Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
BUILDING 1
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m’)
Administration, canteen
Stationery. Cooking oil in canteen.
Automatic water sprinklers
Some firewater contained within building. Some flows out of building to site surface water drainage system and from thence to municipal surface water sewer
216 m2 (Building 1A)
Quantity of Firewater run-off (m3>
5 mm/mm x 216 m2 x 120 min =
Fire hydrant 2 No (Appendix C2): 13m3/minx 12Omin=
130 m3
1,170 m3
Fire Load
Fire brigade units = 22 m3
Total fire suppression water volume = 1,322 m3
I
High
Fire Risk I Low
Environmental Load
Environmental Risk
Containment available
Containment required No, as environmental risk is low. Firewater from office and canteen areas is not normally considered contaminated due to the nature and small quantities of the materials.
a J:\D4500-D4599\D4533\2) Page Al Amp Consulting Engineers
Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
BUILDING 2
4ctivities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3)
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Blister packaging with tablets. Sheets of blistered tablets are printed with quality control information and manufacturing details. Subsequently, the blister sheet can be divided into the required pack size and packaged into secondary packaging containers including insertion of information leaflets as required.
Final product, packaging materials (cardboard, paper, PVC wrapping, plastic shrink wrap, etc.), inks
Automatic water sprinklers Firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer
279 m2 (maximum floor area coverage for valve Bl, 2A North)
Sprinklers (Appendix Cl): 8.15 mm/min x 279 m2
Firewater delivery limited to 1,362 m3 over 2
Fire brigade units =
Total fire suppression water volume =
22 m3
1,384 m3
High
Low
Medium
Medium
No containment is provided for this building
Yes, as environmental risk is medium.
, , . ‘ : _, . ! by 1.
* .+
I. -’ I:u)4500-D4599\D4533\2) DOCUMENTS\16\RePORTS~WATER_REPORT_D4l.DOC
Page A2 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
BUILDING 2A
km
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3>
Fire Load
Fire Risk
Containment available
Containment required
Desctrip&HI
Blister packaging with tablets. Sheets of blistered tablets are printed with quality control information and manufacturing details. Subsequently, the blister sheet can be divided into the required pack size and packaged into secondary packaging containers including insertion of information leaflets as required.
Final product, packaging materials (cardboard, paper, PVC wrapping, plastic shrink wrap, etc.), inks
Automatic water sprinklers
Firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer
279 m2 (maximum floor area coverage for valve B 1,2A North)
Sprinklers (Appendix Cl): 8.15 mm/mm x 279 m2x 12Omin=
273 m3
Fire hydrant 2 No (Appendix C2): 13m3/minx 120min=
1,170 m3
Total = 1,443 m3
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fiie brigade units = I 22 m3
Total fire suppression water volume =
High
Low
1,384 m3
Medium
No containment is provided for this building.
Yes, as environmental risk is medium.
Page A3 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica lreland, Newbridge lPPC Licence Review Firewater Retention Study
0 A4. BUILDING 3
::“. .:... .T :
I :.:.:>“:.:~:
,~, kn $ ::::i::. .:::
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off b3)
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Tablet manufacturing
@Is, excipients, solvents
Automatic water sprinklers
Internal floor drainage system to trade effluent system for transfer to Osberstown WWTW. Some fiiewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer surface water system.
279 m2 (maximum floor area coverage for valve 3s)
Sprinklers (Appendix Cl): 8mm/min x 279 m2x 12Omin=
268 m3
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 mm =
Total =
However, fiiewater delivery limited to 1,362 m3 over 2 hours =
1,170 m3
1,438 m3
1,362 m3
Fine brigade units =
Total fire suppression wirter volume =
22 m3
1,384 m3
High
Low
High
Medium
No containment is provided for this building.
Yes, as environmental risk is medium.
Page A4 Arup Consulting Engineers Issue 22 June 2005
,’
j: ”
,i
‘::: *. , -,,
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
BUILDING 3A
Item
Activities
Materials
Fiie Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3>
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Des&p&n
Tablet manufacturing
APIs, excipients, solvents
Automatic water sprinklers
Internal floor drainage system to trade effluent system for transfer to Osberstown WWTW. Some firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer.
279 m2 (maximum floor area coverage for Ground and First Floor sprinklers in Building 3A)
Sprinklers (Appendix Cl): 8mm/min x 279 m2 x 12omin=
Fire hydrant 2 No (Appendix C2): 13m3/minx120min=
1,170 m3
Total = 1,438 m3
However, firewater delivery limited to 1,362 m3 over 2 hours =
1 1,36=1
Fiie brigade units = I 22 m3 I
Total fire suppression water volume = 1 1,3S4m3 1
No containment is provided for this building.
Yes, as environmental risk is medium.
J:!D4500-D4599u)4533\2) DOCUhENTS\16iREPORTS\FIREWATERJEPORT~D4533-l6JSSDKl.DOC
Page A5 Amp Consulting Engineers Issue 22June2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
Activities Tablet manufacture and some administration
Materials APIs, excipients, solvents, packaging
Fire Fighting Automatic water sprinklers
Destination of Firewater
Sprinkler Coverage Area (m’)
Quantity of Firewater run-off (m3)
Fire Load
Fiie Risk
Environmental Load High
Environmental Risk Medium
Containment available Yes. Any firewater generated in a Glatt room will drain to floor gullies and channels that will be manually diverted to the 30 m3 storage tank TX-007 in the new solvent storage area. This overflows to the 1000 m3 firewater storage tank.
