NI 1000 117C320 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKY6 KP 10 117J320 LM335Z, 10 mV/K, 2,98 V / 25 °C
TEKY6 LL 1177320 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKY6 LU 1179320 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TEKY6S PT 100 1173340 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEKY6S PT 1000 1174340 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEKY6S NTC 10 1175340 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEKY6S NI 1000-LG 1178340 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEKY6S NI 1000 117C340 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEKY6S LL 1177340 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEKY6S LU 1179340 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
8
PRODUAL l 36 l CAtALOgUe
teL sensors are designed for detecting floor temperatures. the sensor is installed in the cable duct inside the floor construction.
range -30…+70 °C
cable 3 m (LIyy 2 x 0,5) PVC cable
other lengths also available
sleeve Ø 7 mm
CABLe teMPeRAtURe SenSORS, FLOOR
°C
Type arT no.
TEL PT 100 1173280 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEL PT 1000 1174280 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEL NTC 1.8 117e280 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEL NTC 2.2 1172280 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEL NTC 10 1175280 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEL NTC 10-AN 117H280 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEL NTC 10-C 117M280 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEL NTC 20 1176280 0 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEL NI 1000-LG 1178280 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEL NI 1000 117C280 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEL KP 10 117J280 LM335Z, 10 mV/K, 2,98 V / 25 °C
teM sensors are designed for detecting temperatures in road ramps and street constructions. the sensor must be installed in a cable duct.
range -30…+80 °C
cable 5 m (PUR 2 x 0,75)
other lengths also available
sleeve Ø 9 mm
CABLe teMPeRAtURe SenSORS, SOIL InStALLAtIOn
°C
Type arT no.
TEM PT 100 1173310 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEM PT 1000 1174310 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEM NTC 1.8 117e310 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEM NTC 2.2 1172310 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEM NTC 10 1175310 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEM NTC 10-AN 117H310 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEM NTC 10-C 117M310 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEM NTC 20 1176310 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEM NI 1000-LG 1178310 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEM NI 1000 117C310 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEM KP 10 117J310 LM335Z, 10 mV/K, 2,98 V / 25 °C
8
PRODUAL l 37 l CAtALOgUe
teSK sensors are designed for detecting combustion gas temperatures.
teHR sensors are designed for detecting room temperatures.
mounting R ½” or with flange on order
range 0…+400 °C
housing silumin cast, IP54, stem or cable gland downwards
cable gland Pg16
pressure rating Pn16
mounting with screws on wall
or on a junction box (hole distance 60 mm)
range 0...+50 °C
housing IP20, ABS plastic
options push button, 5-position switch, LeD-lamp, display
COMBUStIOn gAS SenSORS
ROOM teMPeRAtURe SenSORS
°C
°C
Type arT no.
Type arT no.
TESK PT 100 1173160 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TESK PT 1000 1174160 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TESK LL 0/400 1177160 2-wire transmitter, supply 22...35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TESK LU 0/400 1179160 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TEHR PT 100 1173190 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEHR PT 1000 1174190 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEHR NTC 1.8 117e190 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEHR NTC 2.2 1172190 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEHR NTC 10 1175190 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEHR NTC 10-KB 117B190 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEHR NTC 10-AN 117H190 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEHR NTC 10-C 117M190 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEHR NTC 20 1176190 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEHR NI 1000-LG 1178190 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEHR NI 1000 117C190 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEHR KP 10 117J190 LM335Z, 10 mV/K, 2,98 V / 25 °C
opTionS:
TEHR-S 1170080 push button (no / nc) 24 Vac/dc
TEHR-S5 1170090 5-position switch (1, 2 ,3, 0, A) 24 Vac/dc
TEHR-L 1170100 LeD 24 V
TEHR-N 1171140 digital display, input 0…10 V=0…50 °C
8
PRODUAL l 38 l CAtALOgUe
teHR-P sensors are designed for detecting room temperatures and setting the set point to the controller.
mounting with screws on wall or on a junction box
(hole distance 60 mm)
range 0...+50 °C
potentiometer to order
resistors to order
housing IP20, ABS plastic
options push button, 5-position switch, LeD lamp, display
ROOM teMPeRAtURe SenSORS°C + set point setting
Type arT no.
TEHR PT 100-P 1173230 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEHR PT 1000-P 1174230 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEHR NTC 1.8-P 117e230 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEHR NTC 2.2-P 1172230 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEHR NTC 10-P 1175230 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEHR NTC 10-AN-P 117H230 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEHR NTC 10-C-P 117M230 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEHR NTC 20-P 1176230 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEHR NI 1000-LG-P 1178230 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEHR NI 1000-P 117C230 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEHR KP 10-P 117J230 LM335Z, 10 mV/K, 2,98 V / 25 °C
opTionS:
TEHR-S 1170080 push button (no / nc) 24 Vac/dc
TEHR-S5 1170090 5-position switch (1, 2, 3, 0, A) 24 Vac/dc
TEHR-L 1170100 LeD 24 V
TEHR-N 1170140 digital display, input 0…10 V=0…50 °C
teHR LL (2-wire, 4…20 mA) and teHR LU (3-wire, 0…10 V) are temperature transmitters for dry room spaces. the output range is selectable. the teHR-M output is available as a 0...10 V signal and via Modbus.
mounting with screws on wall or on a junction box (hole distance 60 mm)
range 0...+50 °C
sensor Pt1000 en 60751/B
accuracy ±0,5 °C / 0 °C
potentiometer to order
housing IP20, ABS plastic
ROOM teMPeRAtURe SenSORS°C
Type arT no.
TEHR LL 1177190 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA
TEHR LL-N 1177191 with display
TEHR LL-P 1177230 2-wire transmitter, supply 22…35 Vdc, output 4…20 mA, potentiometer
TEHR LL-N-P 1177231 with display, potentiometer
TEHR LU 1179190 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA
TEHR LU-N 1179191 with display
TEHR LU-P 1179230 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, potentiometer
TEHR LU-N-P 1179231 with display, potentiometer
TEHR-M 1170600 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, Modbus RtU
TEHR-M-N 1170601 with display, Modbus RtU
8
PRODUAL l 39 l CAtALOgUe
teHU sensors are designed for detecting room temperatures. Flush mounting.
teU sensors are designed for detecting outdoor temperatures.
mounting on a junction box
range 0...+50 °C
housing IP20, ABS plastic
mounting with screws on wall, external lugs
range -50…+50 °C
housing IP54, cable gland downwards
cable gland M16
materials PBt, PC, PA
ROOM teMPeRAtURe SenSORS
OUtDOOR teMPeRAtURe SenSORS
°C
°C
Type arT no.
Type arT no.
TEHU PT 100 1173150 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C en 60751/B
TEHU PT 1000 1174150 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEHU NTC 1.8 117e150 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEHU NTC 2.2 1172150 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEHU NTC 10 1175150 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEHU NTC 10-KB 117B150 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEHU NTC 10-AN 117H150 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEHU NTC 10-C 117M150 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEHU NTC 20 1176150 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEHU NI 1000-LG 1178150 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEHU NI 1000 117C150 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEHU KP 10 117J150 LM335Z, 10 mV/K, 2,98 V / 25 °C
TEU PT 100 1173090 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TEU PT 1000 1174090 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TEU NTC 1.8 117e090 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TEU NTC 2.2 1172090 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TEU NTC 10 1175090 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TEU NTC 10-KB 117B090 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TEU NTC 10-AN 117H090 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TEU NTC 10-C 117M090 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TEU NTC 20 1176090 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TEU NI 1000-LG 1178090 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TEU NI 1000 117C090 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TEU KP 10 117J090 LM335Z, 10 mV/K, 2,98 V / 25 °C
8
PRODUAL l 40 l CAtALOgUe
teU transmitters are designed for detecting outdoor temperatures.
mounting with screws on wall, external lugs
ranges -50…+50, -50…+150, 0…+50, 0…+100 °C
housing IP54, cable gland downwards
cable gland M16
materials PBt, PC, PA
OUtDOOR teMP SenSORS
Type arT no.
TEU LL 1177090 2-wire transmitter, supply 22...35 Vdc, output 4…20 mA, accuracy ±0,5 °C
TEU LU 1179090 3-wire transmitter, supply 24 Vac/dc, output 0…10 V < 2 mA, accuracy ±0,5 °C
TEU-N 1170131 display option for teU LL and teU LU transmitters
teS sensors are designed for detecting temperatures in dusty, hot and wet (industrial) spaces.
teSIM sensor simulators are designed for simulating temperature sensor when testing a control system.
mounting with screws on wall
range -50…+120 °C
housing silumin cast IP67, cable gland downwards
cable gland Pg11
ranges 5 selectable temperature values
cable with banana jacks
accuracy, Pt1000 ±0,15°C / 0 °C
accuracy, ntC 10 ±0,25°C / 25 °C
housing IP54
InDUStRIAL teMP SenSORS
teMPeRAtURe SenSOR SIMULAtOR
IP 67, °C
Type arT no.
