REPORT SAMPLE
Saturday, April 7, 2018
Andruch Home Inspections, LLC
907 Sandalwood Road West
Perrysburg, OH 43551
567 331-2280
www.andruch.comAHI@andruch.com
July 18, 2018
Dear Report Sample,
RE: Report No. 1003, v.2123 MyRoadAnytown, OH123456
Thank you very much for choosing AHI to perform your home inspection. We trust the experience was both useful andenjoyable.
Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourageyou to read the Standards of Practice so that you clearly understand what things are included in the home inspection andreport.
The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not beresponsible to any parties for the contents of the report, other than the party named herein .
The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectorscannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. Ifconditions change, we are available to revisit the property and update our report.
The report itself is copyrighted, and may not be used in whole or in part without our express written permission.
Again, thank you very much for choosing Andruch Home Inspections, LLC to perform your home inspection.
Sincerely,
Michael Andruch IVon behalf ofAndruch Home Inspections, LLC
Andruch Home Inspections, LLC907 Sandalwood Road West
Perrysburg, OH 43551567 331-2280
www.andruch.comAHI@andruch.com
INVOICE
July 18, 2018
Client: Report Sample
Report No. 1003, v.2For inspection at:123 MyRoadAnytown, OH123456on: Saturday, April 7, 2018
Home Inspection 1,501 to 2,000 sq/ft $375.00
Total $375.00
PAID IN FULL - THANK YOU!
Andruch Home Inspections, LLC907 Sandalwood Road West
Perrysburg, OH 43551567 331-2280
www.andruch.comAHI@andruch.com
AGREEMENT
PARTIES TO THE AGREEMENT
CompanyAndruch Home Inspections, LLC907 Sandalwood Road WestPerrysburg, OH 43551
ClientReport Sample
Total Fee: $375.00
This is an agreement between Report Sample and Andruch Home Inspections, LLC.
PROPERTY INSPECTION AGREEMENT
THIS CONTRACT LIMITS THE LIABILITY OF ANDRUCH HOME INSPECTIONS, LLC AND ITS MEMBERS, PLEASEREAD CAREFULLY BEFORE SIGNING.
This agreement is entered into between Andruch Home Inspections, LLC (AHI), and (Customer) to conduct a visualinspection (Inspection) and prepare a printed or electronic report (Report) based on said Inspection, of property locatedat (Property).
AHIs fee for the inspection of the Property shall be (Fee). Inspections canceled within 24 hours of the scheduled timeshall be subject to a cancellation fee equal to 50% of the Fee. The Fee shall be paid in full prior to the commencement ofthe Inspection or immediately at the conclusion of the Inspection. Bounced or stopped checks, stopped credit cardpayments, or any similar action by the customer that prevents AHI from collecting its Fee shall be subject to applicablebank fees, interest at the rate of 1.5% per month, and all costs of collection, including but not limited to attorneys fees.
In addition to the limitations in the (ASHI) American Society of Home Inspectors Standards of Practice, the Inspection ofthis property is subject to the Limitations and Conditions set out in this Agreement. The Inspection is performed inaccordance with the Standards of Practice of the ASHI.
LIMITATIONS AND CONDITIONS OF THE HOME INSPECTION
There are limitations to the scope of this Inspection and Report. It provides a general overview of the more obviousrepairs that may be needed. It is not intended to be an exhaustive list. The ultimate decision of what to repair or replaceis yours. One homeowner may decide that certain conditions require repair or replacement, while another will not.
1) THE INSPECTION IS NOT TECHNICALLY EXHAUSTIVE. The Inspection and Report provide you with a basicoverview of the condition of the property. Because AHI has only a limited amount of time to go through the property, theInspection is not technically exhaustive. Some conditions noted, such as foundation cracks or other signs of settling in ahouse, may either be cosmetic or may indicate a potential problem that is beyond the scope of the Home Inspection. Ifyou are concerned about any conditions noted in the Home Inspection Report, we strongly recommend that you consult aqualified Licensed Contractor or Consulting Engineer. These professionals can provide a more detailed analysis of anyconditions noted in the Report at an additional cost.