Containment required
Firewater from Glatt rooms flows to storage tank. Firewater mostly flows to trade effluent system via the internal floor drainage system. Some firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer.
279 m2 (maximum floor area coverage for sprinklers)
Sprinklers (Appendix Cl): 12mm/min x 279 m2
I 1,572 m3
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fire brigade units = 22 m3
Total fire suppression water volume = 1,384 m3
High
Low
Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (4,228 m3 - refer to section 8) is greater than the containment currently provided by the 1 ,000m3 Firewater Retention Tank.
JiD4500-04599iD4533\2) DOCIJh4ENTS\1biREPORTS\mREWATER_REPORT_D4533-l6JSSIJ!~l.DOC
Page A6 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge
BUILDING 4 -WAREHOUSE
Item
Activities Storage raw materials/products being delivered to/from site.
Materials API, excipients, tablets, solvents, inks
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3>
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Description
Automatic water sprinklers Internal floor drainage system to trade effluent system for transfer to Osberstown WWTW. Some firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer.
232 m2 (maximum floor area coverage for sprinklers in Building 4)
Sprinklers (Appendix Cl): 18.4mm/min x 232
Yes, as environmental risk is medium.
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fire brigade units =
Total fire suppression water volume =
22 m3
1,384 m3
High
Low
Medium
Medium
No containment is provided for this building
J:U)4500-D4599\D4533\2) Page A7 Amp Consulting Engineers Issue 22June2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:29
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
BUILDING 4 - SOLVENT STORAGE AREA
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m’)
Quantity of Firewater run-off (m3>
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Storage of solvents within a dedicated bunded room.
Solvents
Foam deluge system Some firewater flows to the on-site surface water drainage system and subseauentlv to the municinal surface water sewer.
77 m2 (Solvent storage area)
Foam deluge system capacity =
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 min = [This water will be used for cooling purposes and for suppression of that part of afire not involving flammable liquids]
Fire brigade units =
Total fire suppression water volume =
High l
1 m3
1,170 m3
22 m3
1,193 m3
Low
Medium
Medium
Foam in solvent storage area would be contained by bund.
Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (6,093 m3 - refer to section 8) is greater than the containment currently provided in the solvent storage area.
Jz!D4500-D4599u)4533\2) DOCUMENTS\16iREPORTS\mREWATER_REPORTJM533-l6JXJE~l.DOC
Page A8 Arup Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
BUILDING 5 - CHILLER BUILDING
Item
Activities Housing of steam boilers, MTHW boilers, chiller units and cooling towers
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m’)
Quantity of Firewater run-off Sprinklers (Appendix Cl): 21.2 mm/mm x 12 m2 Cm31 x 120min=
Fire Load
Boiler chemicals e.g. oxygen scavengers.
Automatic water sprinklers
Internal floor drainage system to trade effluent system for transfer to Osberstown WWTW. Some firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer.
12 m2 (maximum floor area coverage for Building 5 Cooling Towers sprinklers)
31 m3
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 min =
1,170 m3
Fire brigade units =
Total fire suppression water volume =
Low
22 m3
1.223 m3
Environmental Load
Environmental Risk
Fire Risk Low
Containment available
Medium
Low
No containment is provided for this building
No, as environmentd risk is low.
Page A9 Arup Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
Al 0. BUILDING 5A - CENTRAL UTILITIES BUILDING (CUB)
Activities I Site utilities
Materials I No hazardous materials stored in CUB
Fire Fighting I Automatic sprinkler protection
Destination of Firewater Some firewater retained by building. Some flows out of building to site surface water drainage system
Sprinkler Coverage Area (m”) Quantity of Firewater run-off b3>
12 rn20 Sprinklers (Appendix Cl): 21.2 mm/min x 12 m” x 12omin=
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 min =
31 m3
1,170 m3
I Fire brigade units = I 22 m3
Fire Load
Total fire suppression water volume =
Low
1,223 m3
Fire Risk
Environmental Load
Environmental Risk
Containment available I No containment is provided for this building
Containment required I No, as environmental risk is low.
a.
7 No data was available for the maximum area of operation of sp&klers in the CUB. Sprinkle; data (maximum area of operation and discharge rate) for the cooling towers has been used.
J:!D4500-D4599u)4533\2) DOCIJMENTS\16iREPORTS\FIREWATERJXEPORT_D4l.DOC
Page A10 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
All. BUILDING 5 - UTILITIES BUND
Destination of Firewater
Containment available
ontamment require No, as environmental risk is low.
J:ID4500-D4599iD4533\2) Page Al 1 Amp Consulting Engineers DOCUMENTS\16\REPORTS\FIREWATZR~REPORT~D4S33-l6~lSSULl.DOC Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
A12. DIESEL TAI’dK
Fire Fighting
Destination of Firewater
Hose streams Contained in btmd
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off b3>
Not applicable
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 mm =
1,170 m3
I Fire brigade units = I 22 m3
Fire Load
Total fire suppression water volume =
High
1,192 m3
Fire Risk
Environmental Load
Environmental Risk
High
Medium
Containment available I Containment provided in bund and by pump house.