Type arT no.
TES PT 100 1173100 100 Ω / 0 °C, accuracy ±0,3 °C / 0 °C, en 60751/B
TES PT 1000 1174100 1000 Ω / 0 °C, accuracy ±0,3 °C / 0 °C (Honeywell, Danfoss equivalent)
TES NTC 1.8 117e100 1800 Ω / 25 °C, accuracy ±0,3 °C / 25 °C (tAC equivalent)
TES NTC 2.2 1172100 2252 Ω / 25 °C, accuracy ±0,25 °C / 25 °C (Johnson equivalent)
TES NTC 10 1175100 10 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (trend equivalent)
TES NTC 10-KB 117B100 5025 Ω / 25 °C, accuracy ±0,5 °C / 25 °C (Satchwell equivalent)
TES NTC 10-AN 117H100 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Andover equivalent)
TES NTC 10-C 117M100 10 kΩ / 25 °C, accuracy ±0,25 °C / 25 °C (Carel equivalent)
TES NTC 20 1176100 20 kΩ / 25 °C, accuracy ±0,2 °C / 25 °C (Honeywell equivalent)
TES NI 1000-LG 1178100 1000 Ω / 0 °C, accuracy ±0,5 °C / 0 °C (Siemens equivalent)
TES NI 1000 117C100 1000 Ω / 0 °C, accuracy ±0,4 °C / 0 °C (Sauter equivalent)
TES KP 10 117J100 LM335Z, 10 mV/K, 2,98 V / 25 °C
TESIM PT 1000 1170220 Pt1000 simulator
TESIM NTC 10 1170230 ntC 10 simulator
°C
8
PRODUAL l 41 l CAtALOgUe
LLK and LUK are transmitters for temperature measuring. LLK is a 2-wire transmitter converting the sensor resistance to the 4…20 mA signal. LUK is a 3-wire transmitter converting the sensor signal to the 0…10 V signal. the transmitter needs a separatePt1000 sensor.
LLK: supply 22…35 Vdc
output 4…20 mA
LUK: supply 24 Vac/dc < 1 VA
output 0…10 Vdc < 2mA
range selectable
housing IP54
dimensions 115 x 115 x 45 mm
teMPeRAtURe tRAnSMItteRS °C
Type arT no.
LLK 1182190 2-wire transmitter
LLK-N 1182191 2-wire transmitter with display
LUK 1182200 3-wire transmitter
LUK-N 1182201 3-wire transmitter with display
KO IVS is a protective casing for room sensors in spaces like sports halls.Casing is transparent and with a lock.
PROteCtIVe CASIng FOR ROOM SenSOR
Type arT no.
KO IvS KO5239 protective casing for room sensors
8
the casings of room sensors can be delivered painted with special desired colours blending perfectly in the colours of the space.
CASIngS
PRODUAL l 42 l CAtALOgUe
ISO 10 provides galvanic isolation between input and output signals and supply. Signal can also be converted, e.g. a 0…10 V signal into a 4…20 mA signal.
supply 24 Vac/dc
input 0…1 V, 0…10 V, 2…10 V, 0…20 mA or 4…20 mA
output 0…10 V, 2…10 V < 2 mA, 0…20 mA or
4…20 mA < 500 Ω
input impedance at …10 V range < 250 kΩ (I ≤ 50 uA)
input impedance at …20 mA range 100 Ω
isolation voltage < 500 Vdc
ambient temperature -20…+50 °C
housing IP20, for 35 mm DIn rail
dimensions 13 x 111 x 89 mm
tRAnSDUCeRS
Type arT no.
ISO 10 1182060 signal isolator
signal isolator
MIO 12 is an I/O module with a Modbus communication, reading four Pt1000 or digital inputs (MIO 12-Pt) or four 0...10 V or digital inputs (MIO 12-V). Outputs for thermal actuators or two 3-point actuators and also for four 0...10 V signals are available.
DA 6 converts 1...6 digital (contact) inputs into one analogue 0...10 V or 4...20 mA output. the state of each contact can be identified by the control system software.
supply 24 Vac/dc
MIO 12-Pt: inputs 4 x Pt1000 or 4 x potential free digital input
MIO 12-V: inputs 4 x analogue input or 4 x potential free digital input
outputs 4 x 0...10 Vdc, 2 mA; 4 x 24 Vac 1A,
for thermal actuator or two 3-point controller
housing IP20, for 35 mm DIn rail
dimensions 53 x 90 x 58 mm
supply 24 Vac, 1 VA
inputs 1...6 potential free contact inputs
output 1 0...10 Vdc < 10 mA
output 2 4...20 mA
housing IP20, for 35 mm DIn rail
dimensions 68 x 90 x 68 mm
I/O MODULeS
tRAnSDUCeRS
Type arT no.
Type arT no.
MIO 12-PT 1181300 Modbus I/O, 4 analogue inputs (Pt1000 or DI, potential free)
MIO 12-v 1181310 Modbus I/O, 4 analogue inputs (0…10 V)
DA 6 1182040 DI/AO converter
9
PRODUAL l 43 l CAtALOgUe
Jy is a switch mode power supply converting a 24 Vac/dc supply into a lower DC voltage supply. electronic protection for overloading.
PMU 3 converts a 0…10 Vdc signal into a 24 Vac 3-point control signal.
supply 24 Vac/dc
output by coding 10 Vdc, 12 Vdc, 16 Vdc, 18 Vdc,
24 Vdc (only with 24 Vac supply),
ADJ = adjustable 3.6…24 V
loading 1 A
protection electronic overload protection
housing IP20, for 35 mm DIn rail
dimensions 45 x 90 x 58 mm
supply 24 Vac, 1 VA
input 0…10 Vdc < 1 mA
output 24 Vac < 2 A for a 3-point actuator
actuator running time adjustable, 15…240 s
housing IP20, 11-pole relay housing
tRAnSDUCeRS
tRAnSDUCeRS
24 vac/dc 3.6…24 vdc
0…10 v 3-point control
Type arT no.
Type arT no.
JY 1184020 AC/DC to DC converter
PMU 3 1182120 from 0…10 V to 3-point converter
UMP 3 converts a 3-point control signal into a 0…10 Vdc signal.
supply 24 Vac, 1 VA
input 10…40 Vac/dc
output 0…10 Vdc, < 1 mA
output change speed adjustable, 15…240 s
housing IP20, 11-pole relay housing
tRAnSDUCeRS3-point control 0…10 vdc
Type arT no.
UMP 3 1182150 from 3-point to 0...10 V converter
9
PRODUAL l 44 l CAtALOgUe
UV 10 is an amplifier for 0…10 V signals. UV 10 can also be used for controlling fluorescent lamps with electronic transformers.
supply 24 Vac/dc < 0,5 VA
input 0(2)…10 Vdc < 0,5 mA
output 0(2)…10 Vdc < 20 mA,
or inverted (10…0 Vdc)
housing IP20, for 35 mm DIn rail
dimensions 23 x 77 x 45 mm
tRAnSDUCeRS
Type arT no.
Uv 10 1182160 signal amplifier
0…10 v 0…10 v (10…0 v)
PyR 4 converts one 0...10 Vdc signal into two 0…10 V or 10…0 V signals. Output can be restricted with a set point potentiometer if required.
AO 2 and AO 3 are signal converters designed for HVAC applications. the converters divide one 0…10 V signal to two (AO 2) or three (AO 3) 0…10 V signals.
supply 24 Vac 2 VA
input 0…10 Vdc
set point 0…100 % (for restriction)
outputs 0…10 Vdc < 10 mA, (direct and inverted)
housing IP20, 11-pole relay housing
supply 24 Vac/dc, 0,5 VA
input 0...10 Vdc, < 0,2 mA
outputs AO2 0...10 Vdc, 2 mA
y1 0…10 V if In = 0 - 5 …10 V
y2 0…10 V if In = 5…10 V
outputs AO3 0...10 Vdc, 2 mA
y1 0…10 V if In = 0 - 3,3 …10 V
y2 0…10 V if In = 3,3 - 6,6…10 V
y3 0…10 V if In = 6,6…10 V
housing IP20, for 35 mm DIn rail
dimensions 23 x 77 x 41 mm
tRAnSDUCeRS
tRAnSDUCeRS
0…10 vdc 2 x 0…10 vdc with restriction
0…10 vdc 2 x 0…10 vdc / 3 x 0…10 vdc
Type arT no.
Type arT no.
PYR 4 1182130 2-step / limit unit
AO 2 1182220 signal divider, 2 outputs
AO 3 1182210 signal divider, 3 outputs
9
PRODUAL l 45 l CAtALOgUe
M230/24-15 transforms 230 Vac supply to 24 Vac 15 VA supply.
M230/24-30 transforms 230 Vac supply to 24 Vac 30 VA supply.
