Automated energy monitoring system of the power drive laboratory of Perm National Research...

Post on 23-Dec-2015

212 views 0 download

Transcript of Automated energy monitoring system of the power drive laboratory of Perm National Research...

Automated energy monitoring system of

the power drive laboratory of Perm National Research

Polytechnic UniversityAuthor:

Georgii Mikriukovmikriukov.georgii@yandex.ru

Science advisor:Aleksey Kychkin

System’s functionsCollection and processing

information about power consumption;

Visualization of stored data;Generation of emergency

events;Data storing for further

analysis.2

Object of automation

Laboratory of electric drive

1 – Stand with aggregate SAM-4-0.552 – Training stand3 - Training stand4 - Switchboard5 – Lab complex: Synchronous generator – Induction motor6 - Lab complex: 3-phase Transformers7 – Lab complex: Induction motor – DC motor8 – Lab complex: Synchronous generator – DC motor9 - Lab complex: 3-phase Transformers10 – Lab complex: Induction motor – DC motor11 – Stand: DC motor12 – Stand: DC motor13 – Lab’s lighting

3

Hardware

Power analyzer Janitza UMG 104

4 current inputs;4 voltage inputs;RS-485, RS-232;

Power analyzer Janitza UMG 604

4 current inputs;4 voltage inputs;RS-485, RS-232, Ethernet;Web-interface;

Current transformer TTI-A50/5;30/5.

Accuracy class – 0.5

4

5

UMG 104

(slave)

UMG 604

(master) Modbus

RS-485

Ethernet

UMG 104

(slave)

UMG 104

(slave)

UMG 104

(slave)

LAN

5

SoftwareOpenJEVis of ENVIDATEC GmbH:

JEDB – DB based on DBMS MySQL;JEGraph – visualization structure;JEConfig – system parameters

configuration.GridVis of Janitza electronics GmbH:

Data collection & online monitoring;Power analyzers remote setting;Data conversion into csv-format.

6

77

Current values graph (GridVis)

Current values graph (JEGraph)

GridVis Project Tree

JEConfig Registry Tree

Parameters of monitoring

Effective current (phase), A

Effective voltage (phase), V

Apparent power (phase), VA

Active power (phase), W

Reactive power (phase), var

8

System’s structure

9

Data collection

server

Internet

LAN

OpenJEVisPerm

OpenJEVis.org

Hamburgalpha-server

Janitza UMG 104

I measuringU

measuring

Janitza UMG 604

I measuring

U measuring

RS-485

Ethernet

Data

colle

ctio

n

Local storage server

(PNRPU)

JEDB

Work- statio

n

JEConfigJEGraph

JEDB

Global storage server

(Hamburg)

Work-statio

n

JEConfig

JEGraph

Remote user

Modbus

TCP/IP

Janitza UMG 104

I measuringU

measuring

Data

pro

cess

ing a

nd s

tora

ge

Hardware location

– Current measuring– Voltage measuring

Janitza

H

ard

ware

Electric drive lab, PNRPU complex, building A

Data collection

server

Local storage server

PNRPU complex, building A

PNRPU complex, building DT-wire

15 m

Optic fiber

500 m

Global storage server

ENVIDATEC GmbH,

Hamburg

Internet3500 km

10

PerspectivesCorrelation functions calculating;

Power consumption prediction.

11

11

Σ

O1

O2

ON

.

.

S1

S2

SN

S1

S2

SN

yk Analysis block

.

.

Thank you for your attention.