Containment required Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (1,199 m3 - refer to section 8) is greater than the containment currently provided by the volume of the diesel tank bund and pump house (195.75m3).
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
A13. BUILDING 9
Item
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m’)
Quantity of Firewater run-off Cm31
Fire Load
Fire Risk
Environmental Load
Containment available
Containment required
Description i
Storage raw materials/products being delivered to/from site
API, excipients, tablets
Automatic water sprinklers
Firewater flows to basement bund with a capacity of approximately 3,433 m3
280 m2 (maximum floor area coverage for valve FM2, Building 9 ASKS South)
Sprinklers (Appendix Cl): 18.3 mm/mm x 280 m’x 12Omin=
615 m3
Fire hydrant 2 No (Appendix C2): 13m3/minx 12Omin= Total =
1,170 m3
1,785 m3
However, fiiewater delivery limited to 1,362 m3
~
Total fire suppression water volume =
High
1,384 m3
Low
Medium
Yes. Firewater retained by bunded basement.
No (refer to section 7.10). Requirement for WMI to provide “remedial works and/or additional protective measures” for areas posing a medium environmental risk has been met by WMI in providing a dedicated bund for the Building.
J:u)4500-D4599\D4533\2) Page Al3 Arup Consulting Engineers DOCUhIENTS\l6iREPORT.SMREWATERJtEPORT~D4533-I6~ISSDE~l.DOC Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge
a A14. TEMPORARY WASTE MANAGEMENT COMPOUND
Activities Storage of waste chemicals I
Materials Waste chemicals
Fire Fighting Hydrants, fire brigade units if required
Destination of Firewater Firewater could overflow the bunds in Chemstore units and seep into ground
Sprinkler Coverage Area (m’) 1 No sprinkler system provided in this area
Quantity of Firewater run-off Cm31
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 min =
Fire brigade units =
1,170 m3
22 m3
Fire Load
Fire Risk
Total fire suppression water volume =
High
Low
1,384 m3
Environmental Load I High
Environmental Risk
Containment available
Medium
Yes - bunding in Chemstore units
Containment required Yes, as firewater could overflow the bunding in the Chemstore units. A permanent waste handling facility is to be constructed on-site to process waste (refer to Appendix A18).
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
A15. SOLVENT AND AQUEOUS WASTE TANK FARM
1tenl Description
4ctivities Storage of aqueous waste and solvents
Materials Aqueous/solvent-rich waste 3 no. 30m3 tanks
I Dichloromethane (DCM) I 2 no. 30m3 tanks
I 2 no. 30m3 tanks
Fire Fighting Hydrants, fire brigade units if required
Destination of Firewater I Retained by bund
Sprinkler Coverage Area (m2) No maximum area of operation available for the tank farm sprinklers. Therefore, area taken to be the total area of tank farm i.e. Bund Nos 1 - 4 = 365m2
Quantity of Firewater run-off b3>
Sprinklers (Appendix Cl): lOmm/min x 365m2 x 120min
438 m3
Fire hydrant 2 No (Appendix C2): 13m3/minx120min=
Total =
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,170 m3
1,608 m3
1.362 m3
Containment Yes. Bund is constructed of concrete. Capacity is approximately 150m3. This overflows to the 1,000 m3 Firewater Retention Tank.
Containment required Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (1,397 m3 - refer to section 8) is greater than the containment currently provided by the 1 ,000m3 Firewater Retention Tank and the tank farm bund.
Fire brigade units = 22 m3
Fire Load
Total fire suppression water volume =
High
1,384 m3
Fire Risk I Low
Environmental Load
Environmental Risk I Medium
1:\04500-D4599\D4533\2) Page Al 5 Amp Consulting Engineers Issue 22June2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
0 A16. BUILDING 3C (BZAKE-PNP)
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3)
Fire Load
Fiie Risk
Environmental Load
Environmental Risk
Containment available
Tablet manufacture
APIs, excipients, packaging * Automatic water sprinklers
Firewater will be captured within the building and will then flow through the floor gullies and channels into the process drainage from where it will flow by way of an overflow to a dedicated firewater drain to the Firewater Retention Tank. Some firewater flows to the on-site surface water drainage system and subsequently to the municipal surface water sewer.
260 m2 (Level 2 Discharge’)
Sprinklers’: 7.5 mm/mm x 260 m2 x 120 min = 234 m3
Fire hydrant 2 No (Appendix C2): 13m3/minx 12Omin=
1,170 m3
I 1,404 m3
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fire brigade units =
Total fire suppression water volume =
22 m3
1,384 m3
High
Low
Medium
Yes. Any firewater generated in the proposed PNFX building will be contained within the building and will flow through the floor gullies and channels to the 30 m3 storage tank (TK-007) in the new Solvent/Aqueous Waste Tank Farm. This overflows to the 1000 m3 Firewater Retention Tank.