M230/12-4 transforms 230 Vac supply to 12 Vdc 4 VA supply.
supply 230 Vac, 15 VA
output 1 24 Vac 15 VA
housing IP20, for 35 mm DIn rail
dimensions 35 x 90 x 60 mm
supply 230 Vac, 30 VA
output 24 Vac 1,25 A, fuse protected
housing IP00
dimensions 90 x 90 x 68 mm
supply 230 Vac, 4 VA
output 12 Vdc 0,25 A
housing IP20
tRAnSFORMeRS
tRAnSFORMeRS
tRAnSFORMeRS
230 vac 24 vac, 15 vA
230 vac 24 vac, 30 vA
230 vac 12 vdc, 4 vA
Type arT no.
Type arT no.
Type arT no.
M230/24-15 1184090 transformer
M230/24-30 1184050 transformer
M230/12-4 1184080 power supply
9
PRODUAL l 46 l CAtALOgUe
LA 14 is an occupancy sensor for controlling ventilation and lighting. Intelligent, processor based, logic prevents false functions being at the same time very sensible. Relay function is quiet and the release delay is adjustable.
supply 24 Vac/dc, 15…30 Vac/dc < 0,5 W
angle 120°
housing IP20, white plastic
mounting flush (surface mounting casing optional)
settings:
function modes movement detector/occupancy sensor *
relay contact nC*/nO, < 100 mA, 24 Vac/60 Vdc
delay selectable 2 s, 2 min, 10 min tai 20 min*
* Factory settings
OCCUPAnCy SenSORS
Type arT no.
LA 14 1185050 occupancy sensor
KO PRA KO3602 casing for surface mounting
LA 15 is designed for controlling lighting. Up to 1,5 A continuous fluorescent lighting load is allowed.
supply 24 Vac/dc, 20...28 Vac/dc
angle 120°
housing IP20, white plastic
mounting flush (surface mounting casing optional)
settings:
function modes movement detector*/occupancy sensor
signal relay RE1:
contact nC*/nO, < 100 mA, 24 Vac/60 Vdc
delay 2 s
lighting relay RE2:
contact 230 Vac 1,5 A
delay selectable 2 s, 2 min, 10 min or 20 min*
* Factory settings
OCCUPAnCy SenSORS
Type arT no.
LA 15 1185060 movement / occupancy sensor for switching lighting on/off
LA-RAJ 1185070 180° area guard for occupancy sensor
KO PRA KO3602 casing for surface mounting
9
PRODUAL l 47 l CAtALOgUe
PLt 24 is a detector for monitoring occupancy through body heat and movements. the passive infrared PIR detector reacts to temperature changes in the range of the detection beams.Mounting bracket and screws are included to the delivery.
PLt 12 is a detector for monitoring occupancy through body heat and movements. the detector is passive infrared (PIR) which reacts to temperature changes in range of the detection beams. Mounting bracket and screws are included to the delivery.
supply 24 Vac/dc
alarm output nC*/nO, < 100 mA, 24 Vac/60 Vdc
function modes movement detection*/occupancy detection
ambient temperature -10...+45 °C
housing IP20
delay selectable 2 s*, 2 min, 10 min or 20 min
angle 140°, max. 12 m
* Factory settings
supply 12 Vdc
alarm output nC, < 500 mA, 24 Vdc
ambient temperature -10...+40 °C
housing IP20
angle 140°, max. 12 m
PIR DeteCtORS
PIR DeteCtORS
Type arT no.
PLT 24 1185040 PIR movement detector
PLT 24-K 1185045 PIR movement detector, ceiling mounting
PLT 12 1185080 PIR movement detector
9
Type arT no.
PRODUAL l 48 l CAtALOgUe
LAP timers are designed for extending plant operating hours by pushing a button. the selected time is indicated by an indicator light.
supply 24 Vac or 230 Vac, 2 VA
range LAP 1 12, 24, 36, 48 or 60 minutes
range LAP 5 1, 2, 3, 4 or 5 hours
range LAP 10 2, 4, 6, 8 or 10 hours
output change over contact 230 Vac, 8 A. res.
time measurement accuracy ±10 s/h
housing IP20
mounting on a junction box or on the wall surface,
surface mounting casing included
tIMeRS
Type arT no.
LAP 1 1185025 12…60 minutes (max. time can be restricted to 12…36 minutes)
LAP 5 1185020 1…5 hours (max. time can be restricted to 1…3 hours)
LAP 10 1185021 2…10 hours (max. time can be restricted to 2…6 hours)
LAP 5-T 1185026 as LAP 5, but with a fan On/OFF indication
LAP 10-T 1185028 as LAP 10, but with a fan On/OFF indication
PJP is a low voltage push button device with 1, 2 or 4 buttons and indicator lights.
push button contact < 42 Vac, < 60 Vdc, < 0,8 A
indicator lights green, externally controlled
housing IP20
mounting on a junction box, surface mounting casing not included
LOW VOLtAge PUSH BUttOnS
PJP 1 1185030 1 push button and 1 indicator light
PJP 2 1185031 2 push buttons and 2 indicator lights
PJP 4 1185032 4 push buttons and 4 indicator lights
KO PRA KO3602 casing for surface mounting
9
Type arT no.
PRODUAL l 49 l CAtALOgUe
LeKA 24 is an indicator light device with green and red light.
Ry 1 and AR 1 are relays with a 24 Vac/dc coil voltage. RyVA 16 can be used for lighting control because it withstands a short-term inrush current peak.
input 24 Vac/dc, 0,5 VA
output, led 1 red
output, led 2 green
housing IP20
mounting on a junction box, surface mounting casing not included
input 24 Vac/dc, 0,5 VA
output 230 Vac, 10 A res.
housing IP20, for 35 mm DIn rail
InDICAtOR LIgHtS
ReLAyS
24 vac/dc
coil 24 vac/dc
Type arT no.
Type arT no.
LEKA 24 1185090 indicator light
KO PRA KO3602 casing for surface mounting
AR 1 1183010 relay with normally open (nO) contact, width 13 mm
RY 1 1183020 relay with change-over contact, width 23 mm
RY 1-K 1183021 relay with change-over contact, socket connection at the output
RY 1-KK 1183030 relay with change-over contact and manual switch (On-OFF-A)
RYvA 16 1183060 relay for fluorescent lamps, 16 A (inrush current < 80 A, < 2,5 ms)
Ry 1-U and RyV 16-U are voltage controlled relays with 0…10 V input. RyV 16-U can be used for lighting control because it withstands a short-term inrush current peak.
supply 24 Vac/dc, 1 VA
input 0…10 Vdc < 0,2 mA
output change-over contact 230 Vac, 10 A res.
setpoint adjustable, 0…10 V
hysteresis adjustable 0,2…1,0 V
housing IP20, for 35 mm DIn rail
dimensions 23 x 77 x 41 mm
ReLAySinput 0...10 vdc
Type arT no.
RY 1-U 1183040 voltage controlled relay
RY 1-U-K 1183041 voltage controlled relay, socket connection at the output
RYv 16-U 1183050 voltage controlled relay, 16 A (inrush current < 80 A, < 2,5 ms)
9
PRODUAL l 50 l CAtALOgUe
3-speed relay units for controlling fan coils (fan speed). FCRy 3 is for 0…10 Vdc input, and FCRy 3-R is for 3…7 kΩ input.
tH 5 is a surface mounted driver that can drive several parallel connected thermal actuators.
supply 24 Vac, 1 VA
input (FCRy 3) 0…10 Vdc < 0,2 mA
input (FCRy 3-R) 3…7 kΩ
output contacts 3 x normally open 230 Vac, 10 A res. (cross locked)
set points (FCRy 3) adjustable, factory settings 2.5 V, 5.0 V and 7.5 V
hysteresis (FCRy 3) adjustable 0,2…1,0 V
set points (FCRy 3-R) 3 kΩ = RL4; 4 kΩ = off; 5 kΩ = RL1;
6 kΩ = RL2; 7 kΩ = RL3
housing IP20, for 35 mm DIn rail
dimensions 45 x 90 x 48 mm
supply 24 Vac
input 5...30 Vac/dc, < 10 mA
output 5 x 24Vac, 1 A, total load max. 3 A
housing IP66, for surface mounting
ReLAyS
ReLAyS
for fan coil controls
driver for thermal actuators
Type arT no.
Type arT no.
FCRY 3 1183070 fan coil relay, input 0…10 Vdc
FCRY 3-R 1183080 fan coil relay, input 3…7 kΩ
TH 5 1183090 driver for thermal actuators, 5 outputs
9
PRODUAL l 51 l CAtALOgUe
VVK 2 monitors the status of the water leakage sensors connected to the relay. When the sensor becomes wet the resistance decreases and the alarm relay will be activated. Also the sensor circuit is monitored (alarms if R > 300 kΩ).
LPH 10 monitors the resistance of the sensors. When the sensor becomes wet the resistance decreases and the alarm relay is activated.