2) THE INSPECTION IS AN OPINION OF THE PRESENT CONDITION OF THE VISIBLE COMPONENTS. AHIs Reportis an opinion of the present condition of the property. It is based on a visual examination of the readily accessiblefeatures of the building. The Inspection does not include identifying defects that are hidden behind walls, floors orceilings. This includes wiring, heating, cooling, structure, plumbing and insulation that are hidden or inaccessible. Some
Report No. 1003, v.2
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
AGREEMENT
intermittent problems may not be obvious during the Inspection because they only happen under certain circumstances.As an example, AHI may not discover leaks that occur only during certain weather conditions or when a specific tap orappliance is being used in everyday life. Home Inspectors will not find conditions that may only be visible when storageor furniture is moved. They do not remove wall coverings (including wallpaper) or lift flooring (including carpet) or movestorage to look underneath or behind.
3) THE INSPECTION DOES NOT INCLUDE HAZARDOUS MATERIALS. This includes building materials that are nowsuspected of posing a risk to health such as phenol-formaldehyde and urea-formaldehyde based insulation, fiberglassinsulation and vermiculite insulation. AHI does not identify asbestos roofing, siding, wall, ceiling or floor finishes,insulation or fireproofing. We do not look for lead or other toxic metals in such things as pipes, paint or window coverings.The Inspection does not deal with environmental hazards such as the past use of insecticides, fungicides, herbicides orpesticides. AHI does not look for, or comment on, the past use of chemical termite treatments in or around the property.
4) WE DO NOT COMMENT ON THE QUALITY OF AIR IN A BUILDING. AHI does not try to determine if there areirritants, pollutants, contaminants, or toxic materials in or around the building. The Inspection does not include spores,fungus, mold or mildew that may be present. You should note that whenever there is water damage noted in the report,there is a possibility that mold or mildew may be present, unseen behind a wall, floor or ceiling. If anyone who will live inthe Property suffers from allergies or heightened sensitivity to quality of air, we strongly recommend that you consult aqualified Environmental Consultant who can test for toxic materials, mold and allergens at additional cost.
5) WE DON'T LOOK FOR BURIED TANKS. AHI does not look for and is not responsible for fuel oil, septic or gasolinetanks that may be buried on the property. If the building had its heating system converted from oil, there will always bethe possibility that a tank may remain buried on the property. If fuel oil or other storage tanks remain on the property, youmay be responsible for their removal and the safe disposal of any contaminated soil. If you suspect there is a buried tank,we strongly recommend that you retain a qualified Environmental Consultant to determine whether this is a potentialproblem.
6) TIME TO INVESTIGATE. AHI will have no liability for any claim or complaint if conditions have been disturbed, altered,repaired, replaced or otherwise changed before we have had a reasonable period of time to investigate.
7) REPORT IS FOR OUR CLIENT ONLY. This contract is solely between AHI and Customer. It is not for the benefit ofany third party, including but not limited to any subsequent owner of the Property or lending intuition. This agreementmay not be assigned or transferred.
8) NOT A GUARANTEE, WARRANTY OR INSURANCE POLICY. The inspection is not a guarantee, warranty or aninsurance policy with regard to the condition of the property. AHI makes no warranty, express or implied, beyond thewritten terms of this agreement.
9) LIMIT OF LIABILITY / LIQUIDATED DAMAGES The liability of AHI and its members arising out of this Inspection andReport, for any cause of action whatsoever, whether in contract or in negligence, is limited to a refund of the Fee that youhave been charged for this inspection. Any action brought by the customer must be brought within one year of theinspection or be forever time barred.
10) DIACLOSURE: AHI shall keep the results of its Inspection and Report confidential between AHI and Customerunless Customer directs the disclosure to third parties. At the time of Inspection, Customer directs that AHI shoulddisclose the Report to (please check all that apply): ____ Buyer; ____ Buyers Agent; ____ Seller; ____ Sellers Agent;
Report No. 1003, v.2
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
AGREEMENT
____Lender; ____ Others (_________________________________________________).
A hand signed version of this agreement shall be signed before the start of the inspection.The parties have read and agree to the above terms.
I, Report Sample (Signature)___________________________, (Date)_______________, have read, understood andaccepted the terms of this agreement.
Report No. 1003, v.2
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
SUMMARY
This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as acourtesy and cannot be considered a substitute for reading the entire report. Please read the complete document.