’ AWN, Wyeth Medica Ireland Proposed PNFX Development, Environmental Impact Statement identified this as the largest areas which could lead to firewater generation based upon International Codes of Practice (NFPA, Factory ytual Global, International Building Codes)
Rules of the Fire Offices’ Committee for Automatic Sprinkler Installations - 29” Edition (1973). 7.5 mm/min is the design density of discharge for extra high process risks, paint, colour and varnish mfrs, resin, lamp black and turpentine works, over an assumed maximum area of operation of 260 m2
JW45OO-D4599iD4533\2) DOCUMENTS\16W3PORTWlREWATER~REPORT_Dl.DOC
Page Al6 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
Containment required Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (4,228 m3 - refer to section 8) is greater than the containment currently provided by the l,000m3 Firewater Retention Tank and the 30 m3 storage tank (TK-007).
J:U34500-D4599\D4533\2) Page A17 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Iceland, Newbridge IPPC Licence Review Firewater Retention Study
Al 7. BUILDING 4 - LEVO/EE
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off (m3)
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
OC manufacturing facility
APIs (about 50 kg) and excipients (about 5,000 kg). Packaging.
Automatic sprinkler system Via floor gullies to process drains
232 m2
57 l/ruin x 6 heads x 120 min
Fire hydrant 2 No (Appendix C2): 13 m3/min x 120 min = I I
1,170 m3
Fire brigade units =
Total fire suppression water volume =
Medium
1,233 m3
Low
Yes. Diversion of drainage to Firewater Retention Tank is proposed.
No, as environmental risk is low
i -“$
,I ,, (!’
A;“,:’ ,). _,.’
,’ ,.‘: r:;;;.; ;i.i
,52’ + ; .+. :, I,. 12, ,$?
: ;z ,;,.:..:
1 .,:a , I :.. a(/
jj. i JT$,
.v,, * ; ‘. ‘. ~~iC,~.~&
‘, .” i” .,;I:
JXl45OO-D4599iD4533L?) DOCUMENTS\16\REPORTS\FIREWATERBEPORT_D4l.DOC
Page Al8 k&p Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:30
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiwater Retention Study
Al 8. WASTE MANAGEMENT COMPOUND
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m2)
Quantity of Firewater run-off Cm31
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Processing of waste - storage area will be 1,070 m2.
Liquid hazardous and non-hazardous wastes. Solid hazardous wastes.
Water deluge system
Some firewater will be retained within the sumps of the individual storage units. It is proposed to divert firewater to the 1,000 m3 Firewater Retention Tank. Deluge quantity will be 3000 I/mm
Deluge system: 3 m3/min x 120 min =
Fire hydrant 2 No (Appendix C2): 13m3/minx120min=
1,170 m3
Total
However, firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fire brigade units = I 22 m3
Total fire suppression water volume = I 1,384 m3
High
Low
High
Medium
Yes. Some containment will be available within the waste compound, and within the sumps of storage units. The principal containment will be in the 1,000 m3 Firewater Retention Tank, to which the compound will drain. All tanks in the compound will be bunded.
Yes, as environmental risk is medium. The calculated volume of potentially contaminated firewater (4,228 m3 - refer to section 8) is greater than the containment currently provided by the 1 ,000m3 Firewater Retention Tank.
Page A19 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
0 Al 9. R&D FACILITY
Activities
Materials
Fire Fighting
Destination of Firewater
Sprinkler Coverage Area (m”)
Quantity of Firewater run-off Cm31
Fire Load
Fire Risk
Environmental Load
Environmental Risk
Containment available
Containment required
Evaluation of new process and materials
yet yet established but probably smaIl quantities of flammable md toxic substances
Automatic sprinkler system Drainage to the Firewater Retention Tank is proposed
Information not yet available
As no information available on sprinkler discharge rate or maximum area of operation, volume of firewater delivered is taken as the maximum volume capable of being delivered by the site firewater pumps, plus the contribution of fire brigade units
Firewater delivery limited to 1,362 m3 over 2 hours =
1,362 m3
Fire brigade units = I 22 m3
Total fire suppression water volume = I 1,384 m3
It is not yet known what material will be held in the R&D facility, therefore fire load, fire risk, environmental load and environmental risk cannot yet be determined.
See above
See above
See above
Yes. Diversion of drainage to 1,000 m3 Firewater Retention Tank is proposed.
Yes, assuming firewater generated in this area could potentially be harmful to the aquatic environment. The calculated volume of potentially contaminated firewater (4,228 m3 - refer to section 8) is greater than the containment currently provided by the 1 ,000m3 Firewater Retention Tank.
JiD4500-D4599\D4.533\2) DOCUhENTS\16\REPORTSWIREWATER~RFJPORT_D4533-l6JSSUE~l.DOC
Page A20 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge lPPC Licence Review Firewater Retention Study
A20. WASTEWATER TREATMENT PLANT (WWTP)
1t+m I-k3seriptiou
Activities Treatment of facility’s wastewater
I Materials I Acid/base for neutralisation. Ozone generated in-situ. I
Fire Fighting
Destination of Firewater
Hydrants, fire brigade units if required
Runoff from the concrete apron of the WWTP is collected in a drain and discharged back into the WWTP. This runoff may also be diverted to the Firewater Retention Tank if required.