VVA and VVn sensors will be used with VVK 2 and LPH 10. the sensors can be installed on the floor and VVn also e.g. on the bottom of the pipe monitoring possible condensation.
supply 24 Vac/dc, 2 VA
measuring range 10 kΩ / 80…300 kΩ, selectable
output change-over contact 60 V, 2 A res.
set point adjustable, LOW < 10 kΩ, HIgH < 80 kΩ
housing IP20, for 35 mm DIn rail
supply 24 Vac/dc
set point fixed, approx. 10 kΩ
output change-over contact 30 Vdc, 1 A res.
alarm indication indicator light and buzzer, with reset button
housing IP20, ABS plastic
dimensions 87 x 86 x 32 mm
sensor resistance approx. 300 kΩ when dry
WAteR LeAKAge ReLAy
WAteR LeAKAge ReLAy
WAteR LeAKAge SenSORS
Type arT no.
Type arT no.
Type arT no.
vvK 2 1187024 water leakage relay
LPH 10 1187010 water leakage relay
vvA 1 1187020 sensor with connection box
vvA 2 1187021 sensor with 2 m cable
vvA 3 1187026 sensor (25 x 200 mm) with 2 m cable and adhesive tape
vvN 1 1187025 sensor, 1 m sensor band and 2 m cable
vvN 2 1187023 sensor, 2 m sensor band and 2 m cable
VVA 2 VVA 1
VVA 3
VVn
9
KIASMA, MUSeUM OF COnteMPORARy ARt
PRODUAL l 53 l CAtALOgUe
FLtA is a base station for wireless sensors and I/O units. FLtA has 8 x 0...10 Vdc outputs that can be used to deliver the wireless sensor information. the sensor values can also be read via the Modbus. FLtA monitors connected devices for any malfunctions and for the low battery level. FLAn is an antenna for FLtA base station.
FLSeR is a wireless configuration tool for setting the addresses of the sensors, the wireless repeaters and the I/O modules. the tool can also be used for testing the communication signal strength.
FLReP repeaters can be used to extend and boost the range of wireless sensors in difficult environments. It is possible to use up to 8 repeaters for one FLtA base station.
supply 24 Vac/dc, 2 VA
frequency 868.30 MHz Class 1
outputs 8 x 0...10 Vdc
range up to 500 m in the line of sight, 20...100 m in buildings
connectivity max. 99 sensors or max. 20 I/O modules, max. 8 repeaters
network max. 63 base stations
housing IP20, for 35 mm DIn rail
communication Modbus RtU
supply 3,6 V lithium battery
frequency 868.30 MHz Class 1
housing IP20, ABS plastic
supply 12...30 Vac/dc
frequency 868.30 MHz Class 1
housing, FLReP IP20, ABS plastic
housing, FLReP-U IP54
WIReLeSS BASe StAtIOn
WIReLeSS COnFIgURAtIOn tOOL
WIReLeSS RePeAteR
Type arT no.
Type arT no.
Type arT no.
FLTA 1191030 base station for wireless sensors
FLAN 1191040 antenna for FLtA
FLSER 1191070 configuration tool for wireless devices
A04491 A04491 AA lithium battery, 3,6 V 2 Ah
FLREP 1191080 wireless repeater
FLREP-U 1191081 wireless repeater, outdoor
M230/12-4 1184080 230 Vac/12 Vdc 4 VA power supply
10
PRODUAL l 54 l CAtALOgUe
teFL wireless room temperature sensors are designed for temperature detection of indoor spaces. the communication between the teFL room units and the FLtA base station is two-way. Commissioning is done by using the wireless FLSeR configuration tool.
teUFL is a wireless sensor for detecting outdoor temperatures. Communication between the sensors and the FLtA base station is two-way. In addition to temperature information, teUFL sensor can send also one 0...10 V signal or one contact (DI) information (teUFL-DI). Commissioning is done by using the wireless FLSeR configuration tool.
supply 3,6 V lithium battery
frequency 868.30 MHz Class 1
range 0…+50 °C
housing IP20, ABS plastic
mounting with screws on wall or on junction box (hole distance 60 mm)
dimensions 86 x 86 x 32 mm
supply 3,6 V lithium battery
frequency 868.30 MHz Class 1
range 1 -50…+150 °C
range 2 0…10 Vdc
mounting with screws, external lugs
housing IP54, cable glands downwards
WIReLeSS tRAnSMItteRS
WIReLeSS tRAnSMItteRS
room °C, % rH
outdoors °C, 0...10 v
Type arT no.
Type arT no.
TEFL 1191010 wireless room sensor
TEFL-P 1191011 wireless room sensor with set point setting
TEFL-RH 1191020 wireless room sensor with %rH
TEFL-RH-P 1191021 wireless room sensor with %rH and set point setting
FL-S5 1191050 S5 switch option for teFL
FL-N 1191060 display option for teFL
FL-DI 1191051 DI option for teFL
A04491 A04491 AA lithium battery, 3,6 V 2Ah
TEUFL 1191100 wireless outdoor temperature sensor
TEUFL-24 1191101 wireless outdoor temperature sensor, 24 Vac/dc supply
TEUFL-DI 1191102 wireless outdoor temperature sensor, with a contact (DI) input
TEUFL-DI-24 1191103 wireless outdoor temperature sensor, with 24 Vac/dc supply and with a contact (DI) input
A04491 A04491 AA lithium battery, 3,6 V 2 Ah
External Pt1000 temperature sensor, e.g. TEAT PT 1000.
10
PRODUAL l 55 l CAtALOgUe
KLUFL is a wireless transmitter for detecting outdoor temperatures and humidity. the communication between the sensors and the FLtA base station is two-way. Commissioning is done by using the wireless FLSeR configuration tool. LUX 11 illumination sensor can be connected to the KLUFL transmitter.
supply 3,6 V lithium battery
frequency 868.30 MHz Class 1
range 1 0…100 % rH
range 2 -50…+150 °C
range 3 0…1000 lux
mounting with screws, external lugs
housing IP54, cable gland downwards
WIReLeSS tRAnSMItteRSoutdoors °C, % rH
Type arT no.
KLUFL 1191110 wireless outdoor humidity and temperature transmitter
LUX 11 + NTC 10 1133350 illumination and temperature sensor (ntC 10)
LUX 11 + NTC 20 1133351 illumination and temperature sensor (ntC 20)
A04491 A04491 AA lithium battery, 3,6 V 2 Ah
HDHFL transmitters are designed for detecting carbon dioxide concentration and temperature in the room spaces. HDHFL-RH transmitters have also a humidity output. Commissioning is done by using the wireless FLSeR configuration tool.
supply 24 Vac/dc, 1 VA
frequency 868.30 MHz Class 1
range, CO2 0…2000 ppm
range, temperature 0…+50 °C
range, humidity 0…100 % rH
accuracy, CO2 ±40 ppm +3 % from value
accuracy, temperature ±0,5 °C, at 25 °C
accuracy, humidity ±2 % rH, at 25 °C
outputs 0…10 V < 2 mA
ambient temperature 0...+50 °C
housing IP20, ABS plastic
dimensions 87 x 86 x 30 mm
mounting with screws on wall or on junction box
(hole distance 60 mm)
WIReLeSS tRAnSMItteRSroom ppm CO2, °C, % rH
Type arT no.
HDHFL 1191150 CO2 and °C transmitter with wireless communication
HDHFL-N 1191151 CO2 and °C transmitter with wireless communication and with display
HDHFL-RH 1191160 CO2, °C and % rH transmitter with wireless communication
HDHFL-RH-N 1191161 CO2, °C and % rH transmitter with wireless communication and with display
10
PRODUAL l 56 l CAtALOgUe
LAFL is a wireless detector for occupancy monitoring movement. the detector is passive infrared (PIR) which reacts to temperature changes. the communication between the sensors and the FLtA base station is two-way. Commissioning is done by using the wireless FLSeR configuration tool. Mounting bracket and screws are included to the delivery.
supply 3,6 V lithium battery
frequency 868.30 MHz Class 1
ambient temperature 0...+50 °C
housing IP40
coverage angle 140°
WIReLeSS OCCUPAnCy SenSOR
Type arT no.
LAFL 1191120 wireless PIR detector
LAFL-LX 1191121 wireless PIR detector with illumination (0…2000 lux)
AO4491 A04491 AA lithium battery, 3,6 V 2 Ah
PAFL is a wireless pulse counter. the counter can be used to measure pulses from electricity consumption meters, gas flow meters and water consumption meters. Commissioning is done by using the wireless FLSeR configuration tool.
supply 2 x 3,6 V lithium battery or 24 Vac/dc
frequency 868.30 MHz Class 1
max. pulse frequency 20 Hz
min. pulse duration 25 ms
ambient temperature -40...+50 °C
mounting with screws, external lugs
housing IP54, cable gland downwards
WIReLeSS tRAnSMItteRSoutdoors °C, % rH
Type arT no.
PAFL 1191170 wireless pulse counter
A04491 A04491 AA lithium battery, 3,6 V 2 Ah
10
PRODUAL l 57 l CAtALOgUe
FLSnIF is a tool for monitoring the functionality of the wireless network. By using this tool you may follow one by one the signals between the wireless field equipment and the base station. Monitoring is possible only for signals which are available at the very moment. A PC with installed monitoring software is needed with the tool. the software is delivered with the tool.