Priority Maintenance Items
Roofing
SLOPED ROOFING \ Asphalt shinglesCondition: LeakMultiple wet spots were noted in the attic.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: AtticTask: Furthur investigate/repairTime: As soon as possible
Condition: DamageBroken shingle noted.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Roof WestTask: RepairTime: As soon as possible
SLOPED ROOF FLASHINGS \ Chimney flashingsCondition: Missing base or cap flashingsPoor workmanship noted on the chimney cricket detail. Exposed fasteners. Asphalt sealant is considered a temporarysolution.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: ChimneyTask: Monitor and provide proper flashing when re-roofing.Time: Ongoing
Structure
FOUNDATIONS \ GeneralCondition: CrackedEvidence of prior foundation crack repair.Implication(s): Chance of water damage to contents, finishes and/or structure | Weakened structureLocation: BasementTask: Further Investigation/MonitorTime: Ongoing
Condition: Prior repairsSteel I-beams and ejection crack repair noted as previous repairs and past foundation issues.Implication(s): Weakened structureLocation: Basement
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 1 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
SUMMARY
Task: Consult with current homeowner about repair warranty/monitorTime: Ongoing
ROOF FRAMING \ Rafters/trussesCondition: RotMultiple leaks noted at roof vents causing rafter and sheathing rot.Implication(s): Weakened structureLocation: Roof Vents/AtticTask: Furthur InvestingationTime: As soon as possible
Insulation and Ventilation
ATTIC/ROOF \ InsulationCondition: Gaps or voidsCellulite insulation is missing at the attic/wall intersection. Proven by thermography.Implication(s): Increased heating and cooling costs | Reduced comfortLocation: Throughout AtticTask: ProvideTime: Discretionary
Interior
EXHAUST FANS \ GeneralCondition: Does not discharge to exteriorImplication(s): Poor ventilation can cause condensation. | Chance of condensation damage to finishes and/or structureLocation: Throughout Second Floor AtticTask: ImproveTime: As soon as possible
EXHAUST FANS \ DuctCondition: Not vented to exteriorBathroom exhaust vents do not connect to the exterior. This is most likely causing rot/mold on the roof sheathing.Implication(s): Chance of condensation damage to finishes and/or structureLocation: AtticTask: ProvideTime: As soon as possible
This concludes the Summary section.
The remainder of the report describes each of the home's systems and also details any recommendations we have forimprovements. Limitations that restricted our inspection are included as well.
The suggested time frames for completing recommendations are based on the limited information available during a
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 2 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
SUMMARY
pre-purchase home inspection. These may have to be adjusted based on the findings of specialists.
Home Improvement - ballpark costs
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 3 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
Observations & Recommendations
General1. Our inspection of the roofing system includes the roofing material, roof drainage systems, flashing, skylights,chimneys and roof penetrations. We inspect the roof by walking on it whenever it is safe to do so.
SLOPED ROOFING \ Asphalt shingles2. Condition: LeakMultiple wet spots were noted in the attic.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: AtticTask: Furthur investigate/repairTime: As soon as possible
1. Leak
2. Leak
3. Condition: Granule lossMinor granular loos noted at the bottom edges of the shingles.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Throughout RoofTask: ReplaceTime: When Necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 4 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
3. Loss of granules
4. Condition: DamageBroken shingle noted.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Roof WestTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 5 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
4. Broken
5. Condition: PatchedPrior repairs noted on the east roof.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Various, house roofTask: MonitorTime: Ongoing
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 6 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
5. Patched
6. Condition: Exposed fastenersExposed fastener at the plumbing stack penetration.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: RoofTask: Seal fastenersTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 7 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
6. Exposed fasteners not sealed
7. Condition: Exposed fastenersFasteners are exposed under the shingles and lifting the shingles upward.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: VariousTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 8 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
7. Exposed fasteners
SLOPED ROOF FLASHINGS \ Chimney flashings8. Condition: Missing top, bottom, side flashingsMissing side flashings at the chimney.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: RearTask: Provide when re-roofingTime: When Necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 9 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
8. Missing top, bottom, side flashings
9. Condition: Missing base or cap flashingsPoor workmanship noted on the chimney cricket detail. Exposed fasteners. Asphalt sealant is considered a temporarysolution.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: ChimneyTask: Monitor and provide proper flashing when re-roofing.