1 Sprinkler Coverage Area (m’) 1 No sprinkler system present in this area I
Quantity of Firewater run-off Cm31
Fire hydrant 2 No (Appendix C2): 13m3/minx 12Omin=
Fire brigade units =
Total fire suppression water volume =
1,170 m3
22 m3
1,192 m3
I Fire Load
Fire Risk
Environmental Load
Low
Low
I Environmental Risk I Low
Containment available Runoff from the concrete apron of the WWTP will be collected in a dram and discharged back into the WWTP.
Containment required No, as environmental risk is low.
J:ID4500-D4599U)4533\2) Page A2 1 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Arup Consulting Engineers
APPENDIX B Flammable/Harmful to the Environment Materials used on-site
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
Bl. MATERIALS INVENTORY - FLAMMABLE & HARMFUL TO THE ENVIRONMENT
The following is an inventory of materials (taken from the response to Question 10 of the application for the last IPPC licence review) held at the WMI Newbridge site that are flammable and/or have been designated risk phrases R50/5 l/52/53.
l R50 Very toxic to aquatic organisms l R51 Toxic to aquatic organisms. l R52 Harmfnl to aquatic organisms. l R53 May cause long-term adverse effects in the aquatic environment
01&6/zO186/ TrlzO18710187)
l
lo As defined in Schedule 2 of S.I. No. 77/1994: European Communities (Classification, Packaging, Labelling and Notification of Dangerous Substances) Regulations, 1994
Page B 1 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
hexahydrate merck Cyclohexane Highly flammable, 0.005
IDiethyl ether 1 Highly flammable, 0.0027 0.0027 Lab Chemical
Diethylamin
- _ Harmful
Highly flammable,
~Di-isopropyl ether Ethanol Ethyl acetate Heptane
Hydranal solvent
Corrosive Highly flammable
Highly flammable, Irritant Highly flammable, Irritant
Highly flammable, Harmful
Highly flammable, Toxic
Hydranol titrant Methanol Methyl-isobutyl-ketone N-Hexane
Nitroethane N-pentane romil Pentane Perchloric acid
I - C - Highly flammable, Toxic
Highly flammable, Toxic Highly Flammable, Irritant
Highly flammable, Harmful
Flam, Toxic, Carcinogen Highly flammable Highly flammable Highly flammable,
Petroleum ether Aldrich Corrosive
1 Highly flammable,
Potassium permanganate GPR
Harmfnl Highly flammable
Pyridine Highly flammable, Harmfnl
Sodium nitrite super free Highly flammable, Toxic flowing Tert-butyl methyl ether BDH Highly flammable Tetrahydrofuran Highly flammable, Irritant Toluene Highly flammable,
Harmfnl Triethylamine Highly flammable,
Corrosive 1,4-Dioxan 1 Highly flammable, may
I Hydranal Coulomat
for explosive peroxides, Irritant, limited evidence of carcinogenic effects
1 Highly flammable. Toxic -Methanol >60% -Imidazole 515% -SulTphur dioxide Diethanolamine Hydranal Water Standard
- * by inhalation
Flammable
Lab Chemical
0.01 0.01 Lab Chemical
0.00125 I.00125 Lab Chemical 0.02 0.02 Lab Chemical
0.0125 0.0125 Lab Chemical 0.03 0.03 Lab Chemical
0.012 0.012
0.007
Lab Chemical
0.007 0.332
0.0025 0.02
0.332 0.0025 0.02
Lab Chemical Lab Chemical Lab Chemical Lab Chemical
0.01 0.01 Lab Chemical 0.0125 0.0125 Lab Chemical 0.005 0.005 Lab Chemical 0.01 0.01 Lab Chemical
0.04
<O.OOl
0.03
0.0125 0.0025
0.012
<O.OOl
0.0075 0.025 0.015
0.01
0.01
0.012
<O.OOl
Lab Chemical
Lab Chemical R8/25
0.0075 0.025 0.015
0.06
Lab Chemical R36/37/38 Lab Chemical Rl l/19/36/37 Lab Chemical Rl l/20
Lab Chemical Rl l/20/21/22
0.035 Lab chemical
0.001 0.002 Lab chemical
0.00012 0.00024 Lab chemical RI0
0.04
<O.OOl
0.03 Lab Chemical Rl l/36/67
0.0125 Lab Chemical Rl l/41/67 0.0025 Lab Chemical Rl l/20/
Lab Chemical
Lab Chemical
.l l/38/50/53/65/67
R12/19/22/66/67
R22/38/41/48/22
Rl l/19/66/67 Rll
Rl l/36/ 66167 Rl l/38/
50/53/65/67 Rl/23/25/34
Rl li23/24/25/39 Rl ll20/36l37/66 Rl li2Ol36l37l66
Rl O/20/22 Rll Rll
R5/8/35
:l lJ23l25i36/37l38 I65
R8/22/50/53
21122 Rl l/20/ 21/22
Rll-19-36/37-40- 66
Rl 1,23/24/26 39/23/24/25 4 1
J:U)4500-D4599U)4533\2) DOCUMENTS\16tREPORTS\FIREWATER~REPORT_D4l.DOC
Page B2 Arup Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
-
Risk Phrase’”
Lab chemical R23/24/25-40- 48123 -52153 -59
Lab chemical Rl I-23/24/25-34- 39/23/24/25
Lab chemical R34-50
Lab chemical RlO-35
Lab chemical RlO-21122-35 Facilities Eng R38/41
Facilities Eng Facilities Eng R20/21/38/22
Facilities Eng I
Facilities Eng
Facilities Eng
Facilities Eng
110/l 1l2Ol21/22/36 I37138
R10/20/21/38/37
R10/11/20/21/38
RlOll l/20/21/38
Cleaning
Cleaning Engineering Store
Rll R36 R67
Engineering Stan
Engineering Store Excipient
RI 1120
R 11/36/67
R12 Rl l/20
-Anisole >60% -Propylene Carbonate Carbon Tetrachloride