KLM is a mechanical thermometer for a duct installation. two scales are available.
stem Ø 9 x 200 mm
face Ø 100 mm
mounting by a flange
tOOL FOR MOnItORIng WIReLeSS netWORK
MeteRS
Type arT no.
Type arT no.
FLSNIF 1191140 tool for monitoring the wireless network
KLM -40/60 1240010 duct thermometer -40…+60 °C
KLM 0/60 1240020 duct thermometer 0…+60 °C
RyFL is a wireless I/O module for sending and receiving analogue and digital information.
supply 230 Vac (24 Vac to order)
frequency 868.30 MHz Class 1
input 1 contact / 0…10 V, selectable
input 2 contact / 0…10 V, selectable
output 1 0...10 V and 24 Vac PWM / relay 230 Vac, 10 A res., selectable
output 2 0...10 V and 24 Vac PWM / relay 230 Vac, 10 A res., selectable
WIReLeSS I/O MODULe
Type arT no.
RYFL 1191130 wireless I/O module
FLAN 1191040 antenna
11
10
PRODUAL l 58 l CAtALOgUe
PeK switches are designed for monitoring over and under pressures and pressure differences in systems that handle air and other non-flammable gases.
DIFFeRentIAL PReSSURe SWItCH
Type arT no.
PEK 300 1240310 differential pressure switch 20...300 Pa
PEK 400 1240320 differential pressure switch 30...400 Pa
PEK 500 1240330 differential pressure switch 50...500 Pa
PEK 1000 1240340 differential pressure switch 200...1000 Pa
PEK 2500 1240350 differential pressure switch 500...2500 Pa
PEK 5000 1240360 differential pressure switch 1000...5000 Pa
PEK-AS 1240300 Accessory kit for PeK and CPS differential pressure switches
CPS switches are designed for monitoring over and under pressures and pressure differences in systems that handle air and other non-flammable gases.
DIFFeRentIAL PReSSURe SWItCH
Type arT no.
CPS 330 1240100 differential pressure switch 20…330 Pa
CPS 450 1240110 differential pressure switch 30…500 Pa
CPS 1100 1240120 differential pressure switch 100…1100 Pa
CPS 4000 1240130 differential pressure switch 500…4000 Pa
PEK-AS 1240300 Accessory kit for PeK and CPS differential pressure switches
11
PRODUAL l 59 l CAtALOgUe
COntROL PAneLS FOR OPeRAtIOn / CLeAn ROOMS
Type arT no.
LSML 22 9000340 control panel
LSML 22-2 9000341 control panel, includes also a timer with ventilation status leds
LSML 22-3 9000342 control panel, includes also a humidity display and timer with ventilation status leds
LSML 22-4 9000344 control panel, includes also a humidity display
2-way valves with different sizes and with different kvs values for HVAC applications are available. Valves can be used for controlling heating and cooling. A VA 80 adapter is needed for connecting a nV valve with a BA actuator.
Valve actuators are available for 24 Vac and for 230 Vac supply with a nC or nO function. Control signal may be a PWM or a 0...10 Vdc signal. Connection cables may be fixed (length 1 m) or removable. Different lengths of removable cables are available. An adapter between the valve and the actuator is always needed.
LSML is designed for monitoring and controlling conditions in the operation and clean rooms. the control panel is flush mounted and includes differential pressure and temperature measurements and displays. the temperature measurement needs a separate Pt1000 temperature sensor (not included in the delivery). the panel is also available with some additional features.
COntROL VALVeS
tHeRMAL ACtUAtORS
Type arT no.
Type arT no.
Nv2D10 1230100 valve 3/8” fixed Kvs 1,20
Nv2D10v 1230101 valve 3/8” adjustable Kvs 0,10…0,80
Nv2D10F 1230102 valve 3/8” adjustable Kvs 0,05…0,35
Nv2D15 1230150 valve 1/2” fixed Kvs 1,20
Nv2D15v 1230151 valve 1/2” adjustable Kvs 0,10…0,80
Nv2D15F 1230152 valve 1/2” adjustable Kvs 0,05…0,35
Nv2D20 1230200 valve 3/4” fixed Kvs 1,50
Nv2D20v 1230201 valve 3/4” adjustable Kvs 0,10…0,80
A4004.XX.01 1210010 thermal actuator 24 V nC, fixed cable 1 m
A4104.XX.01 1210020 thermal actuator 24 V nO, fixed cable 1 m
AA2004 1210030 thermal actuator 230 V nC, removable cable (sold separately)
AA4004 1210040 thermal actuator 24 V nC, removable cable (sold separately)
AA4104 1210045 thermal actuator 24 V nO, removable cable (sold separately)
AA5014 1210050 thermal actuator 0...10 V, removable cable (sold separately)
vA 80 1220010 adapter, for e.g. all above mentioned nV valves
Different adapters are available for most common valves in the market.Please check the adapter type for each valve model.
11
PRODUAL l 60 l CAtALOgUe
PRODUAL OY’S TERMS OF DELIvERY
Effective as of 1.9.2010
1. SCOPEthese terms of delivery shall be applied to sale of equipment and components (“products”) by Produal Oy (hereinafter “seller”) to its customers and by reference they shall become an integral part of the agreement between the parties unless otherwise agreed (however, not in deliveries in which the object is customized to the individual requirements of the customer, nor in deliveries which include installation work as an integral part). Any amendment made in these terms of Delivery shall be null and void, unless made in writing and duly approved by signatures of competent representatives of the parties.
2. PRICEProdual Oy’s prices that are effective on the date of order shall be used as the basis for pricing. All prices are exclusive of value-added tax, which will be invoiced in accordance with at-each-time applicable legislation.
In the event changes in customs, freight, value-added tax or other general or public payments related to delivery occur, the seller is entitled to change the price of the products in the same proportion that the said changed taxes, prices or payments have affected the price of the products.
3. OFFERthe price referred to in the offer is the net price ex warehouse for a particular unit at the amount in question, excluding value-added tax. the seller’s offer is binding and it valid for thirty (30) days unless otherwise stated in the offer.
If the seller’s offer has been made subject to being unsold, it means an offer immediately from the stock such that products can be sold to a third party while the offer is effective and the seller does not guarantee the sufficiency of products in stock.
4. AGREEMENTAn agreement between the seller and the customer is deemed to have been entered into when
- the contracting parties have signed a written agreement (“supply contract”);
- the customer has approved a binding offer (“order”) in writing or orally; or
- the seller has confirmed in writing or orally an order, as such, that is not based on a offer or that deviates from an offer, and seller accepts this by confirmation of order (“confirmation of order”).
5. DRAwINGS AND PROSPECTUSESInformation presented in prospectuses, pictures, drawings, catalogues and price lists regarding prices, dimensions, weight and performance as well as other data containing technical and other details is provided without obligation unless otherwise agreed between the parties in the agreement. the seller reserves a right to make alterations and changes in the products, provided that such alteration and changes do not materially prevent the use of the products.
All drawings and technical documents relinquished by one party to the other before or after reaching an agreement, and which are needed for manufacturing the products or any part thereof, remain the property of the discloser. the recipient may not without the written consent of the discloser use, copy, relinquish or otherwise give out information about said drawings or technical documents to a third party or use them in its business otherwise than in a manner required by the agreement between the parties.
6. TERMS OF DELIvERYthe terms of delivery are ex warehouse (Incoterms 2000 eXW Produal Oy’s werehouse) unless otherwise agreed in supply contract.
7. PACKINGPrices referred to in price lists and catalogues mean unpacked products.
8. TIME OF DELIvERYthe seller shall deliver the products within the agreed time. If the seller has overdue receivables from the customer, the seller has the right to stop the agreed deliveries, until the overdue receivables have been paid in full. In such event, the time of delivery is deemed to have postponed respectively, and the customer is not entitled to claim any compensation for damages or make other claims resulting from such delay. By stopping the agreed deliveries seller shall not waive any of its rights in connection with or arising out of the agreement or these terms of delivery.
the products are deemed to have been delivered when the risk of loss and damage in respect to the products has transferred to the customer in accordance with the Section 6. in these terms of delivery.
9. NOTIFICATION OF DELAYthe seller and the customer shall without a delay notify each other in the event the delivery or receiving of the products is in danger of delay. When seller or customer receives knowledge of a delay, it shall notify the contracting party of the said delay and the underlying reasons and the new estimated date of delivery.
10. DELIvERY AND INSPECTION OF PRODUCTSthe risk of loss and damage is transferred to the customer when the delivery of products has taken place. Upon the delivery of the products the customer shall confirm that the delivery is in accordance with the agreement and shipment list, and shall carefully inspect that the delivery is externally undamaged. Before using, attaching or installing the products, the customer shall diligently inspect the products with due care once more.