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 10 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
Time: Ongoing
9. Missing base or cap flashings
SLOPED ROOF FLASHINGS \ Roof vent10. Condition: Exposed fasteners not sealedExposed fasteners at roof vent noted.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Throughout RoofTask: SealTime: As soon as possible
10. Exposed fasteners not sealed
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 11 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ROOFING
General Information
The home is considered to face : East
Sloped roofing material: Asphalt shingles Roll roofing
Sloped roof flashing material: Aluminum
Approximate age: 18 years
Typical life expectancy: 20-25 years
Inspection Methods & Limitations
Inspection performed: By walking on roof
Age determined by: Visual inspection from roof surface Receipt from roofing contractor
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 12 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
Observations & Recommendations
General11. The exterior inspection of the home includes the wall coverings, flashing, and trim, exterior doors, attached andadjacent decks, balconies, stoops, steps, porches, and their associated railings, eaves, soffits, and fascias whereaccessible from the ground level, vegetation, grading, surface drainage, and retaining walls that are likely to adverselyaffect the building, adjacent and entryway walkways, patios, and driveways.
ROOF DRAINAGE \ Gutters12. Condition: LooseLocation: Front of houseTask: RepairTime: As soon as possible
11. Loose
WALLS \ Soffits and fascia13. Condition: DamageSoffit damaged, possibly by water intrusion.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: West soffit next to chimneyTask: Repair/further investigateTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 13 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
12. Damage
WALLS \ Trim14. Condition: Paint
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 14 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
Repaint as necessaryImplication(s): Shortened life expectancy of materialLocation: Exterior trim, throughoutTask: PaintTime: Ongoing
15. Condition: Caulking missing or deterioratedMaintain caulking and paint on exterior trim.Implication(s): Chance of water damage to contents, finishes and/or structure | Material deteriorationLocation: ThroughtoutTask: Provide/repairTime: Ongoing
13. Caulking missing or deteriorated
WALLS \ Wood siding16. Condition: RotMasonite stucco board is rotted.Implication(s): Weakened structure | Material deteriorationLocation: South exteriorTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 15 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
14. Rot
WALLS \ Brick, stone and concrete17. Condition: CrackedCracked brick / mortarImplication(s): Weakened structure | Chance of movement | Chance of water entering buildingLocation: North East Corner of house/garageTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 16 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
15. Cracked
18. Condition: CrackedCracked brick/missing mortarImplication(s): Weakened structure | Chance of movement | Chance of water entering buildingLocation: Front of houseTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 17 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
16. Cracked
19. Condition: Mortar deteriorationImplication(s): Chance of water entering building | Weakened structure | Chance of structural movementLocation: Sills, throughoutTask: RepairTime: When Necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 18 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
17. Mortar deterioration
20. Condition: Too close to gradeBrick siding is below grade. Some brick is approved for below grade applications. No evidence of spalling at the time ofinspection.
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 19 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
Implication(s): Chance of water entering building | Weakened structure | RotLocation: ThroughoutTask: Further InvestigateTime: As soon as possible
18. Too close to grade
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 20 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
EXTERIOR GLASS/WINDOWS \ General21. Condition: Lintel rustingImplication(s): Chance of movement | Weakened structureLocation: Throughout ExteriorTask: PaintTime: As soon as possible
19. Lintels rusted, sagging or loose 20. Lintels rusted, sagging or loose
GARAGE \ Door into garage / Man-door22. Condition: Door not fire rated or exterior typeImplication(s): Increased fire hazardLocation: First Floor KitchenTask: ProvideTime: As soon as possible
23. Condition: Door not tight-fitting and weatherstrippedImplication(s): Increased fire hazard | Hazardous combustion products entering homeLocation: First Floor KitchenTask: ProvideTime: As soon as possible
24. Condition: No self-closerImplication(s): Increased fire hazard | Hazardous combustion products entering homeLocation: First Floor KitchenTask: ProvideTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 21 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
EXTERIOR
General Information
Gutter & downspout material: Aluminum
Gutter & downspout type: Eave mounted
Gutter & downspout discharge: Above grade
Wall surfaces and trim: Stucco Board
Wall surfaces and trim: Brick Wood
Driveway: Asphalt
Walkway: Concrete
Fence: Wood
Pergola: Adjacent
Inspection Methods & Limitations
Inspection limited/prevented by: Car/storage in garage Storage in garage
Upper floors inspected from: Ground level
Exterior inspected from: Ground level
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 22 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
STRUCTURE
Observations & Recommendations
General25. When we inspect the structural components of a home, we will look at the foundation and framing by entering readilyaccessible crawlspace and attic areas.
