Chair - Jeff Hebenstreit - UL12/4/2013

BackgroundPrevious presentation – Evaluation of gases to

Method E12/2/2009

Background• Utility contacted UL• Concern surrounding contaminants in chlorine• Provided a study suggesting a concentration

effect of Carbon Tetrachloride.

Concerns• A product could meet the requirements of

the standard, if prepared from a full cylinder, where it truly may be non-compliant.

• As product is used, compliant products can become non-compliant, depending on the application method.

Modified Test Method• Gases prepped via method E• Prepared sample from full cylinder• Vented cylinder to near empty• Prepared a second sample• Analyzed via EPA method 524.2

Results

Sample 1 – Manufacturer A Normalized Result (g/L)

Detected VOC Prior to venting After venting, approx. 15% of original Cl2 weight

SPAC (g/L)

Chloroform 0.041 0.14 8.0

Results

Sample 1 – Manufacturer B Normalized Result (g/L)

Detected VOC 86% capacity 9% capacity SPAC (g/L)

Acetone ND 0.43 600 Carbon tetrachloride 0.36 2.83 0.5 Trichlorofluoromethane ND 0.035 200 Sample 2 – Manufacturer B

Normalized Result (g/L) Detected VOC 86% capacity 9% capacity

SPAC (g/L)

Carbon tetrachloride ND 0.02 0.5 Trichlorofluoromethane ND 0.008 200 Vinyl chloride ND 0.008 0.2

AWWA B301-04Section 4.3, Impurities – Liquid chlorine:a.  Moisture ≤ 150 ppmb.  Heavy Metals, sum of all ≤ 30 ppmc.  Lead ≤ 10 ppmd.  Mercury ≤ 1 ppme.  Arsenic ≤ 3 ppmf.   Nonvolatile residue ≤ 50 ppm mfrd rail/tank cars

or ≤ 150 ppm cylindersg.  Carbon tetrachloride ≤ 100 ppmh. Trihalomethanes ≤ 300 ppm

Examples

CCl4 in Cl Gas (%)

CCl4 (ppm)

Dose Rate Cl (mg/L water)

Approx CCl4 in H20 (ug/L)

SPAC/NSF 60 & CA MCL (ug/L)

0.01 100 2 0.2 0.5

0.01 100 5 0.5 0.5 0.01 100 10 1 0.5

0.005 50 2 0.1 0.5

0.005 50 5 0.25 0.5 0.005 50 10 0.5 0.5

RecommendationFormation of a Task GroupReach out to AWWA

Task Group Actions• Discussed Sampling Procedures (no change)• Issue paper for pre-filling requirements• Proposed Modification AWWA B304• Proposed language for AWWA M20 Manual

10

Pre-filling Requirements• Add 6.3.4 – Chlorine Container and Rail Car Pre-Filling

Requirements

• Requires any remaining liquids to be removed prior to filling

• Certifiers can audit against these requirements if added to NSF 60

• Motion for this to go to ballot

11

Proposed Changes to AWWA B301• Ballot proposal submitted to AWWA

disinfection committee to revise AWWA B301 for the following:

• Carbon Tetrachloride: Revise from the current limit of 100 ppm to 16 ppm.

• Trihalomethanes: Revise from the current limit of 300 ppm to 267 ppm (0.0267 percent).

12

AWWA M20 Manual• Proposed language to warn about the issue• Also indicated that the use of vaporizers do

not necessarily remedy the issue• Suggested a remedy if issue is present

13

Task Group Complete• Thanks for all the task group participants

• Roster members• Other participants

• Recommend closure of this Task Group