Post on 15-Jan-2016
1
Welcome To the AVO International Meter Adapter Recorder
Presentation
This Presentation will Take about 15 Minutes
Click the Right Arrow Button or Press Enter to Advance
2
AVO InternationalMeter Adapter Recorders
High Performance Power Monitoring
For Light Commercial/Residential Sites
3
Requested By Many Utilities
Meter Adapter Recorder Capable of Measuring Voltage and Current of Electrical Service at Meter
Current Values Help Determine Source of Problem(System Side or Load Side)
Safe (no external wires/boxes) Convenient (Meter Forms 2S, 12S, 25S) Extremely Easy To Use
4
State of The Art Technology
High Speed DSP (Digital Signal Processor)• 256 Samples/Cycle Sample Rate
Flash Memory• Easy Field Upgrades (Enhancements, etc).• Upgrade in Minutes (By You) vs. Days (Factory)
Universal Meter Adapter• 190 A Ring/Ringless
Optically Isolated RS232 Port• Don’t Lose Your Neutral and Feed 120vac to Your Laptop!
5
Ground Clip- Must be connected
to neutral in meterbase
= Exclusive Feature
6
Ground Clip
Descriptive LED’sIndicate ProblemsWhile ConnectedTo The ServiceMonitored
= Exclusive Feature
7
Ground Clip
Descriptive LED’sIndicate ProblemsWhile ConnectedTo The ServiceMonitored
= Exclusive Feature
RemovableJaw to 6 or 9O’Clock Positions(Network Meters)
8
Manual ON/OFF Switch
Ground Clip
Descriptive LED’sIndicate ProblemsWhile ConnectedTo The ServiceMonitored
= Exclusive Feature
RemovableJaw to 6 or 9O’Clock Positions(Network Meters)
9
Real Time Display Toggles Between L1, L2 and Countdown Time to Start Recording- Indicates Unit Is Working Properly
Manual ON/OFF Switch
Descriptive LED’sIndicate ProblemsWhile ConnectedTo The ServiceMonitored
Ground Clip
RemovableJaw to 6 or 9O’Clock Positions(Network Meters)
= Exclusive Feature
10
Pull The Meter
Easy to Install and Use
11
Plug in the MeterAdapter Recorder
Easy to Install and Use
12
Plug Meter Into Meter Adapter Recorder and Attach Seal
Easy to Install and Use
13
DONE!!
Easy to Install and Use
14
Parameters Measured
2 Line-Neutral Voltages• Calculated L-L Voltage (By adding 256 Samples/Channel)• Works For 120/240v or 120/208v Services
2 Line Currents (L1 & L2) Captive Integral CT’s• Calculates Neutral Current (Subtract 256 Samples/Line
Current)
15
Operation
You Specify Recorder Response Time, or How Often TRMS Values are Calculated(1 - 60 cycles)
You Specify Data Storage Interval(1 cycle to 4 Hours)
Recorder Automatically Computes TRMS Value per Selected Response Time and Storage Interval
16
Operation
Recorder Stores Highest, Lowest TRMS Value in Storage Interval as Well as TRMS Value over Storage Interval
Result: You Capture Highest/Lowest 1 Cycle Events/Storage Interval Regardless of Storage Interval Length
This is the 1st Type of Continuous Recording
17
Out Of Limits Recording
This is the 2nd Type of Simultaneous Recording Based On Limits You Set, Recorder will Separately Start
Logging Events in the Out Of Limits Report as Soon as They are Detected
Limits Can be Set for: Swells/Sags, THD, Spikes as Fast as 65 microsec (1/256th of a cycle)
18
Use Included 32-Bit, Windows Software to Set Limits
Type of Limit Turn Limit ON
Limit Value THD Limits
Subcycle Transient Limit
= Exclusive Feature
19
Indicating LEDs
At a Glance, External Indicating LED’s () Tell You if any Events Occurred During the Test.
The GE Flicker Table and a Special Loose Neutral Algorithm are Used.
R Recording/Not Recording
N Suspected Loose Neutral
F Flicker Events
H Harmonic Events
S Swell/Sag/Sub-Cycle Events
= Exclusive Feature
20
Ease Of Use & Flexibility
Display Tells Installer Unit Is Working And Will Record Correct Values
Countdown Time (Programmable) Tells User Time Before Recording Will Start
Many Different Ways To Start Recording
= Exclusive Feature
21
StartRecordingWith Manual Switch
CurrentPresent StartsRecording
Specify Starting Date,Time and Length (Hours)
Specify Recording Start Delay Time
Voltage Present Starts Recording
22
Generating Charts with AVO-Metrosoft is a Snap!
5 - Click on Create!!
1- Select the datafile you Wish to Chart 2- Select
Type Of Chart3- Select Items To Chart
4- Select Trace Colors
And Here It Is! Ready to Print, Export, or Cut-and-Paste into a Document or SpreadsheetThis is a 19 Day Recording - Notice the Outage
24
Outage
To Zoom, just hold down the mouse button, drag the cursor to box in the area of interest, release and ZOOM!
25
Power Quality/Power Flow Options
Two Key Options are Available at a Low Cost
Power Quality Option Captures Waveforms Based on Event (Surge/Sag, THD, Sub-Cycle) Trigger or Time Trigger
You can See Disturbances, Select Waveforms and Do Harmonic Analysis
By Capturing Post-Trigger Cycles, You can See how the Disturbance Resolved Itself
26
Power Quality Option: Waveform Capture/Harmonic Analysis- Here is a lighting strike in the vicinity of this residence
27
1 - Select a Waveform with the Cursor
2 - Click on Createfor a HarmonicAnalysis
Harmonic Analysis
28
HarmonicSummary
SelectedWaveform
Detailed Harmonic AnalysisAnd Here Is The Harmonic Analysis!!
29
KVAH
KWH
PF
Power Flow Option:Record all Key Power Parameters, Investigate Billing Complaints, Even Look at Vector Relationships
30
Reports
AVO-Metrosoft Can Automatically Generate Many Different Reports For You:
• Tabular Reports (basic raw data)• Out of Limits Reports (Event Data)• Weekly Energy Report (a whole single week for any one
selected demand parameter)• Voltage Regulation Report
31
Tabular Report: Voltage/Current
32
Note that Power by phase as well as total, and also true pf,displacement pf,voltage and current imbalance per demand interval are presented.
Tabular Report: Demand
33
Out of Limits Report (Event Data)
Event Details
Event Summary with
type of event
34
Summary
Why have we built so much power into a residential unit?• Because Power Quality Problems Have Found Their Way into
The Home–Many Home Offices with Sensitive Equipment and
UPS’s/Surge Arrestors–Chips in Many New Appliances
• To Protect Your Investment With De-regulation, Power Quality Problems in the
Home/Light Commercial are Going to Get Worse, Not Better
35
Summary, Continued
mr-2/4 Using Advanced Technology Offer:• Ease of Use, Flexibility, Versatility• Fast, Easy Field Upgradeability
Users can Start with the Simplest Unit and Add Power Quality and/or Power Flow Options when and if They Want to Make Their Unit Almost into a Full Blown Powerline Disturbance Analyzer
36
Thank you for Viewing our Meter Adapter Recorder Presentation.
For More Information Contact Your Local Representative
or Call AVO International at 800-723-2861
www.avointl.com