FOUNDATIONS \ General26. Condition: CrackedEvidence of prior foundation crack repair.Implication(s): Chance of water damage to contents, finishes and/or structure | Weakened structureLocation: BasementTask: Further Investigation/MonitorTime: Ongoing
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 23 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
STRUCTURE
21. Cracked
27. Condition: Prior repairsSteel I-beams and ejection crack repair noted as previous repairs and past foundation issues.Implication(s): Weakened structureLocation: BasementTask: Consult with current homeowner about repair warranty/monitorTime: Ongoing
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 24 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
STRUCTURE
22. Prior repairs 23. Prior repairs
ROOF FRAMING \ Rafters/trusses28. Condition: RotMultiple leaks noted at roof vents causing rafter and sheathing rot.Implication(s): Weakened structureLocation: Roof Vents/AtticTask: Furthur InvestingationTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 25 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
STRUCTURE
24. Rot
COMMENTS \ Additional29. Condition: Our structural system inspection includes the structural components including the foundation andframing. The inspection does not provide engineering or architectural services or analysis, or offer an opinion about theadequacy of structural systems and components. We do not enter under-floor crawlspace areas that have less than 24inches of vertical clearance between components and the ground or that have an access opening smaller than 16 inchesby 24 inches. We do not traverse attic load-bearing components that are concealed by insulation or by other materials.
General Information
Configuration: Basement
Foundation material: Poured concrete
Floor construction: Joists
Exterior wall construction: Wood frame / Brick veneer
Roof and ceiling framing: Rafters/ceiling joists
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 26 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
STRUCTURE
Inspection Methods & Limitations
Inspection limited/prevented by: Ceiling, wall and floor coverings Carpet/furnishings Storage New finishes/paintInsulation
Attic/roof space: Inspected from access hatch
Percent of foundation not visible: 60 %
Not included as part of a building inspection: Visible mold evaluation is not included in the building inspection report
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 27 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ELECTRICAL
Observations & Recommendations
General30. Our electrical system inspection includes visually inspecting the service drop, service entrance conductors, cables,and raceways, service equipment and main disconnects, service grounding, interior components of service panels andsub-panels, conductors, over-current protection devices, a representative number of installed lighting fixtures, switches,and receptacles, ground fault circuit interrupters and arc fault circuit interrupters.
DISTRIBUTION SYSTEM \ Outlets (receptacles)31. Condition: LooseLoose receptacle noted.Implication(s): Fire hazard | Electric shockLocation: LivingroomTask: RepairTime: As soon as possible
25. Loose
32. Condition: GFCI/GFI needed (Ground Fault Circuit Interrupter)GFCI outlets required outdoors. Also ground plug broken off in recetacle.Implication(s): Electric shockLocation: PatioTask: Provide/RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 28 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ELECTRICAL
26. GFCI/GFI needed (Ground Fault Circuit...
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 29 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
ELECTRICAL
General Information
Service entrance cable and location: Underground copper
Service size: 200 Amps (240 Volts)
Main disconnect/service box rating: 200 Amps
Main disconnect/service box type and location:Breakers - basement
The panel is new.
System grounding material and type: Copper - water pipe and ground rod
Electrical panel manufacturers: Eaton/Cutler-Hammer
Distribution wire material and type: Copper - non-metallic sheathed
Type and number of outlets (receptacles): Grounded - typical
Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): GFCI - bathroom GFCI - kitchen
Smoke detectors: Present
Carbon monoxide (CO) detectors: Present
Inspection Methods & Limitations
System ground: Continuity not verified Quality of ground not determined
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 30 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
HEATING
Observations & Recommendations
General33. When we inspect the heating system we will operate the system by manipulating the thermostat and then checkingfor appropriate temperature response. We will open readily openable access panels, inspect installed heating equipment,vent systems, flues, and chimneys and distribution systems that are readily accessible.