I Toxic, Harmful, 1 0.01
Boron Trifluoride methanol complex -methanol -boron trifluoride methanol complex Ammonia Solution AnalaR
Dangerous to the environment, limited
:vidence of a carcinogenic effect
Highly Flammable, Toxic 0.001
I Perchloric Acid -Acetic Acid -Perchloric Acid Hexvlamine. 99% Fusilade Fluazifop-p-Butyl Nettleban HGW White Spirit Basec Decorative Products - MSD! 101
Corrosive, Dangerous to the Environment
Corrosive, Flammable
0.005
0.0075
Corrosive, Flammable 0.0001 Flammable, Toxic to co.002
aquatic organisms Flammable, Toxic to Fish co.002
Flammable <O.OOl
Highly Flammable, Harmful
Flammable
<O.OOl
<O.OOl MSDS 103 HGW Two Pack Epoxy
Products - MSDS 105
Highly Flammable, Harmful
Highly Flammable, Harmful/Irritant
<O.OOl
<o.oo 1
20035) - Butan- l-01 - Ethyl acetate
Flammable co. 1
Highly Flammable 2 Highly flammable, ’ <0.001
Harmful by Inhalation Highly Flammable <O.OOl
Extremely Flammable <O.OOl Highly flammable, 0.012
Harmful by inhalation
1Isopropanol Highly flammable, Irritant 0.158
l
0
0.01
0.001
0.01
0.01
0.0002 <0.002
<0.002 <O.OOl
<o.oo 1 i
Diluent for Ink Rl l/36/67
<o.oo 1
<O.OOl
<o.oo 1
<O.OOl
4 <0.01
<O.Ol
<O.OOl 0.052
0.16
J:\D4500-D4599!D4533\2) Page B3 Arup Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:31
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
The total quantities of the above materials are summarised in the following table according to the their nature of use:
Highly Flammable 0.574 0.824
Solvents I I I
Toxic, Harm&l, 1 69.59 1 177.47
Packaging
Lab Chemical
Facilities Eng
Cleaning
Engineering Store
Excipient
Diluent for ink
Highly Flammable Highly Flammable
Irritating Flam, Toxic, Carcinogen
cl0 cl2
cl.051 d.076
Flammable/Highly Flammable Harmful/Irritant
Highly Flammable
0.009 0.009
c2.1 c4.01
Highly Flammable co.003 co.021
Highly flammable, Harmful by 0.012 0.052 inhalation
Highly flammable, Irritant 0.158 0.16
. , I s.,:’ * L
Jm4500-D4599\D4533\2) .I,. .,. . ,
DOC~~S\16\RePORTS\mREWATER_REPORT~~””” ” -“--- . --- tJw~J-Io~IDI)“~~L”“L Page B4 Amp ~onhing E&neers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:32
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
B2. MATERIALS INVENTORY - HARMFUL TO THE ENVIRONMENT 0 The following is an inventory of materials held at the WMI Newbridge site that have been designated risk phrases R50/5 l/52/53.
1, 10 phenantbroline ferrous , Irritant 1 CO.01 1 CO.01 , Lab Chemical 1 R25/50/53 I indicator BDH 2, 2,4-Trimethylpentane Highly flammable,
Harmful 0.05 <O.l Lab Chemical Rl l/38/
5Ol53/65/67 Cadmium sulphate I Toxic I 0.0025 I 0.0025 I Lab Chemical 1 R49/50/53 Copper II ethylendediamine Harm, Corrosive 0.003 0.003 I Lab Chemical 1 R22-36138-50153
environment, limited evidence of a
48123 -52i53 -59
carcinogenic effect Ammonia Solution AnalaR Corrosive, Dangerous to 0.005 0.01 Lab chemical R34-50
the Environment
The quantities of materials with the risk phrases is as follows:
R51
R52
R53
Toxic to aquatic organisms
Harmful to aquatic organisms
May cause long-term adverse effects in the aquatic environment
10 0
100 0.01
1,000 0.113
J:U)4500-D4599\D4533\2) Page B5 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:32
Arup Consulting Engineers
APPENDIX C Fire suppression methods
---0
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:32
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
Cl. SPRINKLERS
The following sprinkler specifications were supplied by WMI” (where sprinklers are designed to discharge at a rate of X when supplied with water at a rate of Y gallons/mm over a maximum floor area of Z):
1 - Cafeteria No information [i&I34 IlA - Admin 0.21 9271 30001 IA1 12 - Packaging INo information]
I I Solution Prep and Glatt 60 Rooms
J 4 - Warehouse 0.45 1705 2500 4A - Warehouse No information
I 4A - HRT PrntLSort /No information1 Jl 5 - Utility No information
5 - Cooling Towers 0.52 55.6 129 FM2 9 - AS/RS South 495.4 FM6 9 - ASIRS North 1407 FM10 9-ASIRS 1405.8 FM14 9 -AS/I&’ 449 FM18 9-ASIRS 0.3 1009 3200
I I Solvent and Aqueous Waste Tank Farm I I I
7ipq-q
8 2,731 279 8 3,432 279 8 2,232 279 6 834 139
121 3.3481 2791
18 61458 232
21.1 211 12 18.3 1,875 280 18.3 5,326 280 18.3 5,321 280 18.3 1,701 280
12 3,822 297
10 6148 365
” Amp converted the data to metric units
Page C 1 Amp Consulting Engineers Issue 22June2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:32
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
c2. HYDRANTS
The following fire hydrants are provided on site (as specified in the Fire and Safety Industries monthly report on fire extinguishers, pin-racks and hose reels, and fire hydrants of 28 February 2005):