A notification related to the amount, condition or type of the products must be made in writing within 8 working days of the receipt of the products, at the risk of the customer otherwise losing the right to make any claims based on a defect or deficiency.
11. FORCE MAJEUREthe seller is not liable for non-performance of its the obligations under the agreement, if this is due to an impediment which the seller or its subcontractor or supplier cannot overcome, or if the performance would require seller’s sacrifices that are excessive compared to the benefit gained by the customer. When the manufacturer or supplier has not fulfilled their respective agreement and the seller’s delivery is delayed or is left unfulfilled, the seller is not liable for the customer for any damage thereof. Force majeure events shall include but shall not be limited to strikes, lock-outs, boycotts and other labour disputes to which the seller is a subject or a participant.
If the impediment or disparity ends within a reasonable time, the customer is entitled to demand fulfillment of the agreement from the seller. In the event it becomes impossible to fulfil the agreement within a reasonable period of time due to a circumstance stipulated in this Section 11, each party is entitled to terminate the agreement without liability for damage by notifying the other party in writing thereof.
12. PAYMENTthe payment term shall be fourteen (14) days net, if not otherwise agreed in the supply contract. the payment term shall be calculated from the date of invoicing. Upon delay of payment, the customer is liable to pay late payment interest in accordance with the interest rates applied by the seller, as well
12
PRODUAL l 61 l CAtALOgUe
as expenses incurred from debt collection. the seller has the right to set-off any receivables from the customer against any payment by the customer.
13. GUARANTEEthe seller gives a twenty-four (24) month guarantee for the material and manufacturing of the delivered products. the guarantee period is deemed to begin on the date of delivery.
In respect to defects in raw material or manufacturing, the seller shall correct the defects provided that product has been sent to the seller without delay or no later than at the end of the guarantee period, at the sole discretion of the seller, by repairing the damaged product or by providing the customer with a new product free from defects and sending it to the customer. the customer shall pay for expenses incurred from sending equipment for repair under warranty, and the seller shall pay for the costs of returning it. the Seller is not liable for reimbursement of any costs related to detaching or reinstallation of the products.
the guarantee does not cover damages caused by accidents, lightning, floods or other acts of god, normal wear and tear, improper, careless or abnormal use or use which is non-compliant with the instructions, abnormal storing, over-stressing, defective maintenance or storage or alterations, changes and installation works that are not done by the seller (or the seller’s authorised representative). the customer is responsible for the selection of material for equipment exposed to corrosion unless agreed otherwise.
If the seller alters the structure of its equipment, the seller is not liable for making similar changes to equipment already purchased.
the guarantee is applicable provided that the customer has, for his part, correctly fulfilled his obligations under the delivery and the agreement.
the seller gives a new guarantee for products repaired or replaced under the guarantee, however only until the end of the guarantee period of the original product.
the seller may against separately invoiced fees repair equipment. the seller shall give a three (3)-month service guarantee that covers material and labour for the repair of equipment outside the guarantee.
this guarantee, under section 13, sets forth the total aggregate liability of the seller in respect to any defects in the products and the seller specifically disclaims any other guarantees, representations and warranties, either express or implied, including but not limited to warranty for fitness for specific purpose.
14. LIMITATION OF LIABILITYParties are responsible for their obligations under the agreement. However, the seller shall not be liable for any indirect or consequential damages to customer including but not limited to loss of production or profit, financing costs, loss of data, costs or damages related to cover purchase, damage to other products or equipment.
the total aggregate liability of the seller under the agreement shall not exceed the contract value of the delivered products under the respective agreement excluding the value added tax. the limitations of liability under this section 14 shall not apply, if the damage is caused by wilful misconduct or gross negligence.
15. INTELLECTUAL PROPERTY RIGHTSBy these terms of delivery or by the agreement the seller does not transfer or assign any intellectual property rights in connection to or arising out of the products or any other intellectual property rights. the customer may only use the product. the customer may not copy, alter, amend or develop
further the products or transfer or assign any intellectual property rights in connection to or arising out of the products.
16. RETURN AND TERMINATION OF THE AGREEMENT An agreement that has become effective is binding and irrevocable and the seller is not obligated to accept a return. Products that have been delivered in accordance with the agreement will be taken back and a maximum reimbursement of 70 % will be given only under the condition that the seller has expressly accepted the return. Such products will be taken back and reimbursed only if they are in their original packaging and condition.
the seller may terminate the agreement forthwith in the event 1) there is an application pending for customer’s bankruptcy, liquidation, restructuring or other similar insolvency proceeding 2) bankruptcy, liquidation, restructuring or other similar insolvency proceeding in respect to the customer has been initiated by a court 3) the customer is otherwise insolvent, or 4) the customer is not able to pay overdue receivables of the seller after a lapse of seven days from the sellers written notice thereof. By terminating the agreement seller does not waive any of its rights under the agreement.
17. NOTICESnotices under the agreement shall be in writing. When sending notices to the other party, the sender is responsible for the arrival of the notice.
18. TRANSFER OF THE AGREEMENTthe parties may not assign or transfer any rights, interest or obligations arising out of the agreement to any third party, without the written consent of the other party. the seller may, however, transfer the rights, interest and obligations arising out of this agreement in connection with a transfer of its business or its business assets to a third party without the consent of the customer. Without prejudice to this Section18, the seller may also transfer, partly or entirely, its contractual receivables to a finance company or other third party without the consent of the customer.
19. THE TITLE AND OwNERSHIPthe title and ownership to the products shall transfer to the customer first when the entire purchase price and other receivables arising out of the agreement have been paid to the seller or a third party to which the receivables have been transferred to.
20. ORDER OF PRECEDENCEthe agreement shall consist of the documents and schedules set out below. In the event the documents conflict with one another the documents shall be applied in an order where a document with smaller number shall prevail over a document with a larger number
1. supply contract / confirmation of order
2. these terms of delivery
3. offer
4. order
21. GOvERNING LAw AND DISPUTE RESOLUTIONthe agreement and these terms of delivery shall be governed by and construed in accordance with the laws of Finland excluding any conflict of law stipulations.
Disputes arising out of the agreements and any provisions there of shall primarily be settled between the parties. If no settlement is reached, disputes shall be resolved in one arbitrator’s arbitration in compliance with the rules of Arbitration Institute of Central Chamber of Commerce of Finland in Helsinki.
Without prejudice to this Section 21, the seller may claim undisputed receivables in a district court of the seller’s domicile.
12
PRODUAL l 62 l CAtALOgUe
13
SenSOR SeLeCtIOn gUIDe
Product Measured property
Type Page °C RH CO2 CO Pa bar m/s m3/s lux w/m2 H2O PIR Qty
IVL 7 • •tUnA 20 18 •
UV 7 18 • •VS 3000 18 • •
PeL 8...9 •PeK / CPS 58 •
IML 9 • •KLH 11 • •KLK 11 • •
KLHJ 12 • •KLU 12 • •
KLUFL 55 • • • 1)
LUX 13...14 • •MMSP1 14 •
VPeL 15 •VPL 15 •HDH 16 • • •
HDHFL 16, 55 • • •HDK 16 • •HDU 17 • •HML 17 •teAt 27 •tenA 28 •teKV 29 •teV 29 •teP 30 •
tePK 30 •teK 31 •
teKHA 31 •teKA 32 •teKy 34 •
teL 36 •teM 36 •
teSK 37 •teHR 37...38 •teFL 54 • •teHU 39 •teU 39...40 •
teUFL 54 •teS 40 •LA 46 •
LAFL 56 • •PLt 47 •
KA 10 13 •SA 10 19 •
VVA / VVn 51 •PAFL 56 •
1) Separate light sensor needed.