GAS FURNACE \ Gas burners34. Condition: RustRust was seen on the burners.Implication(s): Material deterioration | Shortened life expectancy of materialLocation: BasementTask: Furthur investigation by a qualified HVAC TechnicianTime: As soon as possible
GAS FURNACE \ Humidifier35. Condition: Clogged pad, mesh or nozzleImplication(s): Equipment not operating properlyLocation: BasementTask: ReplaceTime: As soon as possible
36. Condition: DirtyImplication(s): Equipment not operating properlyLocation: BasementTask: CleanTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 31 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
HEATING
27. Dirty
CHIMNEY AND VENT \ Metal cap37. Condition: Water pondingEvidence of ponding water and rust noted on metal chase cover.Implication(s): Reduced system life expectancyLocation: ChimneyTask: ReplaceTime: When Necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 32 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
HEATING
28. Water ponding
General Information
System type: Furnace
Fuel/energy source: Gas
Furnace manufacturer: York
Heat distribution: Ducts and registers
Approximate capacity: 100,000 BTU/hr
Efficiency: High-efficiency
Exhaust venting method: Direct vent - sealed combustion
Approximate age: 14 years
Main fuel shut off at: Meter
Exhaust pipe (vent connector): PVC plastic
Fireplace/stove: Have the chimney cleaned and inspected by a qualified chimney sweep.
Fireplace/stove: Wood-burning fireplace Zero clearance
Chimney liner: Metal
Combustion air source: Interior of building
Humidifiers: Trickle/cascade type
Location of the thermostat for the heating system: Hallway First Floor
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 33 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
HEATING
Inspection Methods & Limitations
Safety devices: Not tested as part of a building inspection
Heat loss calculations: Not done as part of a building inspection
Fireplace/wood stove: Quality of chimney draw cannot be determined Connection to chimney not inspected
Heat exchanger: Not visible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 34 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
COOLING & HEAT PUMP
Observations & Recommendations
General38. Our inspection of the cooling system includes a visual examination of the systems major components to determinedefects, excessive wear and general state of repair. Weather permitting (temperature must be greater than 60 F ordamage to the system may occur), our inspection of a cooling system includes activating the system by manipulating thethermostat and checking for appropriate temperature response.
AIR CONDITIONING \ Air cooled condenser coil39. Condition: DamageBent fins notedImplication(s): Reduced system life expectancy | Increased cooling costs | Reduced comfortLocation: RearTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 35 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
COOLING & HEAT PUMP
29. Damage
AIR CONDITIONING \ Evaporator coil40. Condition: DirtyImplication(s): Reduced comfort | Increased cooling costsLocation: RearTask: CleanTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 36 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
COOLING & HEAT PUMP
30. Dirty
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 37 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
COOLING & HEAT PUMP
General Information
Air conditioning type: Air cooled
Manufacturer: Goodman
Compressor approximate age: 5 years
Failure probability: Low
Inspection Methods & Limitations
Inspection limited/prevented by: Low outdoor temperature
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 38 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INSULATION AND VENTILATION
Observations & Recommendations
General41. The insulation and vapor retarders get inspected in unfinished spaces that are readily accessible. We check theventilation of attics and foundation areas, kitchen, bathroom, laundry, and similar exhaust systems and the clothes dryerexhaust system. We do not disturb insulation.
ATTIC/ROOF \ Insulation42. Condition: Gaps or voidsCellulite insulation is missing at the attic/wall intersection. Proven by thermography.Implication(s): Increased heating and cooling costs | Reduced comfortLocation: Throughout AtticTask: ProvideTime: Discretionary
31. Gaps or voids
ATTIC/ROOF \ Hatch/Door43. Condition: Not insulated and not weatherstrippedImplication(s): Chance of condensation damage to finishes and/or structure | Increased heating and cooling costs |Reduced comfortLocation: Access hatchTask: ProvideTime: If necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 39 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INSULATION AND VENTILATION
32. Not insulated and not weatherstripped
44. Condition: MissingThe cellulite insulation has drifted away from the front of the house
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 40 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INSULATION AND VENTILATION
Implication(s): Difficult to serviceLocation: AtticTask: Improve
33. Missing
FOUNDATION \ Interior insulation45. Condition: Missing at rim joistImplication(s): Increased heating costsLocation: Basement at AC hose and electrical penetrationTask: ProvideTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 41 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INSULATION AND VENTILATION
34. Missing at rim joist
General Information
Attic/roof insulation material: Glass fiber Cellulose
Attic/roof insulation amount/value: Not determined
Attic/roof air/vapor barrier: Not visible
Attic/roof ventilation:Roof ventSoffit vent
On garage onlyGable vent
Foundation wall insulation material: Plastic/foam board
Inspection Methods & Limitations
Attic inspection performed: From access hatch
Roof space inspection performed: From access hatch
Roof ventilation system performance: Not evaluated
Air/vapor barrier system: Continuity not verified
Mechanical ventilation effectiveness: Not verified
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 42 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
Observations & Recommendations
General46. The plumbing system inspection includes, interior water supply and distribution systems including fixtures andfaucets, interior drain, waste, and vent systems including fixtures, water heaters and hot water supply systems, ventsystems, flues, and chimneys, fuel storage and fuel distribution systems, sewage ejectors, sump pumps, and relatedpiping.