I I I I
2 Pillar 2 Building 2 entrance 6500
3 Pillar
4 Pillar
2 Car park 2 west 6500
2 Car park 2 west 6500
5 Pillar
6 Pillar
7 Pillar
8 Pillar
9 Pillar
10 Pillar
2 West side of house 1 pump 6500
2 Waste recycling B-4 area 6500
2 Rear of house 2 pump 6500
2 South of boiler house 6500
2 East side of boiler house No data available
2 North side of boiler house 550012
11 Pillar
12 Pillar
13 Pillar
14 Pillar
15 Pillar
16 Pillar
2 Side of Building 1-A 6500
2 Offices front 6500
2 Side of B 3-A 6500
2 Rear of B9 6500
2 Rear of B9 warehouse 6500
2 East end of B9 warehouse 6500
17 1 I I I
Pillar 2 East end of 3-B 6500
18 LN13
19 LN
1 Pump house 1 supply 6500
1 Pump house 1 inward
20 I I I I
LN 1 Pump house 2 supply 6500
21 I 1 I
LN 1 Pump house 2 supply
l2 Delivering reduced flow at time of testing l3 LN = landing valve above ground water mains
UD4500-D4599u)4533\2) DOCUMENTS\16\REPORTS\FIREWATER_REPORT_D4l.DOC
Page C2 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
l
l
~ Arup Consulting Engineers
APPENDIX D Methodology for Determining Environmental Risk
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Wyeth Medica Ireland, Newbridge IPPC Licence Review Firewater Retention Study
a Dl. ENVIRONMENTAL RISK ASSESSMENT
An objective, qualitative assessment of the environmental risk was carried out, taking into account the following factors:
l Fire load
l Fire risk
l Environmental load
The environmental risk posed is assessed without regard to existing containment facilities. Therefore, if the risk is medium or high, no action may be required if existing pollution prevention/mitigation measures are deemed adequate.
Significance criteria of ‘low’, ‘medium’ and ‘high’ were assigned to the above factors based on the experience of Amp Menzies. Environmental risk is determined using decision matrices based on these factors (refer to Appendix D2).
Dl .I Fire Load
The fire load is a function of the quantity of combustible materials present and the likely rate of combustion. The following broad classification of fire load is used:
‘: Non-combustible materials, such as-aqueous solutions, metal items (machinery, storage racking) or glass, and mater&s with small combustible element, e.g.
quantities of packing materials, combustible materials (e.g.
oad stationery etc ombustible materials, or large quantities of flammable
D1.2 Fire Risk
The risk of fire depends on the following factors:
l Risk of ignition
l Risk of non-detection
l Risk of failure to extinguish promptly
The risk of ignition of a material is lowest where flammable and highly flammable liquids, flammable solids and gases are not present at a location, or where only small quantities of these materials are present.
The risk of non-detection of a fire outbreak is highest where the relevant area is unoccupied for most of the time, and where no automatic fire detection or sprinkler system is present.
The risk of failure to extinguish a fire promptly, given that the fire has been detected promptly, is low, where automatic sprinklers are provided, and medium elsewhere where sprinkler coverage is not provided.
J:u)4500-D4599u)4533\2) DOCUMENTS\16\REPORTS\mREWATER_RePORT_D4533-l6~ISS~~l.DOC
Page Dl Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
The following classification of fire risk is used: /: ,j-&+&$$ ‘! A fire is unlikely : &&&&@& ” A fire is credible “.m& m& ” A fire is possible ;
The flammable (EC Risk Phrase RlO - Flammable, Rl 1 - Highly Flammable, R12 - Extremely Flammable) materials used on site are listed in Appendix B.
D1.3 Environmental Load
The environmental load is an assessment of the total potential for environmental damage. The environmental load depends on the characteristics and quantities of materials that could cause environmental damage, in this case contamination of the receiving surface waters and/or groundwater.
The characteristics of environmental load include:
. BOD
0 acute toxicity effects
l persistence of the pollutant
0 risk of bio-accumulation
The following classification of environmental load is used:
"~~~~~~ .' Little potential for my signific~t damage to the receiving waters
:. :
~~~~iliili’~~~: Potential for minor damage or likely long term effects to the receiving :..a:.. . . i:::$i$$s .~:~~;,~~,~~ $ : waters . . . . . . ::.:::.:::.:.:::::::::::.:.:.. ;.. :.. .:’ /. ..:.:.:.,.& ‘~~~~~~~~:~~~~ Potential for significant damage, and likely long term effects to the
:::I:,?:: :‘:~~ : ret eivhg waters . . .A........ / .::::. ::::: .:.
