Test Report CESI Approved Page 5
M2029IG
Short-circuit tests with three-phase current Test circuit: M0002 Test frequency: 50 Hz Reference number of the oscillograms: A9023185 Conditions of the transformer before the tests: as supplied by the Client Transformer prearranged on the voltage ratio: 11 kV / 0,415 kV Date: August 7, 2009
Tap-changer No-load Test current
Test Oscillogram position supply peak r.m.s. average Duration
voltage value value value
No. No./sheets - V A A A s 22740 22690 1 1/1 0 -
56900 22870 22770 0,1
33290 82790 33170 2 2/1 0 -
33340 33260 0,5
33380 82180 33270 3 3/1 0 -
33500 33380 0,5
33340 83140 33270 4 4/1 0 -
33570 33390 0,5
85460 34640 34590 5 5/1 + + - 34810
34680 0,5
86750 34800 34660 6 6/1 + + - 34940
34800 0,5
85920 34960 34710 7 7/1 + + - 34990
34880 0,5
32810 32920 8 9/1 - - -
81370 33130 32960 0,5
32800 32960 9 10/1 - - -
81700 33220 32990 0,5
32780 32900 10 11/1 - - -
82280 33260 32980 0,5
Conditions of the transformer after the tests: see notes
- Externally didn’t show any sign of damage or deformation