GAS SUPPLY \ Gas meter47. Condition: RustImplication(s): Equipment not operating properly | Reduced system life expectancyLocation: South side of houseTask: PaintTime: Discretionary
35. Rust
WASTE PLUMBING \ Drain piping - installation48. Condition: Nonstandard materials and patchesImplication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: Upstairs bathroomTask: ReplaceTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 43 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
36. Nonstandard materials and patches
FIXTURES AND FAUCETS \ Basin, sink and laundry tub49. Condition: LeakActive leak noted.Implication(s): Sewage entering the building | Chance of water damage to contents, finishes and/or structureLocation: Upstairs bathroomTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 44 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
37. Leak
50. Condition: LeakActive leak on the cold water side.Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: Main floor half bathTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 45 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
38. Leak
51. Condition: LooseThe laundry tub is not secured.Implication(s): Damage or physical injury due to falling materials | Sewage entering the building | Chance of waterdamage to contents, finishes and/or structureLocation: BasementTask: Secure to floorTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 46 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
39. Loose
52. Condition: Cross connectionsImplication(s): Contaminated drinking waterLocation: BasementTask: CorrectTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 47 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
40. Cross connections
FIXTURES AND FAUCETS \ Bathtub53. Condition: Caulking loose, missing or deteriorated
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 48 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
Caulking missing from tub faucetImplication(s): Chance of water damage to contents, finishes and/or structureLocation: Upstairs bathroomTask: ProvideTime: As soon as possible
41. Caulking loose, missing or deteriorated
54. Condition: Drain stop ineffectiveConnect for proper functionImplication(s): Reduced operabilityLocation: Master bathroomTask: RepairTime: As necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 49 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
42. Drain stop ineffective
FIXTURES AND FAUCETS \ Toilet55. Condition: LooseThe toilet is loose.Implication(s): Sewage entering the building | Chance of water damage to contents, finishes and/or structureLocation: Main floor half bathTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 50 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
General Information
Water supply source: Public
Supply piping in building: Copper
Main water shut off valve at the: Basement
Water flow and pressure: Typical for neighborhood
Water heater type: Conventional
Water heater fuel/energy source: Gas
Water heater manufacturer: Richmond
Tank capacity: 50 gallons
Water heater approximate age: 7 years
Waste and vent piping in building: PVC plastic
Gas piping: Steel
Main fuel shut off valve at the: Gas meter
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 51 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
PLUMBING
Inspection Methods & Limitations
Items excluded from a building inspection: Water quality Isolating/relief valves & main shut-off valve Concealedplumbing Tub/sink overflows Water heater relief valves are not tested The performance of floor drains or clotheswashing machine drains
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 52 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
Observations & Recommendations
General56. We will inspect walls, ceilings, and floors, steps, stairways, and railings, counter tops and a representative number ofinstalled cabinets, a representative number of doors and windows, garage vehicle doors and wired garage vehicle dooroperators, installed ovens, ranges, surface cooking appliances, microwave ovens, dish washing machines, and foodwaste grinders by using normal operating controls to activate the primary function.