PRODUAL l 63 l CAtALOgUe
Output
Type Ω v mA relay Modbus wireless
IVL • •tUnA 20 • •
UV7 •VS 3000 •
PeL • •PeK / CPS •
IML • •KLH • •KLK • •
KLHJ • •KLU • •
KLUFL • • •LUX • • •
MMSP1 • •VPeL • •VPL • •HDH • •
HDHFL • •HDK •HDU •HML • •teAt • • •tenA • • •teKV • • •teV • • •teP • • •
tePK • • •teK • • •
teKHA •teKA • • •teKy • • •
teL •teM •
teSK • • •teHR • • • •teFL •teHU •teU • • •
teUFL •teS •LA •
LAFL •PLt •
KA 10 • •SA 10 • •
VVA / VVn •PAFL •
13
PRODUAL l 64 l CAtALOgUe
Sensor element
PTC 1000
Pt 100
Pt 1000
Ni 1000
Ni 1000-
LG
NTC 1.8
NTC 2.2
NTC 3.0
NTC 10
NTC 20
NTC 10-AN
NTC 10-C
NTC 10-KB
KP 10
tol.±1,3°C/ 25°C
±0,3°C/ 0°C
en60751 B
±0,3°C/ 0°C
en60751 B
±0,4°C/ 0°C
DIn43760
±0,4°C/0°C tcr 5000ppm
Siemens
±0,3°C/ 25°C
tAC1800
±0,25°C/ 25°C
Johnson
±0,25°C/ 25°C
±0,25°C/ 25°C
trend
±0,25°C/ 25°C
H&W
±0.25°C/ 25°C
Andover
±0.25°C/ 25°C
Carel
±0.5°C/ 25°C
LM335Z 10 mV/K
Temp. °C Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω v
140 2128 153.38 1533.8 1909 1737 71 53 70 235 351 298 381 324
130 2041 149.82 1498.2 1833 1675 87 68 90 301 459 377 474 385
120 1923 146.06 1460.6 1760 1615 110 90 117 389 609 483 597 467
110 1810 142.29 1422.9 1688 1557 139 115 153 511 818 624 758 576
100 1700 138.50 1385 1618 1500 178 153 204 679 1114 817 973 723 3,73
95 1647 136.60 1366 1583 1472 202 178 236 787 1307 940 1108 815 3,68
90 1594 134.70 1347 1549 1444 230 207 275 916 1541 1084 1266 923 3,63
85 1543 132.80 1328 1516 1417 264 241 321 1071 1823 1255 1451 1048 3,58
80 1492 130.89 1308.9 1483 1390 303 283 377 1256 2166 1458 1668 1194 3,53
75 1442 128.98 1289.8 1450 1364 349 334 444 1480 2585 1700 1924 1364 3,48
70 1394 127.07 1270.7 1417 1337 403 395 525 1751 3099 1990 2228 1562 3,43
65 1347 125.16 1251.6 1385 1311 468 469 625 2082 3732 2339 2588 1791 3,38
60 1300 123.24 1232.4 1353 1285 545 560 746 2488 4517 2760 3020 2056 3,33
55 1254 121.32 1213.2 1322 1260 638 673 896 2986 5494 3271 3536 2358 3,28
50 1209 119.40 1194 1291 1235 750 811 1080 3602 6718 3893 4160 2702 3,23
45 1166 117.47 1174.7 1260 1210 885 984 1310 4368 8259 4656 4911 3088 3,18
40 1123 115.54 1155.4 1230 1186 1049 1200 1598 5326 10211 5594 5827 3517 3,13
35 1081 113.61 1136.1 1200 1162 1250 1471 1959 6532 12698 6754 6940 3987 3,08
30 1040 111.67 1116.7 1171 1138 1496 1814 2417 8055 15887 8197 8313 4492 3,03
29 1032 111.28 1112.8 1165 1132 1552 1893 2522 8408 16628 8525 8622 4597 3,02
28 1024 110.90 1109 1159 1128 1610 1977 2633 8777 17407 8869 8944 4703 3,01
27 1016 110.51 1105.1 1153 1123 1671 2064 2749 9165 18228 9229 9281 4809 3,00
26 1008 110.12 1101.2 1147 1119 1734 2156 2872 9572 19092 9606 9632 4917 2,99
25 1000 109.73 1097.3 1141 1114 1800 2252 3000 10000 20000 10000 10000 5025 2,98
24 992 109.35 1093.5 1136 1109 1869 2353 3135 10452 20962 10413 10380 5134 2,97
23 984 108.96 1089.6 1130 1105 1941 2458 3277 10923 21973 10845 10780 5243 2,96
22 977 108.57 1085.7 1124 1100 2017 2572 3426 11417 23039 11297 11200 5353 2,95
21 969 108.18 1081.8 1118 1095 2095 2689 3583 11938 24164 11771 11630 5462 2,94
20 961 107.79 1077.9 1112 1091 2177 2813 3748 12490 25350 12268 12090 5573 2,93
15 923 105.85 1058.5 1084 1068 2649 3538 4714 15710 32346 15136 14690 6126 2,88
10 886 103.90 1039 1056 1045 3241 4482 5971 19900 41567 18787 17960 6667 2,83
5 850 101.95 1019.5 1028 1022 3989 5718 7619 25400 53812 23462 22050 7183 2,78
0 815 100.00 1000 1000 1000 4940 7353 9795 32660 70203 29490 27280 7661 2,73
-5 781 98.04 980.4 973 978 6159 9533 12694 42340 92322 37316 33900 8093 2,68
-10 748 96.09 960.9 946 956 7730 12460 16589 55340 122431 47549 42470 8472 2,63
-15 716 94.12 941.2 919 935 9771 16428 21868 72980 163777 61030 53410 8796 2,58
-20 685 92.16 921.6 893 914 12443 21860 29092 97120 221088 78930 67770 9067 2,53
-25 655 90.19 901.9 867 893 15969 29398 39073 130400 301297 102890 86430 9288 2,48
-30 625 88.22 882.2 842 872 20659 39908 53005 177000 414698 135233 111300 9466 2,43
-35 597 86.25 862.5 816 851 26955 54751 72658 243120 576763 179280 9605 2,38
-40 570 84.27 842.7 791 831 35480 75953 100701 337270 810861 239831 9712 2,33
-45 544 82.29 822.9 767 811 47135 106603 141183 473370 1152992 323859 9793
-50 518 80.31 803.1 743 791 63229 151470 200348 672600 1659082 441667 9854
SenSOR CHARACteRIStICS
14
PRODUAL l 65 l CAtALOgUe
15
Sensor element
PTC 1000
Pt 100
Pt 1000
Ni 1000
Ni 1000-
LG
NTC 1.8
NTC 2.2
NTC 3.0
NTC 10
NTC 20
NTC 10-AN
NTC 10-C
NTC 10-KB
KP 10
tol.±1,3°C/ 25°C
±0,3°C/ 0°C
en60751 B
±0,3°C/ 0°C
en60751 B
±0,4°C/ 0°C
DIn43760
±0,4°C/0°C tcr 5000ppm
Siemens
±0,3°C/ 25°C
tAC1800
±0,25°C/ 25°C
Johnson
±0,25°C/ 25°C
±0,25°C/ 25°C
trend
±0,25°C/ 25°C
H&W
±0.25°C/ 25°C
Andover
±0.25°C/ 25°C
Carel
±0.5°C/ 25°C
LM335Z 10 mV/K
Temp. °C Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω Ω v
140 2128 153.38 1533.8 1909 1737 71 53 70 235 351 298 381 324
130 2041 149.82 1498.2 1833 1675 87 68 90 301 459 377 474 385
120 1923 146.06 1460.6 1760 1615 110 90 117 389 609 483 597 467
110 1810 142.29 1422.9 1688 1557 139 115 153 511 818 624 758 576
100 1700 138.50 1385 1618 1500 178 153 204 679 1114 817 973 723 3,73
95 1647 136.60 1366 1583 1472 202 178 236 787 1307 940 1108 815 3,68
90 1594 134.70 1347 1549 1444 230 207 275 916 1541 1084 1266 923 3,63
85 1543 132.80 1328 1516 1417 264 241 321 1071 1823 1255 1451 1048 3,58
80 1492 130.89 1308.9 1483 1390 303 283 377 1256 2166 1458 1668 1194 3,53
75 1442 128.98 1289.8 1450 1364 349 334 444 1480 2585 1700 1924 1364 3,48
70 1394 127.07 1270.7 1417 1337 403 395 525 1751 3099 1990 2228 1562 3,43
65 1347 125.16 1251.6 1385 1311 468 469 625 2082 3732 2339 2588 1791 3,38
60 1300 123.24 1232.4 1353 1285 545 560 746 2488 4517 2760 3020 2056 3,33
55 1254 121.32 1213.2 1322 1260 638 673 896 2986 5494 3271 3536 2358 3,28
50 1209 119.40 1194 1291 1235 750 811 1080 3602 6718 3893 4160 2702 3,23
45 1166 117.47 1174.7 1260 1210 885 984 1310 4368 8259 4656 4911 3088 3,18
40 1123 115.54 1155.4 1230 1186 1049 1200 1598 5326 10211 5594 5827 3517 3,13
35 1081 113.61 1136.1 1200 1162 1250 1471 1959 6532 12698 6754 6940 3987 3,08