D1.4 Environmental Risk
Environmental risk includes the fire risk and fire load, the environmental load, and the area at risk (receptor). The evaluation of the environmental risk of a receptor includes:
l The extent of the pollution of the receiving water
l Any uses to which the receiving waters are put (potable water, livestock water, crop irrigation, fishing, amenity use, wildlife habitat, etc.)
The following classification of environmental risk is used:
~1 Risk not significant, but some additional protective measures may be .: ::. .’ .’ .:: required in the long term 1 :.‘..: .,.,,, ^ :m.:.:.: :.: _ ) :.: ., . . . . . . . . . . . . . . . . . . . . . .::: _ :::$:.:.g.:&
M&&f@&~' i
Discernible ~sk,~dremedial works and/oradditionalprotective measures
.::.. ." ..,. :. : ‘. '. will be required within 12 months, unless an earlier opportunity is afforded yp>,,J$~ .:.. ;. ..:‘: .. ..:::.:.: ‘/:/::” ,.‘i:;! by other works at the site.
; :. ~~~~~:‘~~ H azardous situation vis-a-vis the environment (receiving waters), and action ~,,,,,?~ is required i~ediately
J:ID4500-D4599\D4533\2) Page D2 Arup Consulting Engineers DDCUMENTS\16\REPORTS\FIREWATER_REPORT_D4l.DDC Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiiewater Retention Study
ENVIRONMENTAL RISK DECISION MATRICES
The environmental risk assessments of the main areas of the WMI facility are set out in Appendix A.
If environmental load is low the environmental risk is determined as follows (H = high, M = medium, L = low):
Low environmental lOad
If environmental load is medium the environmental risk is determined as follows:
If environmental load is high the environmental risk is determined as follows: High environmental lOad
Page D3 Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Arup Consulting Engineers
APPENDIX E Fraction of firewater runoff
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Wyeth Medica Ireland, Newbridge IPPC Licence Review Fiwater Retention Study
El. FRACTION OF FIREWATER RUNOFF
This calculation is adapted from a method used to measure stormwater pollutant loads. It is deemed suitable as the initial stage of the process requires calculation of annual rainwater runoff as a product of annual rainfall volume. This is obviously of interest for the purposes of this report, as a large percentage of the WMI facility is green/vegetated area, and the rainfall which flows to the site stormwater drainage system is to be included in any firewater retention calculations, according to the EPA Draft Guidance Note14.
Runoff volume is calculated as:
R=PxP,xR?
Where: R = runoff (inches) P = rainfall (inches) Pj = Fraction of rainfall events that produce runoff (usually 0.9) Rv = Runoff coefficient
I.11
Rv can be obtained from: Rv =0.05+0.9Ia PI
Where: Ia = Impervious fraction Substituting (2) into (l), and assuming Pj equals 1 (since Pj is the fraction of annual rainfall events that produce runoff, and the event in question is the 20-year, 24-hr return, a large rainfall value). The equation becomes:
R=0.05P+0.9xlaxP 131 As highlighted previously, the hardstanding (paved) area of the site is S3,000m2, and the green site area is 50,600 m2. Thus Ia, the impervious fraction is:
la = 83,000 =0.621
83,000+50,600
Thus, the fraction of rainfall that results in runoff during a 20-year, 24-hr return event can be obtained by rearranging equation [3] and substituting the value of Ia as follows:
R -=0.05+0.9x0.621= 0.61 P
i.e. 61% of rainfall falling on green areas during a 20-year, 24-hr return event would flow to stormwater drainage.
: , ,‘;
l4 EPA (Draft) Guidance Note to Industry on Requirements for the Establishment of Fire Water Retention facilities (2 August 1995).
J:u)4500-D4599u34533\2) DOCUMENTS\16NEPORTS\FIREWATER~REPORT_D4l.DOC
Page El Amp Consulting Engineers Issue 22 June 2005
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:33
Arup Consulting Engineers
APPENDIX F Drainage lines firewater retention capacity
: “
. . , :
For
insp
ectio
n pur
pose
s only
.
Conse
nt of
copy
right
owne
r req
uired
for a
ny ot
her u
se.
EPA Export 25-07-2013:15:15:34
Wyeth Medica Jreland, Newbridge IPPC Licence Review Firewater Retention Study
0 Fl. DRAINAGE LINE CAPACITY CALCtiLATlON
The lowest level manhole cover and gullies on both drainage lines were found using data obtained from the recent RPS report into surface water drainage and testing, specifically drawing no. DG-0010’5.
It is assumed that the water rises to just below the level of the lowest egress point at which it could escape. In the south line, this is the manhole cover at S88b, the shipping/receiving area. The cover level of this manhole is measured at 84.043m (above sea-level). The lowest egress point on the north line is the gully situated at S37, east of building 3B, measured at 85.499m.
The volume of the available drainage line below this level was then calculated using pipe diameters.
. Drawing Title: %nfaCe Water Date 17/05/04. l5 Project: Drainage and Survey Testing
Page Fl Amp Consulting Engineers Issue 22 June 2005