CEILINGS \ Plaster or drywall57. Condition: PatchedDrywall settlement crack patched.Implication(s): Chance of damage to contents, finishes and/or structureLocation: StaircaseTask: MonitorTime: Ongoing
43. Patched
WALLS \ Plaster or drywall58. Condition: CrackedDrywall cracks noted in ceilingImplication(s): Damage or physical injury due to falling materialsLocation: GarageTask: Repair/Monitor
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 53 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
44. Cracked
DOORS \ Doors and frames59. Condition: StiffDoor does not fully close.Implication(s): Reduced operabilityLocation: Upstairs red bedroomTask: RepairTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 54 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
45. Stiff
DOORS \ Hardware60. Condition: Does not latch properlyDoor hardware does not engage.Implication(s): System inoperative or difficult to operateLocation: Blue bedroomTask: Adjust strike plateTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 55 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
46. Does not latch properly
EXHAUST FANS \ General61. Condition: Does not discharge to exteriorImplication(s): Poor ventilation can cause condensation. | Chance of condensation damage to finishes and/or structureLocation: Throughout Second Floor AtticTask: ImproveTime: As soon as possible
EXHAUST FANS \ Duct62. Condition: Not vented to exteriorBathroom exhaust vents do not connect to the exterior. This is most likely causing rot/mold on the roof sheathing.Implication(s): Chance of condensation damage to finishes and/or structureLocation: AtticTask: ProvideTime: As soon as possible
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 56 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
47. Not vented to exterior
GARAGE \ Floor63. Condition: CrackedTypical crack in concrete floor noted in garage.Implication(s): Uneven floorsLocation: GarageTask: Monitor/RepairTime: As necessary
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 57 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
48. Cracked
General Information
Major floor finishes: Carpet Laminate Ceramic Vinyl
Major wall finishes: Plaster/drywall
Major ceiling finishes: Plaster/drywall
Windows: Single/double hung Wood
Glazing: Double
Exterior doors - type/material: Hinged Sliding glass Plastic/fiberglass Garage door - metal
Evidence of basement leakage: Recent exterior excavation Storage kept off floor Dehumidifier in basementPrior repairs
Bathroom ventilation: Exhaust fan
Laundry room ventilation: Clothes dryer vented to exterior
Inspection Methods & Limitations
Inspection limited/prevented by: Carpet Storage/furnishings New finishes/paint Storage in closets and cabinets/ cupboards
Not included as part of a building inspection: Carbon monoxide detectors Security systems and intercomsCosmetic issues Perimeter drainage tile around foundation, if any Decorative items Aesthetics or quality of finishesVermin, including wood destroying organisms. Underground components (e.g., oil tanks, septic fields, underground
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 58 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
INTERIOR
drainage systems) Environmental issues including asbestos
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 59 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
Observations & Recommendations
General64. We will run the major appliances through the RecallChek program to determine if any off the appliances have beenrecalled.
General Information
Air Conditioner / Heat Pump:Goodman
49. Goodman
50. Goodman
Furnace:York
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 60 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
51. York
Water Heater:Richmond
52. Richmond
Refrigerator:GE
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 61 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
53. GE
Whirlpool
54. Whirlpool
Freezer:Kenmore Elite
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 62 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
55. Kenmore Elite
Range:Kenmore
56. Kenmore
Dishwasher:Whirlpool
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 63 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
57. Whirlpool
Washer:Frigidaire
58. Frigidaire
Dryer:Frigidaire
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 64 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
RECALLS
59. Frigidaire
Garage Door Opener:General
Chamberlin
60. General
END OF REPORT
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 65 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE
REFERENCE LIBRARY
The links below connect you to a series of documents that will help you understand your home and how it works. Theseare in addition to links attached to specific items in the report.
Click on any link to read about that system.
01. ROOFING, FLASHINGS AND CHIMNEYS
02. EXTERIOR
03. STRUCTURE
04. ELECTRICAL
05. HEATING
06. COOLING/HEAT PUMPS
07. INSULATION
08. PLUMBING
09. INTERIOR
10. APPLIANCES
11. LIFE CYCLES AND COSTS
12. SUPPLEMENTARY
Asbestos
Radon
Urea Formaldehyde Foam Insulation (UFFI)
Lead
Carbon Monoxide
Mold
Household Pests
Termites and Carpenter Ants
13. HOME SET-UP AND MAINTENANCE
14. MORE ABOUT HOME INSPECTIONS
123 MyRoad, Anytown, OH April 7, 2018 www.andruch.com
Home Inspections performed with Honesty and Integrity...every time.
Report No. 1003, v.2
Page 66 of 66
SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING COOLING INSULATION PLUMBING INTERIOR
RECALLS REFERENCE