30 1040 111.67 1116.7 1171 1138 1496 1814 2417 8055 15887 8197 8313 4492 3,03
29 1032 111.28 1112.8 1165 1132 1552 1893 2522 8408 16628 8525 8622 4597 3,02
28 1024 110.90 1109 1159 1128 1610 1977 2633 8777 17407 8869 8944 4703 3,01
27 1016 110.51 1105.1 1153 1123 1671 2064 2749 9165 18228 9229 9281 4809 3,00
26 1008 110.12 1101.2 1147 1119 1734 2156 2872 9572 19092 9606 9632 4917 2,99
25 1000 109.73 1097.3 1141 1114 1800 2252 3000 10000 20000 10000 10000 5025 2,98
24 992 109.35 1093.5 1136 1109 1869 2353 3135 10452 20962 10413 10380 5134 2,97
23 984 108.96 1089.6 1130 1105 1941 2458 3277 10923 21973 10845 10780 5243 2,96
22 977 108.57 1085.7 1124 1100 2017 2572 3426 11417 23039 11297 11200 5353 2,95
21 969 108.18 1081.8 1118 1095 2095 2689 3583 11938 24164 11771 11630 5462 2,94
20 961 107.79 1077.9 1112 1091 2177 2813 3748 12490 25350 12268 12090 5573 2,93
15 923 105.85 1058.5 1084 1068 2649 3538 4714 15710 32346 15136 14690 6126 2,88
10 886 103.90 1039 1056 1045 3241 4482 5971 19900 41567 18787 17960 6667 2,83
5 850 101.95 1019.5 1028 1022 3989 5718 7619 25400 53812 23462 22050 7183 2,78
0 815 100.00 1000 1000 1000 4940 7353 9795 32660 70203 29490 27280 7661 2,73
-5 781 98.04 980.4 973 978 6159 9533 12694 42340 92322 37316 33900 8093 2,68
-10 748 96.09 960.9 946 956 7730 12460 16589 55340 122431 47549 42470 8472 2,63
-15 716 94.12 941.2 919 935 9771 16428 21868 72980 163777 61030 53410 8796 2,58
-20 685 92.16 921.6 893 914 12443 21860 29092 97120 221088 78930 67770 9067 2,53
-25 655 90.19 901.9 867 893 15969 29398 39073 130400 301297 102890 86430 9288 2,48
-30 625 88.22 882.2 842 872 20659 39908 53005 177000 414698 135233 111300 9466 2,43
-35 597 86.25 862.5 816 851 26955 54751 72658 243120 576763 179280 9605 2,38
-40 570 84.27 842.7 791 831 35480 75953 100701 337270 810861 239831 9712 2,33
-45 544 82.29 822.9 767 811 47135 106603 141183 473370 1152992 323859 9793
-50 518 80.31 803.1 743 791 63229 151470 200348 672600 1659082 441667 9854
COntROLLeR SeLeCtIOn gUIDe
Controller
HLS 16 HLS 21 HLS 33 HLS 34 HLS 35 HLS 44 HLS 44-v HLS 45 PDS 2 PDS 2.2 HS 2.2
App
licat
ion
4-pipe fan coil unit control • • • •
2-pipe fan coil unit control • •
Floor heating • • • • •Floor heating/
cooling • • •
Chilled beam • • • • • • • •Heating radiator
control • • • • • • • •
Domestic water temperature control •
Air handling unit control •
Universal controller • •
Act
uato
r thermal • • • • • • • • • • •3-point • • • • • • •0...10 V • • • • • • • • •
Func
tion
Control stages 1 2 2/3 2/3 1 2/3 2/3 1/2 1 1 1
3-speed fan control with FCRy 3 • • • •
eC fan control • • •
VAV control • • • • •
Summer/winter • • •CO2 based
ventilation control • • • •
Lighting control on/off
•
Modbus • • • • • • •
Page 20 21 21 22 22 23 23 24 24 25 25
PRODUAL l 66 l CAtALOgUe
16
InDeX
teAt xx 27
teFL 54
teFL-P 54
teFL-RH 54
teFL-RH-P 54
teHR LL 38
teHR LU 38
teHR xx 37
teHR xx-P 38
teHR-M 38
teHR-M-n 38
teHU xx 39
teK xx 31
teKA xx 32
teKA xx-500 33
teKHA xx 31
teKV xx 29
teKy xx 34
teL xx 36
teM xx 36
tenA xx 28
teP xx 30
tePK xx 30
teS xx 40
teSIM ntC 10 40
teSIM Pt 1000 40
teSK xx 37
teU LL 40
teU LU 40
teU xx 39
teUFL 54
teUFL-24 54
teUFL-DI 54
teUFL-DI-24 54
teV xx 29
tH 5 50
tUnA 20 18
UMP 3 43
UV 7 18
UV 10 44
VA 80 59
VH 1000 18
VK 10 7
VPeL 1.0/2.5 15
VPeL 4.0/6.0 15
VPL 16 15
VPL 16-n 15
VPL 60 15
VPL 60-n 15
VR 1000 18
VS 3000 18
VVA 1 51
VVA 2 51
VVA 3 51
VVK 2 51
VVn 1 51
VVn 2 51
Axx 59
AAxx 59
AO 2 44
AO 3 44
AR 1 49
At 80 27
AtH 300 27
AtH 80 27
AtM 80 27
AtS 80 27
BAK 64 19
CPS xx 58
DA 6 42
eJV 24-Pt 4
FCRy 3 50
FCRy 3-R 50
FLAn 53
FLReP 53
FLReP-U 53
FLSeR 53
FLSnIF 57
FLtA 53
HDH 16
HDH-AL3 16
HDH-C 16
HDHFL 16
HDHFL 55
HDHFL-n 16
HDHFL-n 55
HDHFL-RH 16
HDHFL-RH 55
HDHFL-RH-n 16
HDHFL-RH-n 55
HDH-M 16
HDH-M-n 16
HDH-M-RH 16
HDH-M-RH-n 16
HDH-n 16
HDH-RH 16
HDH-RH-n 16
HDK 16
HDK-C 16
HDK-n 16
HDU 17
HDU-n 17
HLS 16 20
HLS 21 21
HLS 33 21
HLS 34 22
HLS 35 22
HLS 44 23
HLS 44-SeR 23
HLS 44-V 23
HLS 45 24
HLS 45-SeR 24
HM-KK 17
HML 17
HML-C 17
HML-n 17
HMV 17
HM-VS 17
HS 2.2 25
IML 9
IML-M 9
ISO 10 42
IVL 02 7
IVL 02-n 7
IVL 10 7
IVL 10-n 7
IVL 20 7
IVL 20-n 7
JV 24-Pt 4
JVA 24 4
JVS 24 4
Jy 43
KA 10 13
KA 10-eXt 13
KLH 100 11
KLH 100-n 11
KLH 420 11
KLH 420-n 11
KLHJ 100 12
KLHJ 100-n 12
KLH-M 11
KLH-M-n 11
KLK 100 11
KLK 100-n 11
KLM 0/60 57
KLM -40/60 57
KLU 100 12
KLU 100-n 12
KLUFL 55
KO IVS 41
KO PRA 46
LA 14 46
LA 15 46
LA-RAJ 46
LAFL 56
LAFL-LX 56
LAP 1 48
LAP 10 48
LAP 10-t 48
LAP 5 48
LAP 5-t 48
LeK 24-Pt 5
LeKA 24 49
LK 24-Pt 5
LK 24-Pt 0/100 5
LLK 41
LLK-n 41
LPH 10 51
LSML 22 59
LSML 22-2 59
LSML 22-3 59
LSML 22-4 59
LUK 41
LUK-n 41
LUX 11 14
LUX 24 13
LUX 34 13
LUX 34-100 13
M230/12-4 45
M230/24-15 45
M230/24-30 45
MIO 12-Pt 42
MIO 12-V 42
MMSP1 14
nV2D xx 59
PDS 2 24
PDS 2.2 25
PAFL 56
PeK xx 58
PeK-AS 58
PeL 8
PeL 1000 9
PeL 1000-n 9
PeL 2500 8
PeL 2500-n 8
PeL 25K 8
PeL 25K-n 8
PeL-AS 8
PeL-n 8
PJP 1 48
PJP 2 48
PJP 4 48
PJR 4 20
PLt 12 47
PLt 24 47
PLt 24-K 47
PMU 3 43
PP-PK Rxx 10
PP-SK Lxx 10
PR 10/440 20
PR 50/440 20
PRMK 20
PVA 24 4
PyR 4 44
Ry 1 49
Ry 1-K 49
Ry 1-KK 49
Ry 1-U 49
Ry 1-U-K 49
RyFL 57
RyV 16-U 49
RyVA 16 49
SA 10 19
StS 1 20
StS 4 20
PRODUAL l 67 l CAtALOgUe
COntACt InFORMAtIOn
Kotka Produal Oy Keltakalliontie 18 48770 Kotka
tel. +358 5 230 9200fax. +358 5 230 9210info@produal.fiwww.produal.com
JyväskyläProdual Oytahvontie 240420 Jyskä
SwedenProdual Sverige ABpostal address: Box 611, 13526 tyresöstreet address: Solkraftsvägen 16B, 13570 Stockholmtel. +46 8 555 985 80info@produal.sewww.produal.se
DenmarkProdual A/SUdlejrevej 31-5, 3650 Ølstykketel. +45 70 26 03 04info@produal.dkwww.produal.dk
FranceProdual S.A.S.Bureau 302-11, rue Albert einstein, 77420 Champs sur Marnetel. +33 6 19 29 16 71info@produal.frwww.produal.fr
RussiaOOO ProdualRubcovskaya naberezhnaya 2 k 1, 105082 Moscowtel. +7 495 509 1909info@produal.ruwww.produal.ru
PolandProdual Oyul. Płochocińska 19/110, 03-191 Warszawatel. +48 504 024 416info@produal.plwww.produal.pl
FinLanD